After the flow, tube spacing, thermal properties, and boundary loads are entered on one consistent basis, the calculation separates hydraulic capacity from slab conductance and predicts both coolant temperature rise and ice-surface capacity. A single heat-transfer coefficient cannot describe the entire assembly.
Design Inputs and Boundary Conditions
Before anything else, confirm the geometry and operating conditions. The stated case uses 1-inch-ID polyethylene pipe embedded in a 5-inch concrete floor, with 50% ethylene glycol entering at 18°F. The pipe crown is 1.75 in. below the concrete surface. The proposed comparison changes center spacing from 4 in. to 3.5 in.; the initial flow is 5 US gpm.
| Input | Stated value | Required clarification |
|---|---|---|
| Pipe | 1-inch ID polyethylene | Outside diameter and wall conductivity |
| Slab | 5 inches thick | Concrete conductivity and pipe position relative to slab bottom |
| Pipe cover | 1.75 inches from pipe crown to surface | Confirm this is not centerline depth |
| Coolant | 50% ethylene glycol at 18°F inlet | Density, heat capacity, conductivity, viscosity, and basis of concentration |
| Flow | 5 US gpm | Flow per tube, per circuit, or total system flow |
| Spacing | 4 inches; proposed 3.5 inches | Confirm centerline-to-centerline spacing |
| Ice | Proposed 1.5-inch layer | Ice conductivity and target surface temperature |
| Air | 60°F dry bulb, 45°F wet bulb | Air velocity and radiation environment |
| Concrete | 25°F reported temperature | Measurement location and operating state |
| Ground | Not stated | Ground temperature and insulation construction |
Do not move on until circuit length, number of parallel circuits, supply/return routing, and every missing property are taken from drawings, measured, or read from the applicable property table at the operating concentration and temperature.
Refrigeration-Load Definition
Calculate the required surface duty before selecting spacing or flow. During ice formation, the refrigeration system must remove the sprayed water's sensible heat, its latent heat of freezing, and any ongoing heat entering from the room and ground. During holding operation, the water-freezing term may fall, but convection, radiation, moisture deposition, lighting, occupants, and ground heat remain.
For a water mass m, write the pull-down energy as:
Q_water = m[c_p,water(T_initial − T_freeze) + h_fusion + c_p,ice(T_freeze − T_final)]
Include the final ice-cooling term only when the design requires cooling below the freezing point. Divide total energy by the permitted freezing time to obtain an average refrigeration rate, then add simultaneous surface and ground loads. Use the 2006 ASHRAE Refrigeration Handbook, Chapter 35, as a rink-load calculation reference and verify the selected design conditions against the project requirements.
The stated 60°F dry-bulb and 45°F wet-bulb conditions help define air-side loads, but air velocity and surrounding surface temperatures are also needed. Lighting and other warm surfaces raise radiant load even when the air temperature remains unchanged.
Check: express the final requirement as heat rate and surface heat flux, both with an explicit time basis. Do not proceed with a value stated only as Btu/ft².
Coolant Flow and Circuit Capacity
Set flow from the required heat pickup and the allowable coolant temperature rise. For one circuit:
Q_circuit = m_dot × c_p × (T_return − T_supply)
with m_dot = density × volumetric flow. Obtain density and specific heat for 50% ethylene glycol at the circuit's mean temperature. Do not substitute water properties; glycol concentration and low temperature materially change heat capacity and viscosity.
- Assign the design heat load to each circuit from its served slab area.
- Select an allowable supply-to-return temperature rise from the refrigeration and surface-uniformity requirements.
- Calculate the required mass flow, then convert it to volumetric flow using glycol density.
- Calculate velocity, Reynolds number, and internal convection from the actual pipe inside diameter and glycol properties.
- Calculate circuit pressure loss, including pipe, fittings, headers, and balancing devices.
- Compare total system flow and head with the pump curve and the chiller's permitted evaporator flow range.
Reducing flow increases coolant temperature rise for the same heat load. It can also reduce internal convection when the flow approaches a less effective regime. Excess flow may improve internal convection only modestly while sharply increasing pumping power and pressure loss.
A reported operating reference used approximately 3 US gpm per tube, with nominal coolant temperatures of 18°F entering and above 20°F leaving. That is a comparison point, not a design setting; circuit length, glycol properties, and heat duty decide whether it transfers to this installation. Lowering circulation can also drive a refrigeration system toward low evaporator pressure or low leaving-solution-temperature limits. Do not change protective settings to compensate for an unverified flow selection.
Check: at the selected flow, calculated circuit heat pickup must equal its assigned load, and measured or predicted pressure drop must lie on the pump operating curve.
Tube Spacing and Slab Conductance
Changing spacing from 4 in. to 3.5 in. places more tube length under each unit of floor area and shortens the lateral conduction path between adjacent pipes. It therefore raises area-based heat-transfer capacity and reduces the warm stripe midway between tubes. It does not proportionally increase the internal pipe coefficient, which is governed mainly by coolant properties, tube diameter, and flow.
Treat the slab as a two-dimensional conduction field. A one-dimensional calculation using only the 1.75-in. cover misses lateral spreading resistance and the interaction between neighboring tubes. Model a repeating section extending halfway to the adjacent tube on each side. Include the pipe wall, concrete above and below the tube, the ice layer, surface boundary conditions, and any bottom insulation or ground resistance.
Reported comparison values were 42 Btu/ft² at 4-in. centers and 47 Btu/ft² at 3.5-in. centers for 1-in. ice and approximately 3 US gpm per tube. Their time basis was not stated, so they cannot be entered as heat fluxes until that basis is identified. They also do not directly apply to the proposed 1.5-in. ice layer. Thicker ice adds conduction resistance and generally requires a colder coolant condition for the same surface load.
Check: compare both spacings at identical coolant temperatures, flow basis, ice thickness, concrete properties, and room and ground boundaries. Accept a spacing only after both average heat flux and maximum midpoint surface temperature meet the design target.
Composite Heat-Transfer Calculation
Calculate component resistances before reporting an overall coefficient. On a consistent reference-area basis, the thermal path contains internal coolant convection, polyethylene wall conduction, concrete spreading, ice conduction, and the surface boundary. A conceptual resistance expression is:
1/U = R_internal + R_pipe + R_concrete,2D + R_ice + R_surface
The resistances cannot be added until each is converted to the same reference area. For the cylindrical pipe terms, use the actual inside and outside diameters. Obtain internal convection from the calculated flow regime and glycol properties. Obtain slab spreading resistance from a validated embedded-tube correlation or a two-dimensional numerical model.
- Solve the hydraulic model to obtain local coolant temperature along the circuit.
- Apply that temperature to successive slab sections rather than treating the entire tube as being at
18°F. - Solve conduction through the pipe, concrete, and ice to the surface.
- Apply convection, radiation, and moisture-related loads at the ice surface and ground or insulation conditions at the slab bottom.
- Iterate until the heat removed by the coolant equals the heat crossing the slab boundaries.
Check: the model's coolant-side heat gain must match the integrated slab heat flow within the chosen numerical tolerance, and the predicted return temperature must follow from the same energy balance.
End-to-End Commissioning Verification
- Confirm glycol concentration and record supply and return temperatures with calibrated sensors.
- Measure total flow and individual circuit flow; verify that the reported
5 US gpmbasis matches the design interpretation. - Record pump differential pressure and compare it with calculated system resistance.
- Map concrete or ice-surface temperature above a tube and midway between tubes. A large repeating temperature difference points to excessive spacing, inadequate cover conduction, circuit imbalance, or insufficient coolant capacity.
- Record room dry-bulb, wet-bulb, air movement, lighting state, and ground-side conditions during the test.
- Calculate measured refrigeration pickup from glycol mass flow, specific heat, and supply/return temperature difference, then compare it with the modeled slab load.
Do not move on until flow, temperature rise, pump head, surface-temperature pattern, and calculated heat balance agree under one documented operating condition.
Frequently Asked Questions
How do I calculate heat transfer from buried glycol pipes?
Calculate coolant heat pickup with Q = m_dot c_p ΔT, then solve the pipe wall, two-dimensional concrete spreading, ice conduction, and surface boundary on a common area basis. Confirm the result by matching predicted return temperature to the coolant energy balance.
How do I compare 4-inch and 3.5-inch pipe spacing?
Run both geometries with the same pipe dimensions, cover, glycol properties, circuit temperatures, ice thickness, and boundary loads. Compare average heat flux and the surface temperature midway between tubes.
How do I select glycol flow per circuit?
Divide the assigned circuit load by c_p ΔT to obtain mass flow, convert with glycol density, and check velocity, flow regime, pressure loss, pump capacity, and chiller flow limits. Treat 3 US gpm per tube only as the reported comparison condition.
How do I account for 1.5 inches of ice?
Add the ice layer as a conduction resistance using its actual thickness and thermal conductivity. Do not apply values associated with 1-in. ice without recalculating the surface temperature and coolant requirement.
How do I verify the buried-pipe model in operation?
Measure circuit flow, glycol concentration, supply and return temperatures, pump differential pressure, and surface temperatures above and between tubes. The final verification is agreement between m_dot c_p ΔT, integrated slab heat flow, and the measured surface-temperature map.