Adding ET 200SP HA Safety Modules (6DL1136-6DA00-0PH1 / 6DL1136-6AA00-0PH1) to TIA Portal V17
1. Problem Statement
Engineers commissioning a SIMATIC ET 200SP HA head-end station under TIA Portal V17 cannot locate the fail-safe digital input module 6DL1136-6DA00-0PH1 (F-DI) or the fail-safe digital output module 6DL1136-6AA00-0PH1 (F-DQ) in the hardware catalog. The search returns no hits under Distributed I/O > ET 200SP HA > F-modules, and the modules cannot be inserted into the device configuration of the IM 155-6 PN HA interface module. This blocks Safety Integrated commissioning, blocks the safety signature assignment, and prevents project compilation.
The same issue affects every TIA Portal release that ships without the corresponding Hardware Support Package (HSP) for ET 200SP HA fail-safe modules. The catalog simply does not contain the article numbers, regardless of firmware selection on the IM 155-6 PN HA.
2. Affected Components and Software Versions
| Component | Article Number | Role |
|---|---|---|
| F-DI 16×24VDC HA | 6DL1136-6DA00-0PH1 | Fail-safe digital input module for ET 200SP HA |
| F-DQ 10×24VDC/2A HA | 6DL1136-6AA00-0PH1 | Fail-safe digital output module for ET 200SP HA |
| IM 155-6 PN HA | 6DL1155-6AU00-0PH1 / 6DL1155-6BU00-0PH1 | Head-end interface module for the ET 200SP HA station |
| TIA Portal | V17 (all updates up to V17 Update 8 verified) | Engineering framework — base catalog lacks F-modules for ET 200SP HA |
| STEP 7 Professional | V17 | Required subset of TIA Portal for ET 200SP HA configuration |
3. Root Cause Analysis
The two ET 200SP HA F-modules belong to a class of "distributed safety" I/O whose catalog entries are delivered outside the standard TIA Portal installation media. Three contributing factors explain the missing entries:
- Catalogue delivery channel. Siemens ships the device descriptions of safety modules through three parallel channels: (a) the main installation DVD, (b) Hardware Support Packages (HSP), and (c) GSD/GSDML files. TIA Portal V17 ships only the base catalog and a partial HSP set; the F-DI/F-DQ HA entries are not among them.
- Licensing restriction. The Siemens product note 109780933 states that safety-related configuration of ET 200SP HA F-modules is officially supported only through the PCS 7 process-control engineering environment combined with the optional S7-F-Systems library. A bare TIA Portal installation is therefore de-scoped from this subset.
- Catalog naming. Even after the modules are added, the user must navigate the correct filter path. F-modules are not listed under "ET 200SP HA > F-modules" until the corresponding HSP or GSDML has been installed and TIA Portal restarted.
The net result is identical from the user side: the modules are missing from the catalog and cannot be dragged into the device view.
4. Solution Overview — Three Independent Paths
| Method | Tool / File | Best for | Restrictions |
|---|---|---|---|
| 1. Hardware Support Package (HSP) | HSP for ET 200SP HA F-modules (TIA Portal V17 or later) | Standard TIA Portal users without PCS 7 | Requires the matching TIA Portal major version |
| 2. GSD/GSDML import | PROFINET GSDML file for ET 200SP HA F-modules | Multi-vendor PROFINET projects; already using GSDML on the station | Loses native TIA Portal diagnostic faceplates |
| 3. PCS 7 + S7-F-Systems library | PCS 7 V9.0 SP2 or later with S7-F-Systems | Process-control projects with Safety Integrated lifecycle | Requires PCS 7 license and S7-F-Systems license |
All three paths are sanctioned by Siemens for the ET 200SP HA F-module family; the choice depends on which other tools the plant has licensed.
5. Solution Method 1 — Install the Hardware Support Package (HSP)
The HSP is the cleanest path for engineers who do not own PCS 7. It re-introduces the missing catalog entries as native TIA Portal objects, preserving the integrated diagnostics, the parameter editor, and the safety signature workflow.
5.1 Prerequisites
- TIA Portal V17 (or later in the V17 line) installed with administrator rights.
- Local administrator account on the engineering station.
- HSP file downloaded from the Siemens Industry Online Support portal — search for the term "ET 200SP HA HSP TIA Portal V17" or navigate via support.industry.siemens.com.
5.2 Step-by-Step Procedure
- Close every running instance of TIA Portal (including any open project files).
- Start TIA Portal V17.
- Open the menu Options → Support Packages.
- In the "Support Packages" dialog, click Install support packages / HSP.
- Browse to the folder where the HSP file (
.zipor unpacked folder) is stored. - Select the HSP that contains the ET 200SP HA F-module descriptions and confirm with Install.
- Wait for the "Installation completed successfully" message — this typically takes 10–60 seconds.
- Restart TIA Portal completely. Catalog changes do not take effect until the application is relaunched.
- Re-open the project and navigate the hardware catalog: Distributed I/O → ET 200SP HA → F-modules.
- Confirm that both
6DL1136-6DA00-0PH1and6DL1136-6AA00-0PH1are now listed. - Drag the required F-module into a free slot of the ET 200SP HA station. The slot must respect the ET 200SP HA slot rules (F-modules are allowed from slot 1 onwards, after the IM).
6. Solution Method 2 — Import the GSD/GSDML File
If no HSP is available — for example when working in a locked-down engineering environment or when the project requires PROFINET interoperability with third-party controllers — the F-modules can be added through their PROFINET device description (GSDML).
6.1 Prerequisites
- GSDML file for ET 200SP HA F-modules, versioned against TIA Portal V17 or compatible. Available from the Siemens product support pages; the file is named
GSDML-Vx.xx-Siemens-ET200SP_HA-F-xxxxxx.xml. - TIA Portal V17 with administrator rights.
6.2 Step-by-Step Procedure
- Download the GSDML archive and unzip it to a known folder on the engineering station.
- Open TIA Portal V17 and the target project.
- Navigate to Options → Manage General Station Description Files (GSD).
- In the "Manage GSD" dialog, set the source path to the unzipped folder.
- Select the GSDML file and click Install.
- Wait for the import to complete; a progress bar indicates the parsing of XML, image, and bitmap assets.
- Close the dialog and restart TIA Portal.
- Open the Devices & Networks editor and drag an ET 200SP HA station from the catalog as usual.
- In the catalog tree, expand Other field devices → PROFINET IO → Sensors → Siemens AG → ET 200SP HA. The F-DI and F-DQ now appear as GSD-imported entries.
- Insert the modules into the ET 200SP HA slot list. Note: GSD-imported modules appear with their vendor device designation rather than the full Siemens article description.
7. Solution Method 3 — PCS 7 with S7-F-Systems Library
For process-control plants whose engineering toolchain is PCS 7 rather than TIA Portal, Siemens officially routes the configuration of ET 200SP HA F-modules through the PCS 7 environment plus the S7-F-Systems safety library. This is the configuration path sanctioned by the Siemens product note 109780933.
7.1 Prerequisites
- PCS 7 V9.0 SP2 or later (also valid on V9.1 and the corresponding SP levels).
- STEP 7 / S7-PCT inside the PCS 7 installation.
- S7-F-Systems library licensed and installed (delivery form: SIMATIC S7 F-Systems DVD or download package).
- F-modules physically wired with PROFIsafe addresses set on the IM 155-6 PN HA.
7.2 Step-by-Step Procedure
- Open the PCS 7 project and the relevant plant view.
- Add or select the ET 200SP HA head-end station in the HW Config equivalent (PCS 7 → Component View).
- Open the S7-F-Systems library and instantiate the F-Shutdown / F-Block building blocks corresponding to the application.
- Bind the F-block inputs/outputs to the F-DI / F-DQ slots added under the IM 155-6 PN HA.
- Assign the PROFIsafe addresses, the safety signature (CRC), and the F-monitoring time.
- Compile and download — the safety signature is enforced on the CPU side and the F-CPU will only accept modules whose PROFIsafe address matches.
This is the recommended configuration path for plants already running PCS 7 because the lifecycle of safety modules, including periodic proof tests, is tracked in the PCS 7 asset management.
8. Configuration Walkthrough — Sample Slot Map for ET 200SP HA
Once the F-modules are available in the catalog (any of the three methods), the slot structure of the ET 200SP HA station should resemble the table below. Slot 0 is always the IM 155-6 PN HA.
| Slot | Module | Article Number | Role |
|---|---|---|---|
| 0 | IM 155-6 PN HA | 6DL1155-6AU00-0PH1 | PROFINET interface |
| 1 | F-DI 16×24VDC HA | 6DL1136-6DA00-0PH1 | Fail-safe digital inputs (e.g., E-stop, guard door) |
| 2 | F-DQ 10×24VDC/2A HA | 6DL1136-6AA00-0PH1 | Fail-safe digital outputs (e.g., contactors, muting lamps) |
| 3 … n | Standard DI/DO/AI/AO | 6DL1x4x-xxx | Non-safety I/O |
9. Verification Procedure
- Module presence check. In the hardware catalog, expand ET 200SP HA > F-modules and confirm that both article numbers are listed.
- Slot consistency check. Compile the project. TIA Portal must report "No errors" and the slot list must be consistent with the physical module arrangement.
- PROFIsafe address assignment. Open the properties of each F-module, navigate to the PROFIsafe tab, and verify that a unique F-destination address (1–1023) has been assigned per module.
- Safety signature check. For TIA Portal/STEP 7 Safety Advanced: generate the safety program, then verify that the safety signature is calculated and stored in the project.
- Online diagnostic check. Download the configuration to the CPU and the IM 155-6 PN HA. In Online & Diagnostics, confirm that both F-modules report OK status, no channel faults, and the PROFIsafe communication is established.
- Forcing / passivation test. Briefly disconnect one F-DI channel and verify that the module reports the channel as passivated, the F-CPU raises the appropriate safety message, and the F-DQ executes the configured fail-safe reaction.
10. Troubleshooting Matrix
| Symptom | Likely Cause | Resolution |
|---|---|---|
| F-module not visible in catalog after HSP install | TIA Portal not restarted | Close all TIA Portal windows, restart via Start menu |
| HSP install fails with "Incompatible version" | HSP built for a different TIA Portal major version | Download the HSP matching the exact TIA Portal version (V17, V18, …) |
| GSDML installs but module greyed-out in slot | Slot type not allowed for F-modules on the IM 155-6 PN HA | Verify IM firmware supports F-modules; place F-modules in slots that allow safety I/O |
| Module visible, but F-CPU rejects it on download | PROFIsafe address mismatch | Re-set PROFIsafe address on the module (DIP switches or HW Config), recompile, re-download |
| Catalog still empty after restart | HSP installed under a different Windows user | Run TIA Portal "as Administrator" so HSP catalog is shared |
| PCS 7 path: F-block compiles with errors | S7-F-Systems library version mismatch | Update the F-library to the version bundled with PCS 7 SP level in use |
| GSD-installed module: no diagnostic faceplate | GSD does not include Siemens-curated diagnostics | Switch to HSP method if the integrated diagnostic is required |
11. Compatibility, Migration, and Lifecycle Notes
- TIA Portal version pairing. An HSP built for TIA Portal V18 cannot be installed on a V17 engineering station. Always match the HSP major version to the TIA Portal major version.
- Project portability. A project containing the F-modules (added through HSP or GSDML) on TIA Portal V17 can be upgraded to V18/V19 as long as the matching HSP is installed on the target version. The slots, parameters, and safety signatures are preserved through the project upgrade.
- IM firmware dependency. The IM 155-6 PN HA must run a firmware version that recognises the F-modules. Older IM firmware (prior to V6.x) may not enumerate F-modules even when the catalog lists them.
- Safety lifecycle. Both F-module article numbers are subject to the standard Siemens Safety Integrated lifecycle. Proof-test intervals and firmware updates must be tracked in the plant's safety management system.
- Mixing standard and F-modules. F-modules can coexist with standard DI/DO/AI/AO on the same ET 200SP HA station as long as the IM 155-6 PN HA supports the total module count and the slot width budget.
12. Field-Commissioning Tips
- Document the PROFIsafe address plan. Maintain a sheet per station listing F-destination address, slot, module serial number, and the assigned safe function.
- Lock the HSP version. Once a project is signed off, freeze the HSP version. A later HSP update can subtly change module parameter defaults and trigger unintended safety re-validation.
- Validate after every firmware update. After an IM firmware update, perform a full passivation test on every F-channel before returning the line to production.
- Backup the safety program separately. The safety signature depends on the compiled F-library version. Keep the exact STEP 7 Safety / S7-F-Systems library version alongside the safety program backup.
- Verify on a real rack. The GSDML path may compile in the offline project but fail on the physical rack if the IM firmware does not recognise the F-module variant. Always verify against real hardware or the SIMATIC S7-PLCSIM Advanced instance with Safety licence.
13. References to Official Documentation
For deeper reading, consult the following Siemens Industry Online Support entries:
- Product Note 109780933 — Configuration of ET 200SP HA F-modules via PCS 7 + S7-F-Systems library
- Siemens Industry Online Support — entry page for HSP, GSDML, and firmware downloads
- TIA Portal Documentation Portal — ET 200SP HA manual collection (HSP installation procedure)
14. Frequently Asked Questions
Why are the ET 200SP HA F-modules missing from the TIA Portal V17 catalog?
The base TIA Portal V17 installation only ships the standard ET 200SP HA catalog. The F-module device descriptions are delivered separately through an HSP, a GSDML file, or via PCS 7 with the S7-F-Systems library. The catalog path ET 200SP HA > F-modules is empty until one of those three sources is installed.
Which method is officially supported by Siemens for ET 200SP HA F-modules?
Product note 109780933 states that the configuration of ET 200SP HA F-modules is officially supported through PCS 7 combined with the S7-F-Systems library. For TIA Portal users without PCS 7, the HSP or GSDML paths are the practical alternatives.
Can I install an HSP built for TIA Portal V18 onto a V17 engineering station?
No. HSPs are version-locked to the TIA Portal major version. Download the HSP that matches your installed TIA Portal version — "HSP for TIA Portal V17" for V17, "HSP for TIA Portal V18" for V18, and so on.
After HSP installation, do I have to restart TIA Portal?
Yes. TIA Portal reads the installed HSPs only at startup. Restart the application fully — closing the project window is not sufficient; exit the program and relaunch via the Start menu or shortcut.
Will GSDML-installed F-modules show the Siemens-integrated diagnostic faceplate?
No. GSD-imported modules appear in the catalog under Other field devices and use generic PROFINET diagnostics. The Siemens-curated diagnostic faceplate and the alarm text are only available when the module is installed through the HSP path.
What PROFIsafe address range should I use for the F-modules?
Each F-module on a PROFINET subnet requires a unique F-destination address in the range 1–1023. Avoid duplicating addresses across F-modules on the same PROFINET network; the F-CPU will reject conflicting addresses at download time.