Can Eccentric Orifice Plates Measure Vertical Flow?

Brian Holt6 min read
Other ManufacturerProcess ControlTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Eccentric orifice plates do not gain a preferred clock position merely because the pipe is vertical. Set the orientation from the approved meter calculation, plate drawing, tap geometry, flow direction, and phase behavior. If those records do not define an orientation, stop rotating hardware and establish a documented basis before accepting the measurement.

Reject the usual quick fixes

Quick fix Why it fails Required action
Put the opening at the bottom as on a horizontal liquid line A vertical line has no invert where liquid or solids drain around the plate. The horizontal drainage rule supplies no measurement basis. Use the orientation specified by the calculation, drawing, calibration, or manufacturer.
Put the opening at the top to prevent heavy-phase buildup In two-phase service, that position can retain the heavy phase. Changing orientation may exchange one hold-up mechanism for another. Determine flow direction, phase fractions, and which phase can collect.
Rotate the opening away from a pressure tap Rotation changes the relationship between the eccentric jet and both taps. Moving the opening away from one tap can move it toward the other without removing the asymmetric pressure field. Match the documented plate-to-tap clocking.
Reuse a concentric-plate coefficient An eccentric opening creates a different velocity field. An unverified coefficient introduces a systematic flow error even when the differential pressure is stable. Use the coefficient and uncertainty assigned to the exact eccentric configuration.
Add another plate close to the first Closely spaced plates interact through swirl, turbulence, and an undeveloped jet. Differential pressure and restriction can then vary with spacing and relative clocking. Treat series plates as one engineered restriction system.

Define the duty before choosing an orientation

First decide whether the plate measures flow or only creates a pressure drop. A measurement plate requires controlled geometry, valid discharge-coefficient data, correct pressure-tap placement, and an uncertainty target. A restriction plate is selected around pressure reduction, noise, cavitation, flashing, vibration, erosion, and downstream recovery instead.

  1. Identify the fluid and whether it remains one phase through the operating range.
  2. Record whether flow is upward or downward.
  3. List minimum, normal, and maximum flow conditions, including batch or pump-driven variation.
  4. Confirm pressure and temperature at the plate rather than at a remote instrument.
  5. Check the plate drawing for opening orientation, flow arrow, bevel direction, tap locations, and required straight run.
  6. Confirm whether other valves, fittings, or orifice plates disturb the inlet profile.

Do not infer the service from the pipe orientation. The unresolved combination of fluid, phase condition, flow direction, and purpose is the main reason a universal clock position cannot be assigned.

Account for vertical two-phase behavior

Gravity acts along the pipe axis in a vertical run. That removes the horizontal-line drainage advantage of an eccentric opening, but it does not remove phase separation.

During vertical upflow, a heavy liquid or solids-rich phase can slip downward while a lighter vapor phase rises. Material may accumulate below a restriction until velocity carries it through. The eccentric opening then forms an off-axis jet that can disperse or atomize the heavy phase, but the same jet also creates an asymmetric velocity and pressure field.

Hole-down orientation can permit light-phase hold-up in part of a two-phase pattern; hole-up orientation can promote heavy-phase hold-up. Which effect controls depends on the relative phase amounts, velocities, density difference, and flow regime. Observe differential-pressure cycling, process density, and upstream level behavior rather than selecting an orientation from phase names alone.

Vertical downflow generally presents less tendency for the heavy phase to fall back against the bulk flow. It still can suffer maldistribution, intermittent flow, flashing, solids deposition, or unstable restriction behavior. Verify the actual phase state at plate pressure and temperature.

Control the relationship between the jet and taps

A concentric plate produces a nominally axisymmetric jet. An eccentric plate places the vena contracta and strongest velocity gradients toward one side of the pipe. Pressure recovery around the circumference can therefore be nonuniform, particularly close to the plate.

Pressure taps at different clock positions may sample different local static pressures when the flow field is asymmetric. The risk increases when the opening is close to a tap, upstream flow is already distorted, or another restriction is close enough for its jet to reach the plate. Tap lines at different elevations can also add hydrostatic head to the measured differential, especially in liquid or condensable service.

A documented comparison assigns a best-case uncertainty of 2% at two standard deviations to an eccentric plate, versus 1.2% for a concentric plate. Treat those figures as configuration-specific rather than universal accuracy guarantees. Likewise, informal estimates of ±10% versus ±6% of scale are not acceptance limits or substitutes for calibration.

Install from the measurement basis

  1. Isolate, depressurize, drain, and verify the line condition under the site work procedure.
  2. Confirm the plate bore, pipe inside diameter, plate thickness, material, bevel, and flow direction against the approved drawing.
  3. Clock the eccentric opening exactly as shown on the drawing or calibration record. Mark the carrier or tab so maintenance can reproduce that position.
  4. Inspect both pressure taps for blockage, burrs, deposits, and unequal impulse-line routing. Restore the specified axial and circumferential relationship.
  5. Remove liquid pockets from gas-service impulse lines and gas pockets from liquid-service impulse lines. Put both transmitter legs into the same known fill condition.
  6. Check nearby valves, elbows, reducers, and other plates against the required upstream and downstream geometry.
  7. For multiple eccentric plates, verify spacing and relative orientation as an engineered assembly. Greater separation reduces interaction only after the upstream jet and pressure field have sufficiently recovered.
  8. Reassemble with the plate centered in its holder and the gasket clear of the opening and taps.

If no drawing, coefficient record, or calibration defines the eccentric orientation, do not create one during a breakdown. A controlled comparison against a neutral reference or full-scale calibration is the defensible way to quantify orientation error.

Verify the result under operating conditions

  1. Zero the differential-pressure transmitter with equal pressure applied to both sides.
  2. Return the process gradually and watch for step changes, oscillation, or a differential pressure that does not track flow demand.
  3. Compare indicated flow with an independent reference such as a calibrated meter, mass balance, tank rate, or known batch quantity.
  4. Repeat the comparison at more than one stable operating point. A single point can hide a coefficient error or nonlinear disturbance.
  5. Trend differential pressure with pressure, temperature, valve position, and pump state. Cycling tied to phase loading points to process behavior rather than transmitter zero.
  6. Inspect for noise, vibration, cavitation, flashing, erosion, or unstable choking when the plate is a restriction device.

Record the plate clocking, tap clocking, flow direction, phase condition, operating point, and reference result. Get production running only after the reading is credible; then correct drawings and maintenance instructions so the same uncertainty does not return.

FAQ

Can I install an eccentric orifice with the hole down in vertical pipe?

Only when the approved drawing or calibration specifies hole-down orientation. The horizontal-pipe drainage reason does not apply to a vertical run.

Does pressure-tap orientation matter with an eccentric plate?

Yes. The off-axis jet can create circumferential pressure differences, so changing the plate-to-tap clocking can change the indicated differential pressure.

Can I use the concentric-orifice coefficient for an eccentric plate?

Use it only when the meter calculation or calibration explicitly assigns that coefficient to the exact eccentric geometry. Otherwise, obtain the correct coefficient before accepting the flow result.

Does vertical downflow eliminate two-phase measurement problems?

No. Heavy-phase fallback is generally less troublesome than in upflow, but flashing, intermittent flow, solids, and phase maldistribution can still make differential pressure unstable.

Can I keep operating when the differential pressure changes after rotating the plate?

Stop if the reading cannot be reconciled with an independent flow reference or if the line develops vibration, cavitation, flashing, or unstable choking. Do not keep rotating the plate to tune the indication. Escalate to the meter or plate manufacturer's official support channel with the drawing, tap layout, flow direction, fluid state, operating conditions, and trend data.

Back to blog