The 1-inch branch flow changes when the 2-inch branch opens, even though the pump previously transferred about 100 gpm through the 3-inch line. Treat the reported flow and 40 psig discharge pressure as operating-point measurements, then solve the pump, common pipe, branch losses, valve positions, elevations, and 7 psig receiving-tank boundaries as one hydraulic network.
Required readings and boundary state
Before anything else, confirm the exact valve lineup and operating state to be calculated. A network solution applies to one defined state; opening or throttling either automated valve changes the system resistance and can move the pump to a different flow and discharge pressure.
- Record whether the 1-inch and 2-inch automated valves are fully open, modulating, or at repeatable fixed positions. Obtain each control valve flow relation or operating
Cv. A resistance coefficient for a fully open valve cannot represent a throttled valve. - Measure pump suction pressure and pump discharge pressure while both branches are in the target lineup. Record gauge locations and elevations. The reported 40 psig is useful only when its location and valve state match the case being solved.
- Define the outlet boundary for each receiving tank. The tanks are maintained at 7 psig, but branch backpressure must also include elevation and, for a submerged connection, the liquid head above the entry point.
- Confirm the common 3-inch pipe length of 100 ft, the 2-inch branch length of 39 ft, and the 1-inch branch length of 48 ft. Use actual inside diameters rather than nominal pipe sizes.
- Inventory fittings, strainers, reducers, valves, and discharge connections by branch. Keep their loss coefficients assigned to the pipe velocity at the component location.
- Obtain acetone viscosity at operating temperature and confirm that the stated density of
49 lb/ft³applies to the transferred liquid. Density converts pressure to head; viscosity and roughness determine the friction factor.
Do not move on until every pressure is tied to a physical node and every elevation uses the same datum.
Pump-boundary decision
The first decision is whether the calculation must reproduce a measured snapshot or predict operation under other valve conditions.
| Available information | Meaning | Next check |
|---|---|---|
| 40 psig measured at the pump outlet during the target valve lineup | Use it as the downstream inlet boundary for a snapshot calculation. | Calculate common-line loss to obtain junction pressure, then solve both branches. |
| A controller actively maintains 40 psig | The control element changes pump speed or valve resistance to hold pressure. | Include the controller’s final element and verify it has sufficient operating range. |
| 40 psig came from another lineup or operating time | It is not the discharge boundary for the requested case. | Use the pump differential-head-versus-flow curve with measured suction conditions. |
| Only the earlier 100 gpm tank-volume result is known | It identifies one previous operating point, not a fixed flow after branches were added. | Measure the new pressures or obtain the pump curve before predicting the split. |
A centrifugal pump normally supplies differential head as a function of total flow. It does not independently impose both 100 gpm and 40 psig. Adding parallel branches lowers or reshapes system resistance, so the intersection between the pump curve and system curve moves.
Do not calculate suction pressure by simply subtracting discharge pressure from total dynamic head. Apply the pump energy balance using consistent pressure, elevation, and velocity-head terms. Also keep suction pressure separate from the pump’s required net positive suction head: compare calculated available NPSH with the manufacturer’s required value at the solved flow.
Pipe and component loss functions
A friction-loss result cannot be correlated with flow unless it is expressed as a function of flow. For each uniform pipe segment, calculate velocity from V = Q/A and pipe-friction head from h_f = f(L/D)(V²/2g). Calculate fitting loss from h_m = ΣK(V²/2g). Determine the friction factor from Reynolds number, relative roughness, and the selected friction correlation.
Build three loss functions:
-
R3(Q3)for the 100 ft, 3-inch common line from the pump discharge node to the split. -
R2(Q2)for the 39 ft, 2-inch branch from the split to its receiving-tank node. -
R1(Q1)for the 48 ft, 1-inch branch from the split to its receiving-tank node.
Each function must include pipe friction, its own fittings and strainer losses, control-valve pressure drop, and elevation change. Because velocity varies with diameter, do not add all fitting coefficients and apply one network-wide velocity.
Use 49 lb/ft³ only for pressure-to-head conversion after confirming the process condition. A pressure difference represents more feet of acetone head than the same pressure difference represents for water. Keep the complete calculation in either pressure or head units and convert once; mixing psi loss and feet of head without density conversion produces a false operating point.
Junction and outlet checks
The split imposes two non-negotiable network conditions: all connected pipes share one junction pressure, and flow is conserved at the junction. With no storage or third takeoff at the split, use Q3 = Q1 + Q2.
- Calculate each effective outlet head from the 7 psig tank pressure, pipe-outlet elevation, tank liquid level when relevant, and the selected terminal-loss convention.
- Guess a junction head
Hj. - Solve
Hj − Hout,1 = R1(Q1)for the 1-inch branch. - Solve
Hj − Hout,2 = R2(Q2)for the 2-inch branch. - Add the branch flows to obtain
Q3. - Calculate the 3-inch common-line loss at that total flow and determine the pump-discharge head required to support the guessed junction head.
Do not split the reported 100 gpm in proportion to nominal pipe area. Equal junction pressure does not create equal branch velocity or an area-based flow division. The 1-inch branch is longer than the 2-inch branch and has a smaller flow area; its valve, fittings, elevation, and outlet condition further determine its share.
Pump and system iteration
For a predictive calculation, close the network against the pump curve. At each trial total flow, obtain pump differential head from the curve, add it to the measured suction-side total head, and compare the resulting discharge head with the head required by the common pipe and both branches.
- Choose a trial junction head and solve both branch flows.
- Set common-pipe flow equal to their sum.
- Calculate required pump discharge head from junction head plus
R3(Q3). - Read available pump differential head at
Q3and combine it with suction total head. - If available discharge head exceeds required head, increase the trial flow or junction head. If it is lower, decrease the trial value.
- Repeat until the pump balance, both branch balances, and
Q3 = Q1 + Q2close within the project’s calculation tolerance.
If a pressure controller holds the discharge at 40 psig, replace the uncontrolled pump boundary with the maintained pressure boundary and calculate the required control action. Then check the valve position or pump speed against its permitted operating range. A mathematical solution outside that range is not a realizable operating point.
Symptoms and deciding measurements
| Observed symptom | Likely calculation or field cause | Deciding measurement |
|---|---|---|
| The old 100 gpm value is not reproduced after opening the branches | The added paths changed the system curve and pump operating point. | Measure simultaneous suction pressure, discharge pressure, and total tank-volume change. |
| Losses were calculated but branch flows remain unknown | Loss was treated as a fixed value instead of R(Q). |
Recalculate velocity, Reynolds number, friction factor, and valve loss at every trial flow. |
| Both tanks read 7 psig but receive different flows | The branches have different diameters, lengths, component losses, elevations, or liquid heads. | Measure junction pressure and each tank connection’s effective outlet pressure. |
| The model overpredicts the 1-inch wash flow | The automated valve position, strainer loss, inside diameter, or fitting inventory is wrong. | Record valve position and pressures immediately upstream and downstream of the branch. |
| A 40 psig boundary gives inconsistent results | The reading came from a different lineup, elevation, or gauge location, or the pump pressure moved with flow. | Repeat the reading during simultaneous 1-inch and 2-inch operation. |
| Calculated branch flows do not add to measured total flow | Tank level conversion, timing, an unlisted path, or transient inventory is affecting the test. | Run a steady timed collection with all other paths positively isolated. |
Resolving procedure and field verification
- Place the system in the intended simultaneous-transfer state and wait for pump discharge pressure, tank pressures, and valve positions to stop drifting.
- Record suction pressure, pump discharge pressure, junction pressure if a tapping exists, both 7 psig tank pressures, liquid levels, valve positions, and elevations.
- Time the receiving-tank volume changes. Calculate each branch flow as
Q = ΔVolume/ΔTime, using the tank calibration rather than raw level change when tank area varies with level. - Compare the measured branch flows with the hydraulic solution. Recalculate velocities separately as
V1 = Q1/A1,V2 = Q2/A2, andV3 = (Q1 + Q2)/A3. - Use measured pressure drops to localize disagreement. A common-line mismatch points to the 3-inch model or pump boundary; a single-branch mismatch points to that branch’s valve, strainer, fittings, diameter, elevation, or outlet head.
- Update only the input demonstrated by the measurement, solve again, and repeat the timed tank test with the same valve lineup.
Frequently asked questions
Can I divide 100 gpm between the 1-inch and 2-inch pipes by area?
No. The 48 ft, 1-inch branch and 39 ft, 2-inch branch share junction pressure but have different nonlinear resistance; solve each branch loss equation and require their flows to sum to the 3-inch flow.
Can I use 40 psig as a constant pump discharge pressure?
Use 40 psig as a boundary only when it is measured or actively maintained during the exact valve lineup being analyzed. Otherwise use the pump differential-head curve, suction total head, and calculated system resistance.
Does 7 psig tank pressure completely define branch backpressure?
No. Add the pipe-to-tank elevation difference and any liquid head above a submerged inlet, using one consistent datum. Final verification is a steady timed tank-volume test in which measured branch flows sum to measured 3-inch flow and reproduce the recorded pressure readings.