1. Application Overview
This reference describes a two-stage gas-heater cascade implemented on a Siemens LOGO! 0BA5 base module extended with an AM2 RTD expansion block. Two PT1000 Class A sensors measure flow and return water temperatures of a primary heating loop. A room thermostat provides the demand signal. Stage 1 starts when the room calls for heat. Stage 2 is allowed to start only when the return-water temperature has not reached a configurable set point (default 50 °C) within a configurable window (default 10 minutes). The intent is to maximize single-stage efficiency, reduce burner cycling, and limit the parallel running time of the second appliance.
The same architecture generalises to any LOGO! 5-series base module (0BA5) with the 6ED1055-1MD00-0BA2 RTD expansion. Programming is performed in LOGO!Soft Comfort V5.x; the FBD and ladder fragments in this article are compatible with the 0BA5 instruction set.
2. System Architecture
| Block | Function | LOGOLabel / Address |
|---|---|---|
| Base module 0BA5 | Logic execution, 8 DI, 4 DO, 2 AI (0–10 V) | I1…I8, Q1…Q4, AI1, AI2 |
| AM2 RTD (6ED1055-1MD00-0BA2) | 2 × PT100/PT1000 inputs | AI3, AI4 (mapped to AM inputs) |
| PT1000 sensor A | Return water temperature (T_ret) | AI3 |
| PT1000 sensor B | Flow water temperature (T_flow) | AI4 |
| Room thermostat | Potential-free contact, demand | I1 |
| Heater 1 start | Relay output to burner 1 | Q1 |
| Heater 2 start | Relay output to burner 2 | Q2 |
| System enable | Hard-wired safety contact | I2 |
| Fault reset | Pushbutton, NC | I3 |
The AM2 RTD expansion is mandatory; the 0BA5 onboard analog inputs (AI1/AI2) are 0–10 V and cannot accept a 2-wire PT1000 directly. The PT1000 must be wired in the 2-wire configuration to terminals I1+ / I1- and I2+ / I2- of the AM2 module using shielded cable, with the shield grounded at the LOGO! end only.
3. Sensor Scaling on the 0BA5 / AM2 RTD
PT1000 nominal resistance is 1000 Ω at 0 °C with a near-linear slope of approximately 3.85 Ω/°C. The AM2 RTD linearises the resistance and presents the result as a scaled analog value on the LOGO! 0BA5.
| Parameter | Value | Note |
|---|---|---|
| PT1000 sensing range | -50 °C to +200 °C | Application range, sensor and AM2 limited |
| AM2 measurement range | 0 to 1000 (mapped from range) | Verify against AM2 manual |
| Resistance at 0 °C | 1000 Ω | IEC 60751 |
| Resistance slope | 3.85 Ω/°C average | Use Callendar-Van Dusen for high accuracy |
| Recommended excitation | < 1 mA | Self-heating limit per IEC 60751 |
For FBD use an Analog Amplifier (B02) block in conjunction with the AI input. Configure sensor type = PT1000 and measurement range = 0…100 °C. The amplifier output becomes a 0–1000 integer equivalent that downstream math blocks (threshold triggers, PI controller) interpret directly.
If the AM2 RTD block is configured for PT1000 in LOGO!Soft Comfort, the block performs linearisation internally. Do not apply a second linearisation in the FBD; the gain will be applied twice. The output scaling is in tenths of a degree by default on the 0BA5 (verify in the AM2 manual shipped with the module).
4. Why Both Flow and Return Are Measured
A common confusion in the source thread is whether the flow sensor is required when the return sensor already gives a meaningful signal. The answer is that the two sensors carry different information:
- Return water (T_ret) is the controlled variable. It indicates how much heat the emitters have already extracted from the loop. If T_ret stalls, the loop is calling for more heat than a single burner can deliver.
- Flow water (T_flow) is a supervisory variable. The flow/return differential (ΔT) is a proxy for instantaneous loop load. A high ΔT with a low T_ret is a robust start condition for a second burner; a low ΔT with a high T_ret means the loop is over-supplied and the demand should be shed instead of added.
A simple two-stage cascade can run on T_ret alone, but the addition of T_flow enables anti-oscillation, lead/lag, and maximum ΔT clamp logic, which prevents short cycling of the second burner when the loop is near steady state.
5. Cascade Control Strategy
The recommended state machine for the heater pair is shown below.
State transitions in plain language:
- IDLE → STAGE 1: room thermostat closes (I1) and system enable (I2) is present.
- STAGE 1 → STAGE 1 + 2: timer T1 elapses (10 minutes default) AND T_ret is below set point (50 °C default).
- STAGE 1 + 2 → COOLDOWN: room thermostat opens, fault, or T_ret ≥ (set point + hysteresis, default 2 °C).
- COOLDOWN → IDLE: minimum off-time T2 (3 minutes default) expires, both Q1 and Q2 are forced off to allow pump overrun.
6. Building the FBD on LOGO! 0BA5
The program is constructed in the following block order in LOGO!Soft Comfort V5.x. Block numbers shown are illustrative; renumber for your project.
6.1 Inputs and Scaling
B01 Digital Input I1 -- Room thermostat
B02 Digital Input I2 -- System enable
B03 Digital Input I3 -- Fault reset (NC)
B04 Analog Input AI3 -- PT1000, T_ret (return)
B05 Analog Input AI4 -- PT1000, T_flow (flow)
B06 Analog Amplifier (PT1000, 0..100 °C) -> AQ3
B07 Analog Amplifier (PT1000, 0..100 °C) -> AQ4
6.2 Threshold Detection
B08 Threshold Trigger On: AQ3 >= 500 (T_ret >= 50.0 °C)
Off: AQ3 < 480 (hysteresis 2.0 °C)
Output -> M1
B09 Threshold Trigger On: AQ3 < 500 (T_ret < 50.0 °C)
Off: AQ3 >= 500
Output -> M2
B10 Threshold Trigger On: (AQ4 - AQ3) >= 150 (ΔT >= 15.0 °C)
Off: (AQ4 - AQ3) < 130
Output -> M3 -- "loop still hungry"
The 0BA5 does not perform subtractions between two analog inputs directly. Use an Analog Math block (B11) with the expression AQ4 - AQ3 and feed the result into B10.
6.3 Time-Delayed Stage-2 Enable
B12 AND I1, I2 -- master demand
B13 On-Delay 00:10:00 -- 10 minute window
Triggered by: B12
Output: M4 -- "stage 2 allowed"
B14 AND M4, M2, M3 -- stage 2 allowed AND
-- T_ret < 50 °C AND
-- loop ΔT > 15 °C
B15 Set/Reset Latch S = B14, R = B08
6.4 Output Drivers
B16 AND B12, NOT(B15) -- Q1 if demand and not in stage 2
B17 Output Q1 = B16
B18 Output Q2 = B15
Block B16 deliberately forces Q1 off while B15 is set if you want exclusive operation, but for parallel/cascade operation with the source's requirement keep B16 = (I1 AND I2) so that Q1 stays on whenever there is demand and the safety contact is closed. Replace B16 with a direct pass-through of B12 if parallel running is desired.
7. PI Controller Variant
The source thread mentions that a PI controller was attempted but abandoned due to unfamiliarity. The PI controller block (B20) on the 0BA5 can be used as a supervisory controller on T_ret with a slower integral action that decides whether stage 2 should be added. A practical implementation:
| Parameter | Value | Comment |
|---|---|---|
| Set point SP | 500 (= 50.0 °C) | T_ret target |
| Sensor input | AQ3 | From B06 |
| Kp (gain) | 1.0 | Proportional band of 100 % |
| Ti (integral time) | 120 s | Slow integration prevents oscillation |
| Direction | Direct | Output rises as T_ret falls below SP |
| Output low limit | 0 | Disable stage 2 |
| Output high limit | 1000 | Enable stage 2 |
The PI output is fed into an additional threshold trigger (B21) that turns on stage 2 when the integrated error exceeds 70 % of the controller span. This provides soft staging and avoids hard time-based decisions during steady-state operation.
For thermal loops with response times in minutes, Ti in the 60–240 s range is typical. Start with Ti = 120 s and reduce by half if the controller is too slow, or double it if the system oscillates. Kp = 1.0 with normalised output is the safest starting point on a 0BA5.
8. Hardware Wiring
| Wire | From | To | Notes |
|---|---|---|---|
| PT1000 #1, red | Sensor A | AM2 terminal I1+ | 2-wire, no polarity |
| PT1000 #1, red | Sensor A | AM2 terminal I1- | Use a single pair, no junction |
| PT1000 #2, red | Sensor B | AM2 terminal I2+ | 2-wire |
| PT1000 #2, red | Sensor B | AM2 terminal I2- | 2-wire |
| Room thermostat | Common | LOGO! terminal I1 | Potential-free contact |
| Room thermostat | Switched | +24 V (or L for 230 V base) | Match base module supply |
| Heater 1 start | LOGO! Q1 | Burner 1 enable input | Respect burner control voltage |
| Heater 2 start | LOGO! Q2 | Burner 2 enable input | Respect burner control voltage |
| PE | Earth | LOGO! PE terminal | Required for CE compliance |
9. Commissioning Procedure
- Power the LOGO! 0BA5 with the AM2 RTD detached. Verify the base module boots and the LOGO! display shows no expansion error.
- Connect the AM2 RTD on the expansion bus. Confirm in LOGO!Soft Comfort online view that AQ3 and AQ4 appear in the I/O status list.
- Apply known temperature sources (ice-water slurry at 0 °C, boiling water at 100 °C) to each PT1000. Read AQ3/AQ4 values. Trim the amplifier offset in the AM2 configuration if the deviation exceeds 0.5 °C.
- Force I1 on in online test. Confirm Q1 energises within 100 ms and the burner lights.
- Force I1 off and verify Q1 drops, Q2 drops, and the on-delay B13 resets.
- Simulate the alarm condition: with I1 on, clamp T_ret to 20 °C using a calibration source. After 10 minutes Q2 must energise. The on-delay B13 must be the only gating element on the cold start.
- Apply the actual return temperature by running the loop. Verify M1 toggles at the expected set point ± hysteresis.
- Log the LOGO!Soft Comfort online trace for at least 30 minutes of normal operation; verify no fault, no spurious stage transitions.
10. Verification Checklist
| Check | Expected | Method |
|---|---|---|
| T_ret scaling at 0 °C | AQ3 ≈ 0 | Ice bath |
| T_ret scaling at 50 °C | AQ3 ≈ 500 | Calibrated source |
| T_flow scaling at 50 °C | AQ4 ≈ 500 | Calibrated source |
| Stage 1 only at warm start | Q1=1, Q2=0, T_ret > 50 °C | Heat loop to 55 °C, energise I1 |
| Stage 2 enabled after 10 min | Q2=1, T_ret < 50 °C | Clamp T_ret low, wait 10 min |
| ΔT detection | M3 true when ΔT ≥ 15 °C | Online monitor |
| Safety contact (I2) | Both Q1 and Q2 drop when I2 opens | Manual test |
| Minimum off-time | No re-start for 3 min after shutdown | Cycle thermostat |
11. Troubleshooting Matrix
| Symptom | Likely Cause | Action |
|---|---|---|
| AQ3 reads 0 with sensor connected | Open or shorted PT1000 | Measure resistance at AM2 terminal: 1000 Ω ± 4 Ω at 0 °C |
| AQ3 reads negative or out of range | Sensor type misconfigured (PT100 vs PT1000) | Reconfigure AM2 in LOGO!Soft Comfort to PT1000 |
| Q1 never energises | I1 not wired to 24 V reference, or I2 open | Check I1 and I2 with multimeter; verify I/O status |
| Q2 energises immediately | On-delay B13 disabled or short-circuited | Check B13 trigger input; reset to 10:00 |
| Q2 chatters on/off | Hysteresis too small on B08, or no minimum off-time | Raise hysteresis to 20, add 3 min off-delay (B22) |
| Q1 and Q2 both on for hours | ΔT set point wrong, or T_ret sensor in dead leg | Verify sensor location; check B10 threshold |
| No expansion detected | AM2 not seated, bus terminator issue | Power down, reseat AM2, restart |
| LOGO! display shows "No program" | Program not transferred | LOGO!Soft Comfort > PC → LOGO!, then run mode |
12. Safety Considerations
Gas burners require independent flame supervision; the LOGO! must never be the sole safety interlock. The burner controller's own safety chain (air pressure, flame rod, gas valve proving) is authoritative. The LOGO! enable outputs (Q1, Q2) must be wired in series with the burner enable circuit so that a LOGO! fault cannot energise a burner unintentionally. A watchdog or fail-safe relay on Q1 and Q2 is recommended if the burner enable input is not galvanically isolated.
Verify that the LOGO! 0BA5 output relays are rated for the burner control voltage and current. On a 230 V AC base module, the relay contacts are typically rated 8 A resistive, which is generally adequate for low-current enable inputs only. Do not switch the gas valve directly from Q1/Q2 unless the contact rating has been confirmed against the valve coil inrush.
13. Practical Tuning Notes
- Default 10 min delay is a good cold-start value. For well-insulated loops, reduce to 6 min; for sluggish emitters, extend to 15 min.
- Set point 50 °C is appropriate for low-temperature underfloor loops. For radiator loops, raise to 60–65 °C.
- Hysteresis on the disable threshold should be 2–3 °C, not less, to prevent contactor hunting.
- ΔT threshold of 15 °C is conservative. Calibrate it to the actual ΔT observed at design load (typically 10–20 °C for residential heating loops).
- Pump overrun: if the system pump is not controlled by the LOGO!, the 3 min minimum off-time protects the burner; if the pump is also LOGO!-controlled, extend the off-time to 5 min to dissipate loop heat.
Why does my LOGO! 0BA5 show "No program" after transfer?
The 0BA5 must be in STOP mode to receive a program. In LOGO!Soft Comfort select PC → LOGO!, place the base in STOP, transfer, then run. If "No program" persists, the cartridge may be loose or the password is locked; clear via Tools > Clear Password.
Is the flow sensor really required if the return sensor already drives the cascade?
A return-only cascade works for simple on/off staging. The flow sensor adds ΔT information that prevents short cycling when the loop is near steady state, and allows a true PI-based load share. For a two-stage installation the return sensor alone is sufficient, but the flow sensor is recommended for diagnostics.
What is the resolution of a PT1000 on the AM2 RTD?
The AM2 RTD linearises the PT1000 internally and presents a 10-bit value (0–1000) over the configured measurement range, giving approximately 0.1 °C resolution on a 0–100 °C span. Verify the exact specification in the AM2 RTD manual shipped with the 6ED1055-1MD00-0BA2 module.
Can the 0BA5 outputs switch a 230 V gas valve coil directly?
Only if the relay contact rating matches the coil inrush. The 0BA5 relay is typically 8 A resistive; solenoid coils often have inrush of 20–30 A. Use an interposing relay or contactor between Q1/Q2 and the gas valve.
How do I log the cascade behaviour for debugging?
Connect LOGO!Soft Comfort online, open the I/O status, and use the data log function to record AQ3, AQ4, Q1, Q2, M1, M2, M3 over time. Export to CSV and plot the stage transitions against T_ret to confirm the 10 min delay is honoured.