Across a well-insulated 1 m² duct carrying air at 10 m/s and 20 °C, a 1000 Pa obstruction changes the air temperature by about 0.002 °C for real air and by zero for an ideal gas. The +0.83 °C figure from ΔP·Q/(ṁ·cp) is wrong for a gas. The same method predicts +414 °C for a 5 atm drop, where the Joule-Thomson coefficient gives cooling of roughly 1–2 °C. The deciding quantity is enthalpy: an adiabatic obstruction with no shaft work conserves stagnation enthalpy, and the enthalpy of an ideal gas depends on temperature alone.
Reading the three conflicting results
Three methods give +414 °C, −2 °C and 3.33 °C for the same 6 atm to 1 atm restriction because each carries a different hidden assumption. Only the enthalpy-based methods are valid for a flowing gas through an insulated restriction.
Input check before comparing methods: the source writes the flow as 10 m3/2, which reads as 10 m³/s (1 m² × 10 m/s). The stated 1.2 kg/m³ matches air at about 1 atm absolute and 20 °C (ρ = P/(R·T) with R = 287 J/kg·K gives 1.204 kg/m³, R being an assumed air constant). The upstream pressure is never stated, so fix absolute pressure at both stations before any calculation. Mass flow is ṁ = 1.2 × 1 × 10 = 12 kg/s.
| Approach | Reported result | Embedded assumption | Status for an insulated duct with no shaft work |
|---|---|---|---|
Power equation ΔP·Q/(ṁ·cp)
|
+0.83 °C (1000 Pa); +414 °C (5 atm) | All dissipated pressure energy becomes internal energy; flow work does not change (incompressible fluid) | Valid for liquids. Wrong for gases, where expansion offsets the dissipation. |
Ideal gas ratio 6/20 = 1/x
|
3.33 °C | Pressure proportional to temperature (constant volume), temperature taken in °C | Invalid: the gas expands, temperature must be in kelvin, and a flowing stream is not a closed constant-volume system. |
Throttling, ideal gas (h = h(T)) |
0 °C change | Adiabatic, no work, enthalpy depends on T only | Correct limit. |
| Joule-Thomson, real air | about −2 °C for 6 atm to 1 atm | Constant enthalpy, real-gas deviation from ideal | Correct method for the small residual. |
Enthalpy balance across the obstruction
An insulated obstruction with no moving parts is a steady-flow control volume with zero heat transfer and zero shaft work, so h1 + V1²/2 = h2 + V2²/2. The obstruction is not a turbine and does not transmit shaft work across the boundary. Insulation removes heat transfer. No energy leaves the stream, which is why a temperature drop from "lost energy" does not occur.
The 10 kW in Q·ΔP = 10 m³/s × 1000 Pa is mechanical energy dissipated by turbulence. It does not appear as extra sensible heat, because enthalpy is h = u + p/ρ and the flow-work term p/ρ falls as the internal energy rises. The general relation is:
dh = cp·dT + [ v − T·(∂v/∂T)p ]·dp
- Ideal gas:
v = R·T/p, so the bracket equalsv − v = 0. Constanthmeans constantT. - Incompressible fluid:
(∂v/∂T)p ≈ 0, the bracket equalsv, andΔT = ΔP/(ρ·c). This is the form of the power equation. With the source numbers it is1000/(1.2 × 1005) = 0.829 K, valid for a liquid and wrong for air.
The power equation does apply where shaft work crosses the boundary, such as a fan or blower in the control volume. There the shaft power delivered to the air enters the balance as ΔT = P_shaft/(ṁ·cp). A passive restriction between two stations delivers no shaft power.
Joule-Thomson correction for real air
The Joule-Thomson coefficient μJT = (∂T/∂P)h = −[v − T·(∂v/∂T)p]/cp is exactly zero for an ideal gas, so any nonzero value measures the departure of the real gas from ideality. Air at 20 °C has μJT ≈ 0.2 °C/atm, a positive value, so air cools on throttling at room temperature.
| Quantity | Value for this duct | Where to read or how to derive |
|---|---|---|
| Mass flow ṁ | 12 kg/s |
ρ·A·V with the stated density |
Mechanical dissipation Q·ΔP
|
10 kW (1000 Pa); 5000 kW (about 500 000 Pa) | Not a heating rate for a gas |
| Power-equation result | 0.83 K; 414 K | Incompressible-fluid answer, not applicable to air |
| Pressure drop in atm | 1000 Pa = 0.00987 atm | Divide by 101 325 Pa/atm |
| JT cooling, 1000 Pa | about 0.002 °C | 0.2 °C/atm × 0.00987 atm |
| JT cooling, 5 atm | about 1 °C constant-μ estimate; about 2 °C quoted for 6 atm to 1 atm | μJT varies with T and P; read h(T,P) from a real-gas property library or enthalpy table |
| Dynamic temperature at 10 m/s | 0.05 K | V²/(2·cp) = 100/2010 |
For a small ΔP, ΔT = μJT·ΔP is sufficient. For a multi-atmosphere drop, hold enthalpy constant between the two states and solve for the downstream temperature from real-gas enthalpy data, because μJT is not constant across the range.
Choked flow in the 6 atm to 1 atm case
A 6:1 pressure ratio exceeds the critical ratio for air, so the flow through the obstruction chokes. With γ = 1.4 (assumed for air), p*/p0 = (2/(γ+1))^(γ/(γ−1)) = 0.528, which places the choke at about 3.2 atm from a 6 atm upstream. A shock or pressure discontinuity forms downstream of the throat, and static temperature swings well below the stagnation value in the expansion jet before mixing restores it. The enthalpy balance conserves stagnation enthalpy, so the outlet temperature is read after the jet has mixed and the velocity profile has recovered.
The 5 atm case is also not the 1000 Pa case scaled up. The drop is about 500 times larger, and the stated 10 m/s and 1.2 kg/m³ cannot hold at both stations. At 6 atm and 20 °C the density is roughly 7.2 kg/m³ (proportional to absolute pressure), so 12 kg/s in 1 m² runs at about 1.7 m/s upstream. The kinetic-energy term ΔV²/2 ≈ 49 J/kg is still only about 0.05 K.
A reversible, work-extracting expansion gives a different bound: T2 = T1·(P2/P1)^((γ−1)/γ) = 293.15 K × (1/6)^0.2857 ≈ 176 K (about −97 °C). Throttling extracts no work, so it does not follow this line. The 6/20 = 1/x ratio fails even as a constant-volume estimate: in kelvin it gives 293.15/6 = 48.9 K, which shows a closed constant-volume relation cannot describe a flowing, expanding gas.
Procedure for the temperature change across a duct obstruction
- Record absolute upstream and downstream pressure, upstream temperature, and gas composition. Convert gauge readings to absolute.
- Compute density at each station from
ρ = P/(R·T)and the velocity at each station fromV = ṁ/(ρ·A). - Draw the control volume from the upstream station to a downstream station past the mixing length. List every boundary crossing: shaft work (none for a passive obstruction, nonzero if a fan is inside), heat transfer (zero if insulated, otherwise estimate it), and mass flow.
- Write
h1 + V1²/2 = h2 + V2²/2and evaluate the kinetic-energy difference. For 1000 Pa near 1 atm it is about 1 J/kg (about 0.001 K); this assumes upstream pressure near 1 atm because the source omits it. - For an ideal gas set
T2 = T1after correcting for the kinetic term. For real air useΔT = μJT·ΔPat small ΔP, or the constant-enthalpy solution from real-gas property data at large ΔP. - If
P2/P1is below the critical ratio (about 0.528 for γ = 1.4), treat the obstruction as choked and reference stagnation properties, then recheck the density and velocity at each station. - Add heat gain or loss through the duct wall and any fan or motor heat separately as boundary terms; do not fold them into the throttling term.
Expected magnitudes and sensor limits
An expected 0.002 °C change across a 1000 Pa obstruction sits far below the accuracy of a duct temperature sensor. Read the sensor accuracy class, resolution, and self-heating in its datasheet and compare against the calculated ΔT before trusting any measured difference.
- Compare the calculated
ΔTagainst the stated accuracy of both sensors. WhenΔTis smaller, no measurement across the obstruction can confirm the calculation. - Take a baseline with the obstruction removed or fully open at the same flow; any reading difference at zero restriction is sensor offset, stratification, or wall heat exchange.
- Swap the two sensor positions to separate sensor offset from real air temperature difference.
- Use total (stagnation) temperature comparisons, or correct the static reading with the dynamic term (0.05 K at 10 m/s), when velocities differ between stations.
- Check duct insulation and ambient gradient. Heat exchange through the wall of a few tens of watts is large compared with the JT effect at 1000 Pa.
- For the multi-atmosphere case, compare the measured downstream temperature with the constant-enthalpy real-gas prediction, allowing for the choked-flow mixing length.
Recurring calculation and measurement pitfalls
- Applying
ΔP·Q/(ṁ·cp)to gas throttling. It reproduces the incompressible-fluid answer and overpredicts by orders of magnitude for the 5 atm case. - Using °C in gas-law ratios. Convert to kelvin, and remember
P ∝ Tholds only at constant volume. - Treating the ideal gas law as a state equation that fixes T from P alone. It ties P, V and T together; the process path (throttling, isentropic, isochoric) fixes the outcome.
- Omitting the upstream absolute pressure. Density stated without pressure cannot define both stations.
- Holding μJT constant over a multi-atmosphere drop. Use enthalpy data or integrate.
- Ignoring choked flow above the critical pressure ratio.
- Mixing up throttling with fan work. Fan shaft power heats the stream as
P_shaft/(ṁ·cp); a passive restriction does not.
FAQ
How do I calculate the temperature change across a damper or orifice in a duct?
Write the steady-flow energy balance h1 + V1²/2 = h2 + V2²/2 with no shaft work and no heat transfer. For ideal-gas air the static temperature change is only the small kinetic-energy correction, and for real air add μJT·ΔP with about 0.2 °C/atm at 20 °C.
How do I know when the Joule-Thomson effect matters for air in a duct?
Convert ΔP to atm and multiply by μJT: 1000 Pa is 0.00987 atm and gives about 0.002 °C, which is below typical duct sensor accuracy. It matters at multi-atmosphere drops such as 6 atm to 1 atm, where roughly 1–2 °C of cooling appears.
How do I account for fan heat separately from throttling in a duct temperature calculation?
Add the shaft power delivered to the air as a boundary term, ΔT = P_shaft/(ṁ·cp), and treat the obstruction with the enthalpy balance. Never use Q·ΔP across a passive restriction as a heat input to the stream.
How do I decide when to stop calculating and escalate to official support?
Stop when the pressure ratio exceeds the critical ratio, when the pressure drop reaches multiple atmospheres, or when the expected ΔT is below sensor accuracy. Then take the choked-flow or thermal-measurement question to the damper, valve, or sensor manufacturer's official application support with absolute pressures, temperatures, flow, and sensor specifications.