Can an AP1100 Be Simple Apparatus in a Zone 1 IS Loop?

Patricia Callen6 min read
Other ManufacturerSafety SystemsTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

A powered multichannel thermocouple transmitter cannot be classified as simple apparatus merely because its 4–20 mA circuits pass through intrinsic-safety barriers. Treat the AP1100 as active field equipment until its hazardous-area certificate, entity parameters, approved control drawing, and channel architecture establish otherwise. Keep the thermocouples and compensation RTD as separate devices in the assessment; their possible treatment as simple apparatus does not extend to the transmitter.

How should the symptoms be read?

The immediate symptom is a loop calculation containing cable and barrier parameters but no parameters for the AP1100, 17 thermocouples, or plate-temperature RTD. That omission makes the calculation incomplete unless the governing code permits each omitted device to be documented as simple apparatus.

Look at the signal chain first. Each thermocouple generates a low-level voltage, the transmitter measures it, applies cold-junction or plate-temperature compensation, converts the result, and drives an individual 4–20 mA signal toward the control panel. A wrong value can originate before, inside, or after the transmitter.

Signal Source Wrong-value symptom
Thermocouple voltage One of 17 field thermocouples through up to 20 m of compensation cable Offset, reversed response, noisy temperature, or a value driven upscale or downscale by an open circuit
Plate-temperature measurement RTD mounted with the AP1100 in JB1 Several channels shift together because compensation uses the wrong terminal temperature
Conditioned measurement AP1100 input, compensation, and conversion electronics One channel or multiple channels disagree with applied test signals
4–20 mA output Individual transmitter channel through the barrier and approximately 150 m of multipair cable Control-panel reading differs from local current or changes with loop loading

Process accuracy and explosion protection are different decisions. Correct readings do not prove an intrinsically safe installation, and tuning or scaling changes cannot correct missing hazardous-area documentation.

Why does the transmitter break the simple-apparatus argument?

Simple apparatus is generally limited to devices whose electrical behavior and energy storage fit the definition in the governing hazardous-area code. A thermocouple is a passive sensor, and an RTD is a passive resistance element, although both still require documented evaluation of generated energy, stored energy, temperature, wiring, and installation conditions.

The AP1100 is different. It measures multiple inputs, uses the RTD for compensation, performs electronic conversion, and produces individual 4–20 mA outputs. Those functions require active circuitry and may introduce capacitance, inductance, internal power distribution, faults, or connections between channels. A PCB construction or low normal operating voltage does not make that circuitry simple apparatus.

A safe-area barrier limits the energy available at its hazardous-side terminals; it does not certify every connected field device. The complete loop must remain safe under the fault assumptions required by the selected protection method. That assessment depends on the barrier limits, field-device input parameters, cable capacitance and inductance, polarity, grounding, and any interaction through common transmitter circuitry.

What must be checked before accepting the loop calculation?

First resolve the area designation. Div 1 and Zone 1 belong to different classification systems and should not be written as interchangeable labels without the project basis. Record the country code, governing installation rules, protection method, gas or dust classification as applicable, and the Authority Having Jurisdiction.

Then obtain the AP1100 manual, hazardous-area certificate, approved control drawing, and terminal diagram. Identify how it is powered, whether its channels are isolated or share common circuits, where the barriers sit relative to every terminal, and whether the plate-temperature RTD connects only to an internal measuring circuit. Read the barrier certificate and control drawing for its permitted connected apparatus and wiring conditions.

For every intrinsically safe circuit, compare the barrier output limits with the corresponding field-device input limits. Add cable capacitance and inductance using the installed cable data and actual route length. The approximately 150 m multipair run and each thermocouple extension run of no more than 20 m are lengths, not electrical parameters; conductor size of 1.5 mm² does not supply the missing capacitance, inductance, screening, or mutual-coupling data.

Review common and individual screens, screen termination, segregation, terminal identification, conductor color, enclosure protection, and bonding against the governing project rules. Where conductor color conflicts with local requirements, the Authority Having Jurisdiction decides acceptance.

How should the design be corrected?

  1. Draw one complete schematic showing JB1, JB2, the control panel, every barrier, the AP1100 supply, 17 thermocouple inputs, the RTD, every 4–20 mA output, screens, earth connections, and cable boundaries.
  2. Split the drawing into distinct circuits. Do not combine all channels into one entity calculation unless the approved documentation explicitly defines them as one system.
  3. Mark the hazardous-area boundary and assign the project’s actual classification system. Remove the combined Div 1 (Zone 1) notation unless the project documents formally provide both classifications.
  4. Classify each thermocouple and the RTD separately under the governing simple-apparatus rules. Record the basis rather than leaving entity fields blank.
  5. Require certification or a formally approved system assessment for the AP1100. If neither exists, relocate it to a suitable safe area or replace it with equipment approved for the intended protection method and location.
  6. Recalculate every loop with barrier, field-device, and cable parameters. Include any manufacturer-defined restrictions on channel combinations, grounding, and multicore cable use.
  7. Submit the revised drawing, calculations, certificates, and installation details to the responsible hazardous-area engineer and the Authority Having Jurisdiction before energization.

How is the corrected installation verified?

Verify documentation and signals independently. Match every installed model and terminal connection to the approved drawing, then confirm cable identity, length, screen treatment, segregation, and enclosure entries. Record certificate identifiers and calculation inputs in the loop dossier.

Inject or simulate each thermocouple input and compare the transmitter output with the control-panel indication. Test the plate-temperature RTD path because one compensation error can bias several channels. Measure the 4–20 mA current on both sides of the relevant interface when isolating a discrepancy, and check loop loading against the equipment documentation.

Finally, inspect the system with all channels connected. Shared supplies, common returns, screens, or internal channel connections may be invisible during a single-channel test. Acceptance requires both correct measurements and an approved intrinsic-safety assessment.

What pitfalls recur on multichannel IS loops?

The most common mistake is treating a barrier as blanket approval for everything downstream. Other recurring errors include calling all low-energy sensors simple apparatus, omitting active electronics from entity calculations, using cable length without cable electrical data, overlooking shared multichannel circuitry, and changing process scaling to hide a wiring or compensation fault. Tuning does not fix wiring.

Another failure is reviewing only the 4–20 mA side. The thermocouple inputs, RTD circuit, transmitter supply, and internal relationships can all affect the protection concept. A large junction box also does not create protection by itself; its construction, entries, terminals, bonding, and installed equipment must suit the classified location.

FAQ

What happens if an AP1100 has no Ex certificate?

Do not accept it as simple apparatus based only on low signal levels or PCB construction. Obtain a formally approved system assessment, relocate it outside the hazardous area, or select equipment approved for the required protection method.

What happens if only the IS barrier has entity parameters?

The loop comparison remains incomplete because the field-device limits and cable capacitance and inductance are missing. Check each barrier-to-device circuit, including shared connections inside the multichannel transmitter.

When should work stop and official support be contacted?

Stop before energization when the AP1100 certificate, control drawing, entity parameters, or channel-isolation details cannot be produced. Escalate to the equipment manufacturer’s official technical support, the responsible hazardous-area engineer, and the Authority Having Jurisdiction; do not resolve missing protection data by field testing alone.

Back to blog