Comfort Panel Alarm Buffer Empty: Root Cause and USB Log Fix

David Krause13 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Description

On a SIMATIC HMI Comfort Panel (TP700, TP900, TP1200, TP1500, TP1900, TP2200), the alarm window object displays an empty alarm buffer after a power cycle of the panel, even though identical HMI stations in the same plant show the historical alarm entries correctly. Operators open the alarm view, the list is empty, and the only historical record available is what was acknowledged before the last reboot. This is a known runtime behavior on Comfort Panels when the alarm log storage location is set to the default internal flash path and the panel reboots unexpectedly or is power-cycled. The alarm buffer is a volatile copy of the active (unacknowledged) alarms, while the alarm log is the persistent record. When the log path is misconfigured, deleted, or unwritable, the buffer appears empty on startup even when configuration is correct.

The symptom presents in two distinct ways:

  • Empty after power cycle — Alarms are visible during operation, but on the next boot the alarm view shows zero entries. This indicates the alarm log location was not persistent across the reboot.
  • Empty on a single HMI only — A specific panel in a fleet of identically-configured units does not show alarms while its peers do. This typically points to a per-device project configuration drift, a corrupted runtime file system, or a hardware issue with the storage medium.

The error is most commonly reported on projects originally created in TIA Portal V13 SP1 and later updated in V15, V15.1, V16, V17, V18, V19, or V20. It affects WinCC Comfort, WinCC Advanced, and WinCC Professional runtime environments where Comfort Panel targets are configured.

Affected Products and Versions

Component Designation Notes
HMI Hardware SIMATIC HMI TP700 Comfort, TP900 Comfort, TP1200 Comfort, TP1500 Comfort, TP1900 Comfort, TP2200 Comfort All 4-inch through 22-inch widescreen Comfort panels
HMI Hardware SIMATIC HMI KP700 Comfort, KP900 Comfort, KP1200 Comfort, KP1500 Comfort Key variants share the same alarm subsystem
HMI Hardware SIMATIC HMI KTP700 Comfort, KTP900 Comfort, KTP1200 Comfort Combined key/touch variants
Engineering TIA Portal V13 SP1, V14, V14 SP1, V15, V15.1, V16, V17, V18, V19, V20 Configuration tooling for project and runtime settings
Runtime WinCC Comfort / Advanced / Professional Runtime Version must match the panel image
Image Comfort Panel firmware images delivered with the matching TIA Portal version Mismatched image and project can cause alarm class registration issues
Important: Always match the panel's runtime image to the TIA Portal version used to compile the project. A V13 SP1 project downloaded to a V16 image frequently yields alarm class registration errors and buffer initialization failures. Use the "OS Update" or ProSave procedure to reflash the panel image to the correct version before troubleshooting further.

Alarm Architecture on Comfort Panels

Comfort Panels maintain three separate alarm data structures. Understanding the distinction is the prerequisite to resolving the empty-buffer symptom.

Alarm Buffer (Active Alarms)

The alarm buffer is a volatile, in-memory list of currently active or unacknowledged alarms. It exists in RAM only and is reconstructed on each boot from the alarm log plus the live tag conditions. If the alarm log is not persistent across the boot, the buffer reconstructs empty even when alarms had been active prior to the reboot.

Alarm Log (Persistent Alarms)

The alarm log is a circular file stored on the configured storage medium. Default storage is the internal flash file system at /home/cf-card/Logs or, when no CF card is present, on the internal NAND at /home/Logs. The log survives reboot only if the storage medium is persistent and the file is intact.

Alarm Archive (Long-Term)

The alarm archive is a separate configurable file used for long-term export, often to a network share or USB stick. Archives are not used to populate the alarm view on startup; only the log is.

The alarm window object on the screen reads from the buffer and the log simultaneously. If the log cannot be read, the window falls back to showing only the currently active (unacknowledged) alarms, which may be zero after a clean boot.

Root Cause Analysis

Five root causes account for nearly all field reports of an empty Comfort Panel alarm buffer.

Cause 1: Internal Flash Wear or Corruption

Comfort Panels use internal NAND flash for the alarm log when no external storage is configured. After tens of thousands of write cycles, particularly on panels with high alarm traffic, the file system can develop bad blocks. The alarm log file may exist but be unreadable, and the runtime silently fails to populate the buffer. The SystemLog.txt on the panel contains entries such as "Alarm logging: file system error" when this occurs.

Cause 2: Missing or Unmounted Storage Medium

If the alarm log is configured to point to an SD card or USB stick path and that medium is not present at boot, the runtime cannot reconstruct the buffer. The error is silent: the alarm view simply shows zero entries.

Cause 3: Power Loss During Log Write

An uncontrolled shutdown (24 V DC supply removed under load) while the log file is open can truncate the file. The next boot detects an invalid log header and discards the contents, leaving the buffer empty.

Cause 4: Project Drift Between Identical HMI Stations

When a fleet of panels is configured from the same master project but only some show the symptom, the project loaded on the affected panel is not identical to its peers. The drift is typically a difference in:

  • Alarm log storage path (one panel set to internal, another to USB or SD)
  • Alarm log segmentation (size, time-based rollover)
  • Alarm classes registered (missing user-defined class)
  • Project version (one panel not updated during a recent TIA Portal upgrade)

Cause 5: xlsx Alarm Import Issue

When alarms are imported into the project from an xlsx file, empty list entries for existing alarms are ignored. The entries of the existing alarms remain. This is documented behavior in the TIA Portal help and means a partial or malformed import will leave the project with stale alarm definitions, which can produce an empty buffer if the runtime cannot resolve the alarm classes. Review the official Siemens documentation on importing alarms in TIA Portal V20 to confirm import semantics before assuming a project drift cause.

Solution 1: Route the Alarm Log to a USB Stick (Field-Proven Workaround)

Siemens support recommends configuring the alarm log storage location to a USB stick on the front USB port of the Comfort Panel. The USB stick is mounted as /media/usb0 at runtime and the log persists across power cycles independently of the internal file system.

Prerequisites

  • USB 2.0 stick formatted with FAT32 file system (one partition, 32 KB cluster size recommended)
  • USB stick capacity 1 GB to 32 GB (larger sticks are not always recognized by the panel image)
  • Industrial-grade stick recommended (MLC or SLC NAND) for environments with high write cycles
  • Project source in TIA Portal V13 SP1 or later
  • Active project download capability (ProSave, Ethernet, or USB)

Step-by-Step Configuration

  1. Open the TIA Portal project containing the affected Comfort Panel.
  2. In the project tree, select the HMI device and open Runtime Settings > Alarm Logging (or Alarms > Settings > Alarm Logging in older TIA versions).
  3. Locate the Storage location property for the alarm log. By default this is Storage Card or Internal Flash.
  4. Change the storage location to USB (path /media/usb0/Logs) or define a custom path under the USB mount point.
  5. Confirm the Log size and Segmentation parameters: a 2 MB to 8 MB circular log with time-based segmentation of 24 hours is typical for alarm-only retention.
  6. Enable Activate alarm log.
  7. Compile the HMI project (full rebuild, not incremental).
  8. Download the compiled runtime to the Comfort Panel.
  9. Insert the prepared USB stick into the front USB port (X1) of the panel before the panel boots, or insert it and reboot the panel via the Control Panel > Reboot menu.
  10. Trigger a known alarm and acknowledge it. Power-cycle the panel. Verify the alarm is still visible in the alarm view.

Verification

  1. Trigger an alarm (e.g., a level switch overrange).
  2. Acknowledge the alarm from the alarm window.
  3. Open the Control Panel on the HMI and select Reboot.
  4. Wait for the panel to restart and load the project.
  5. Open the alarm view. The previously triggered alarm must still be present in the log.
  6. If the alarm is missing, check the USB stick for the file AlarmLog_ALG_0.csv (or similar). The file should be present and contain the historical entries.
Important: The USB stick must remain inserted at all times. If the panel boots without the stick, the log cannot be read and the buffer will reconstruct empty. For unattended operation, use a panel with an SD card slot and configure the storage to SD card instead, which is mechanically retained.

Solution 2: Realign the Project on the Affected HMI

When a single HMI in a fleet shows the empty buffer and others do not, the project on the affected unit is not byte-identical. Restore parity.

  1. Identify the project source archive used for the working peers (TIA Portal .ap13, .ap15_1, .ap16, etc.).
  2. Connect the engineering station to the affected HMI via Ethernet or Profinet.
  3. In TIA Portal, select the HMI device and choose Download to device > Software (full download).
  4. Confirm the dialog indicates a full project transfer, not a delta update.
  5. After download completes, the panel reboots automatically. Verify the alarm buffer reconstructs from the log.

Solution 3: Clear and Re-create the Alarm Log

If the internal flash log is corrupted, clear and re-create it.

  1. Open the Control Panel on the HMI (the small panel behind the Start Center).
  2. Navigate to File System > Logs.
  3. Delete the alarm log file (typically AlarmLog_ALG_0.csv or *.dat depending on version).
  4. Reboot the panel.
  5. The runtime will create a new log file on the next alarm event.
Caution: Deleting the log file permanently removes historical alarm data. Capture the data via ProSave or by copying the CSV off the panel before deletion if retention is required for compliance.

Solution 4: Reflash the Panel Image

For panels that have been in service for multiple years with high alarm traffic, the internal NAND may be worn. Reflash the image with ProSave.

  1. Launch ProSave on the engineering station.
  2. Connect to the panel via Ethernet (set the panel IP temporarily via the Control Panel if unknown).
  3. Select OS Update and load the matching TIA Portal image (for example, the V16 image for a V16 project).
  4. Reset the panel to factory defaults after the image update.
  5. Re-download the project.
  6. Verify the alarm buffer behavior.

Diagnostic Steps for Field Engineers

Use this sequence when arriving on site to isolate the cause quickly.

  1. Read SystemLog.txt. Use ProSave or an FTP client to retrieve /home/SystemLog.txt from the panel. Search for entries containing "Alarm", "log", "file system", or "CSV". Errors here pinpoint storage issues.
  2. Verify storage medium. Check that the configured storage path exists and is writable. Trigger a test alarm and confirm a new entry appears in the log file via FTP.
  3. Compare project versions. On the engineering station, right-click the HMI device and select Device Information > Compile Information. Repeat for a working peer. The compile timestamps and project hashes must match.
  4. Check alarm class registration. Open the alarm window in the TIA Portal simulation. If the simulation shows alarms but the runtime does not, the project compiled correctly but the runtime cannot resolve the alarm class definitions.
  5. Inspect the alarm log file size. A zero-byte or suspiciously small log file indicates the file system refused to write. A truncated file indicates a power loss during write.

Alarm Log Configuration Reference

Parameter Default Value Recommended for Persistent Retention
Storage location Internal flash USB stick (/media/usb0/Logs) or SD card
Log size 1 MB 4 MB to 8 MB depending on alarm rate
Segmentation By size By time (24 h) for predictable archives
Log overflow behavior Overwrite oldest Overwrite oldest unless compliance requires stop
Activate alarm log Enabled Enabled
Time stamp format Local time UTC for multi-region fleets

Troubleshooting Matrix

Symptom Likely Cause Verification Fix
Empty buffer on all panels, consistent across reboots Log storage path not persistent Check Runtime Settings > Alarm Logging storage path Move storage to USB or SD; reflash if internal flash worn
Empty buffer on one panel only Project drift on that unit Compare compile info with working peers Full project download to the affected HMI
Empty buffer after power loss Truncated log file Inspect log file size and content Clear log; route storage to UPS-backed or USB stick
Empty buffer after TIA Portal version upgrade Panel image does not match project Check ProSave image version Reflash image to match project version
Empty buffer when USB removed Storage path unreachable Confirm USB stick present at boot Switch to SD card slot if available, or industrialize USB retention
Empty buffer immediately after xlsx alarm import Import dropped classes due to empty entries Cross-check alarm classes in project tree Re-import the xlsx with complete rows, or manually re-create dropped classes
Buffer populates but old alarms gone Circular log overflowed and overwrote history Check log size vs. alarm rate Increase log size or shorten segmentation interval

Preventive Measures

  • Always deploy projects with the alarm log routed to an external medium (USB or SD card) to avoid dependency on internal flash longevity.
  • Maintain a baseline project archive and verify the compile hash of every deployed HMI quarterly. Drift is the most common cause of unexplained single-unit faults.
  • For plants with 24 V DC supply that is not backed by a UPS, add a small UPS or use a buffered DC supply to prevent uncontrolled power loss on the panel.
  • Use industrial-grade USB sticks (e.g., Swissbit, ATP, or Siemens SIMATIC HMI USB sticks rated for industrial temperature and write cycles).
  • Schedule a periodic export of alarm logs to a network share using the panel's archive function. This decouples retention from a single storage medium.
  • Document the TIA Portal version and panel image version per HMI in the plant asset register.

Cross-Reference: Importing Alarms into the Project

When bulk-loading alarms from a spreadsheet, the TIA Portal import treats empty list entries for existing alarms as no-ops: the existing alarm definitions remain in the project. This means a malformed import will not delete alarms but may leave the project in a state where classes, groups, or trigger tags referenced by some alarm rows are not present. The runtime will fail to register those alarms and the buffer appears empty for the affected class. To avoid this, validate the xlsx before import and ensure every row has a complete alarm class, trigger tag, and message text. Refer to the official TIA Portal help for importing alarms in TIA Portal V20 for the complete import procedure and field constraints.

FAQ

Why is my Comfort Panel alarm buffer empty after a power cycle?

The alarm buffer is reconstructed from the alarm log at boot. If the log storage is the internal flash and the file is truncated, missing, or the medium is not present, the buffer shows zero entries. Route the alarm log storage to a USB stick or SD card via Runtime Settings > Alarm Logging to make the log persistent across power cycles.

Which TIA Portal versions are affected by the empty alarm buffer issue?

The symptom is reported most often on projects compiled in TIA Portal V13 SP1 and is reproducible in V14 through V20 when the alarm log storage is not externalized. The root cause is the storage path, not the TIA version itself, so all Comfort Panel runtime versions are potentially affected.

Can I use any USB stick to store the alarm log?

Use a USB 2.0 stick formatted with FAT32 and a 32 KB cluster size. Capacity between 1 GB and 32 GB is recommended. Industrial-grade sticks (MLC/SLC) are strongly preferred for plants with high alarm traffic because consumer-grade sticks wear out under continuous write cycles.

How do I verify the alarm log is being written?

Connect to the panel via FTP or ProSave, navigate to /media/usb0/Logs (or the configured path), and check for files like AlarmLog_ALG_0.csv. Trigger a test alarm and confirm a new row appears in the CSV. If the file is absent or zero bytes, the runtime cannot write to the path.

What happens if the USB stick is removed while the panel is running?

The runtime loses access to the log and the alarm view shows only currently active unacknowledged alarms. Historical entries are not lost on the stick itself and reappear when the stick is reinserted and the panel reboots. For continuous retention, use a panel with an SD card slot and route the log to the SD card.

Back to blog