B&R ARSim FileIO Error 20708: Troubleshooting AS6 Guide

Jason IP2 min read
B&R AutomationOther TopicTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

After upgrading an ARSim project from Automation Studio 4.x to Automation Studio 6, FileIO access that targets C: can fail even when the file exists. The reported AS6 and Runtime 6.2.1 case returns 20708 (fiERR_FILE_NOT_FOUND) from FileInfo. A related AS6.2 case returns 20709 from DirCreate.

Identify the AS6 ARSim path change

Automation Studio 6 ARSim no longer supports using C: as it was used by the affected Automation Studio 4.x projects. During simulation, access the simulation user location through the USER file device and its USER_PATH instead of addressing C: directly.

Operation Observed AS6 result Required correction
FileInfo against C: 20708 / fiERR_FILE_NOT_FOUND Use the USER file device in ARSim.
DirCreate through a device mapped to a nonexistent folder 20709 Create the parent folder through UserPartition before using the dependent device.

Create the directory through the valid device

A file device that points into AlarmX is not valid until that directory exists. Create the directory through UserPartition; do not call DirCreate through the device whose target directory has not yet been created.

DirCreate_0(
    enable := TRUE,
    pDevice := ADR('UserPartition'),
    pName := ADR('/AlarmX')
);

Apply the correction in ARSim

  1. Replace direct C: access in the simulation path with the USER file device.
  2. Place the test file under the directory referenced by the active ARSim USER_PATH.
  3. If the application requires a subdirectory such as /AlarmX, create it first with DirCreate using UserPartition.
  4. Only after the directory exists, use any file device configured to point into that directory.

Verify the active configuration

Run the same FileInfo request after moving the file to USER_PATH and changing the file device to USER. Confirm that 20708 no longer occurs. For directory creation, confirm that the folder appears before invoking operations through a device mapped beneath it and that DirCreate no longer returns 20709.

The ARSim USER_PATH can depend on the selected PLC configuration or working path. If an external HMI must copy files to that location, either configure a constant simulation destination or obtain the active USER_PATH and communicate it to the HMI. The evidence does not specify a supported programmatic interface for reading that value.

FAQ

Why does B&R FileInfo return error 20708 in AS6 ARSim?

20708 is reported as fiERR_FILE_NOT_FOUND when the upgraded simulation still targets C:. Use the USER file device and place the file under the active USER_PATH.

Why does DirCreate return 20709 after upgrading to AS6?

The reported failure occurred when directory creation used a file device whose target folder did not yet exist. Create the folder through UserPartition first, such as pName := ADR('/AlarmX').

Can an ARSim HMI use one fixed USER_PATH for every configuration?

The reported USER_PATH depends on the PLC configuration or working path unless the simulation destination is configured consistently. Otherwise, the HMI must receive the active path; the evidence does not identify a programmatic read method.