Configuring 7 PTO Outputs on S7-314 2DP: FM and ET 200S Solutions
Generating seven independent pulse train outputs (PTO) from a SIMATIC S7-314 2DP CPU is a recurring engineering question because the standard S7-314 2DP (6ES7314-6CG03-0AB0 or equivalent order numbers) does not include on-board PTO channels. Only the compact CPUs of the S7-300 family (S7-312C, S7-313C, S7-313C-2 PtP, S7-313C-2DP, S7-314C-2 PtP, and S7-314C-2DP) ship with up to four integrated high-speed outputs. The "plain" 314-2DP without the "C" suffix has no pulse generator hardware at all, so any PTO requirement must be satisfied through function modules (FM), distributed I/O (ET 200S), intelligent drives, or a controller change.
This reference documents the four practical paths for delivering seven pulse-and-direction or CW/CCW pulse pairs to stepper or servo drives from an S7-300 station:
- Four ET 200S 2-channel pulse modules
6ES7138-4DD01-0AB0on a Profibus DP slave, producing eight 24 V pulse outputs up to 10 kHz each. - One or more FM 352-5 high-speed Boolean processors for high-speed pulse generation with ramp and direction control.
- Migration of the motion task to an S7-1500 with TM PTO technology modules (4 channels per module, 24 V, up to 1 MHz).
- Replacing PLC-side pulse generation with intelligent servo or stepper drives that accept setpoints over Profibus, Profinet, or analog/digital commands.
The remainder of this document covers hardware selection, electrical topology, STEP 7 / TIA Portal configuration, signal integrity constraints, and field-proven commissioning checks specific to driving seven axes from an S7-314 2DP.
Why the S7-314 2DP Cannot Generate PTO Directly
The S7-314 2DP CPU (order number 6ES7314-6EH04-0AB0 for the -2DP variant, depending on firmware release) provides:
- One Profibus DP master interface (X2).
- One MPI/Profibus combined interface (X1).
- No on-board digital outputs rated for high-speed pulse generation.
- No integrated technology functions such as positioning, counting in technology object form, or PTO.
By contrast, the S7-314C-2DP (6ES7314-6CG03-0AB0) integrates four 24 V high-speed outputs capable of PTO, PWM, and frequency output modes at up to 2.5 kHz from the standard technology objects. The user's station as described uses the non-"C" 314-2DP, so a different mechanism is required for each of the seven pulse streams.
Three electrical constraints govern every solution discussed below:
- Output voltage. All Siemens S7-300 pulse outputs switch 24 V push-pull or PNP sourcing logic. This matches the standard differential line receiver inputs on modern stepper and servo drives (typically 5 V to 24 V opto-isolated inputs).
- Output current. 24 V outputs from ET 200S pulse modules source typically 0.5 A per channel, with short-circuit protection. The cable length to the drive determines the capacitive load that limits maximum frequency.
- Common-mode range. Differential receivers (RS-422 or 26LS31/26LS32 type) tolerate a common-mode range of typically -7 V to +12 V on the signal pair, which is comfortable for industrial cabinets. Refer to Texas Instruments differential PTO interface application brief (TIDUC30) for the receiver-side constraints.
Solution 1: ET 200S 2-Pulse Modules on Profibus DP (Recommended for ≤ 10 kHz)
The ET 200S distributed I/O family is the canonical answer for "I need more pulse outputs than the CPU has." The specific module is:
| Attribute | Value |
|---|---|
| Order number (MLFB) | 6ES7138-4DD01-0AB0 |
| Module designation | 2 PULSE / PWM pulse generator |
| Channels per module | 2 (each with pulse and direction pair, or CW/CCW) |
| Maximum output frequency | 10 kHz per channel |
| Output voltage | 24 V DC nominal (15 to 30 V supply range) |
| Output current | 0.5 A per channel, short-circuit protected |
| Module width | 15 mm |
| Bus interface | Profibus DP slave via IM 151-1 / IM 151-3 interface module |
| Configuration tool | STEP 7 V5.x or TIA Portal (HSP for ET 200S) |
| Function blocks | FB for PWM/PTO from Siemens standard library or Drive ES |
For seven PTO outputs, use four 6ES7138-4DD01-0AB0 modules on a single ET 200S Profibus DP slave. Eight channels are available; the eighth channel can serve as a spare, an electronic cam, or be disabled. The station is wired as follows:
- Interface module: IM 151-1 STANDARD (6ES7151-1AA05-0AB0) for Profibus DP, or IM 151-3 PN (6ES7151-3BA23-0AB0) if Profinet is preferred (the pulse module ships Profibus variant; the Profinet variant uses the same pulse module article number with the standard ET 200S Profinet backplane).
- Power module: PM-E 24 V DC (6ES7138-4CA01-0AA0) to provide 24 V to the electronic modules.
-
Pulse modules: 4×
6ES7138-4DD01-0AB0for 8 PTO channels. - Digital inputs (optional): DI modules for home/reference switches, end limits, and drive enables.
Each pulse module channel exposes the following data in the Profibus cyclic I/O image:
| Signal | Direction | Width | Meaning |
|---|---|---|---|
| PULSE | Output to drive | 1 bit per channel | Pulse train at the configured frequency |
| DIR | Output to drive | 1 bit per channel | Direction (0 = positive, 1 = negative) |
| ENA (enable) | Output to drive | 1 bit per channel | Hardware enable of the drive stage |
| STS (status) | Input from drive | 1 bit per channel | Drive ready / fault flag |
| CNT (counter value) | Input from module | 32 bit per channel | Current pulse count (read back for position verification) |
Configuration Limits and Frequency Derating
The 10 kHz ceiling is not a hard limit of the silicon; it is the guaranteed frequency given worst-case cable capacitance of 2 nF per metre and a 30 m cable. If you wire the drive within 5 m of the ET 200S terminal block and use twisted-pair shielded cable, field installations have shown reliable operation at 20 kHz. However, treat 10 kHz as the engineering limit, especially when driving stepper motors where pulse rate sets the rotational speed:
For a 1.8° stepper motor (200 full steps per revolution) and a 10 kHz maximum pulse rate:
speed_rpm = (pulse_frequency / steps_per_revolution) * 60 speed_rpm = (10000 / 200) * 60 = 3000 rpm
If microstepping is used (e.g. 1/10 microstepping on a 1.8° motor = 2000 steps/rev), the maximum speed drops accordingly:
speed_rpm = (10000 / 2000) * 60 = 300 rpm
For servo drives, the pulse count is typically a fraction of the encoder resolution (e.g. one pulse = 1/4096 of a motor revolution if electronic gearing is 4096). The frequency ceiling is therefore usually acceptable for point-to-point positioning, but inadequate for continuous high-speed spindle-type applications.
Solution 2: FM 352-5 High-Speed Boolean Processor
The FM 352-5 is a function module that mounts in the S7-300 backplane and provides high-speed digital processing independent of the CPU scan time. The module is documented under the Siemens support entry for FM 352-5. Its primary use is high-speed Boolean processing at cycle times as low as 1 µs, but it is also capable of producing pulse trains with direction control and ramp-up/ramp-down profiles suitable for stepper drives.
Key parameters:
| Attribute | Value |
|---|---|
| Module type | Function module (FM) |
| Slot | Any S7-300 backplane slot that accepts FMs |
| Digital outputs | 12 (8 fast outputs up to 1 MHz, plus 4 standard) |
| Digital inputs | 12 (8 fast inputs up to 1 MHz) |
| Max output frequency | 1 MHz on the high-speed channels |
| Programming | Graphical configuration under STEP 7 with FM 352-5 configurator |
| Number of axes per module | Depends on the Boolean program; up to 4 axes are practical |
A single FM 352-5 can therefore deliver four pulse-and-direction channels at frequencies far above the 10 kHz limit of the ET 200S approach. To reach seven axes you would either:
- Use two FM 352-5 modules in the S7-300 rack (8 axes total), or
- Combine one FM 352-5 (4 axes, high speed) with one ET 200S 4×
6ES7138-4DD01-0AB0(8 channels, low speed), giving 12 axes from which 7 are used.
The FM 352-5 is configured with the included FM 352-5 Configuration Tool, which is launched from STEP 7. The configuration yields a DB (instance data block) plus an FB that the user program calls. The FB exposes inputs for target position, target velocity, acceleration, deceleration, and a start bit.
Ramp Profile Calculation
The trapezoidal velocity profile generated by the FM 352-5 follows standard motion equations. For an axis that must traverse a distance S in time T with constant acceleration a and deceleration -a:
v_max = (S / T) + (a * T / 4) (trapezoidal, where T > sqrt(2*S/a))
For a triangular profile (no constant velocity segment), the peak velocity is:
v_peak = sqrt(a * S) (triangular, where T = 2*sqrt(S/a))
The FM 352-5 accepts acceleration and deceleration in pulses/s² directly. For a servo with 4096 pulses/rev at a peak velocity of 3000 rpm (50 rev/s):
v_peak_pps = 50 * 4096 = 204800 pulses/s a_pps2 = 204800 / 0.05 s = 4,096,000 pulses/s² (50 ms to reach v_peak)
Confirm the value remains within the FM 352-5's 1 MHz ceiling, which it does by a factor of approximately 5. Slower ramps (200 to 500 ms) are typical in packaging machinery and remain comfortably within limits.
Solution 3: Migration to S7-1500 with TM PTO Technology Modules
If a controller change is acceptable, the S7-1500 platform is the modern answer. The TM PTO technology module (order numbers in the 6ES7553-1xxx0-xxx0 range, depending on output type) provides 4 high-speed PTO channels per module with the following documented characteristics (see Pulse Train Output (PTO) for S7-1500 in the TIA Portal Help):
- 4 PTO channels per TM PTO module.
- 24 V push-pull outputs, opto-isolated.
- Maximum output frequency up to 1 MHz per channel (configured per channel).
- Pulse-and-Direction or CW/CCW modes.
- Integrated homing, jog, and absolute/relative positioning technology objects in TIA Portal.
- Two modules (8 PTO channels) require only two free slots in the S7-1500 backplane.
For seven axes, two TM PTO modules deliver 8 channels with one spare. The configuration is performed entirely in TIA Portal V20 (or later) under Technology Objects → PTO. Each axis is configured with a technology object of type "PTO", with parameter sets for drive interface (output addresses), encoder feedback (optional), mechanical ratios, and dynamic limits.
For an S7-1500 system, the engineering effort is dramatically lower than for an ET 200S Profibus DP pulse module solution: the technology objects are pre-defined, the motion FB (MC_Power, MC_MoveAbsolute, MC_MoveRelative, MC_Home, MC_Stop) are part of the standard PLC open library, and diagnostic events appear in the TIA Portal online view with detailed cause codes.
Solution 4: Distributed Smart Servo Drives
A common modern architecture removes pulse generation from the PLC entirely. Each axis is driven by an intelligent servo drive (Siemens SINAMICS V90 with Profinet, or third-party units such as Yaskawa Sigma-7, Mitsubishi MR-JE, etc.) that accepts a setpoint position, velocity, or torque over a bus. The PLC computes the target and writes it via Profinet IRT, Profibus DP-V2, or even a single analog ±10 V command.
This approach scales to any number of axes (8, 16, 32, more) and decouples the motion controller cycle from the PLC OB1 scan. The downside is the higher per-axis cost of intelligent drives versus stepper drives, and the requirement for commissioning software per drive family.
Topology and Wiring
The typical cabinet topology for Solution 1 (ET 200S pulse modules) is illustrated below. The CPU S7-314 2DP acts as Profibus DP master. A single ET 200S station with IM 151-1 interface module houses the four pulse modules. Each pulse module routes PULSE, DIR, and ENA through a shielded twisted-pair cable to a stepper or servo drive. The 24 V power module in the ET 200S backplane supplies the pulse module logic, while the load supply to the drive is taken from a separate 24 V power supply with adequate current rating.
[CPU S7-314 2DP, X2: Profibus DP master] | | Profibus DP, 1.5 Mbps, 6XV1830-0EH10 cable | [IM 151-1 STANDARD] -> [PM-E 24 V DC] -> [6ES7138-4DD01-0AB0] ch1 --> Drive Axis 1 [6ES7138-4DD01-0AB0] ch2 --> Drive Axis 2 [6ES7138-4DD01-0AB0] ch3 --> Drive Axis 3 [6ES7138-4DD01-0AB0] ch4 --> Drive Axis 4 [6ES7138-4DD01-0AB0] ch5 --> Drive Axis 5 [6ES7138-4DD01-0AB0] ch6 --> Drive Axis 6 [6ES7138-4DD01-0AB0] ch7 --> Drive Axis 7 (ch8 spare / disabled)
Cable and Shielding Rules
- Use 24 AWG to 22 AWG (0.25 to 0.5 mm²) twisted-pair shielded cable, one pair per signal (PULSE/DIR share a 4-wire cable with ENABLE and ground return).
- Maximum recommended length: 30 m at 10 kHz; 10 m above 10 kHz; 3 m above 100 kHz.
- Ground the shield at the cabinet entry panel only; do not ground both ends (avoid ground loops).
- Separate the pulse cables from power cables by at least 200 mm, or use a divided cable tray.
- Twist the 24 V supply and 0 V return for each pulse module pair to cancel common-mode noise.
STEP 7 / TIA Portal Configuration
The exact configuration steps differ between STEP 7 V5.x (classic) and TIA Portal. Both ultimately generate a Profibus DP slave entry for the ET 200S station and place the pulse modules in the slot table. The procedure is summarized below for STEP 7 V5.7 (still common in brownfield S7-300 installations).
STEP 7 V5.x Configuration Steps
- Open SIMATIC Manager and load the S7-300 station that contains the 314-2DP.
- Open HW Config and select the ET 200S from the catalog under “Profibus DP → ET 200S”.
- Drag the IM 151-1 STANDARD interface module to the Profibus subnet, assigning a unique DP address (e.g. 4).
- Insert the PM-E 24 V DC power module in slot 1 of the ET 200S rack.
- Insert four 6ES7138-4DD01-0AB0 modules in slots 2 through 5. Each occupies 2 bytes of output and 4 bytes of input in the Profibus I/O image.
- Double-click each pulse module to open its properties. Set:
- Operating mode = "Pulse output, pulse and direction" or "Pulse output, CW/CCW".
- Output format = "Pulses per second (Hz)" or "Pulses per time unit" depending on the FB used.
- Maximum frequency = 10000 (Hz) for 10 kHz applications.
- Acceleration/deceleration = ramp time in ms (typical: 100 to 500 ms).
- Diagnostics = enable "Short circuit" and "Missing load voltage".
- Save and compile the HW Config. The cyclic I/O addresses are assigned automatically (e.g. Outputs 0..7 and Inputs 0..15 for the first module).
- Use the Siemens standard FB "SFB 49" (Pulse Width Modulation) or the user FB from the ET 200S pulse module HSP to start, stop, and monitor each axis. Alternatively, integrate the pulse generation into the user's own OB1 logic, writing frequency and direction setpoints to the module's output words.
Structured Text Example: Starting Axis 1 at 5000 Hz, Direction = Forward
// Axis 1 control word - PULSE Module 1, Channel 0
// Output address from HW Config: QW 0 (control), QW 2 (frequency), Q0.0 (DIR bit)
// 1. Set direction = 0 (forward)
"Axis_1_DIR" := FALSE;
// 2. Wait one OB1 scan to allow the drive to latch direction
// (Direction must be stable 1 ms before the first pulse edge)
// 3. Write frequency in Hz to the module's frequency setpoint word
"Axis_1_Freq_Word" := 5000;
// 4. Start the pulse generator by setting the start bit
"Axis_1_Start" := TRUE;
// 5. Pulse train begins on the next module cycle (~1 ms for the ET 200S pulse module)
Ladder Logic Example: Jogging Axis 3
// Network 1: Direction select
A "Jog_Axis3_Forward" // I0.5 - operator pushbutton
AN "Jog_Axis3_Reverse" // I0.6
= "Axis_3_DIR" // Q4.0
A "Jog_Axis3_Reverse"
AN "Jog_Axis3_Forward"
= "Axis_3_DIR_Reverse_Indicator" // M20.0 (for HMI feedback)
// Network 2: Run with jog frequency
A "Jog_Axis3_Forward"
O "Jog_Axis3_Reverse"
AN "Axis_3_Fault" // I0.7 - drive OK contact
= "Axis_3_Start" // Q4.1 - latched to pulse module start bit
Pulse Train Output Signal Characteristics
The electrical interface of the pulse module outputs is identical to a Siemens 24 V digital output, with one critical caveat: the pulse rise and fall times determine the maximum usable frequency. The ET 200S 6ES7138-4DD01-0AB0 specifies a typical rise/fall time of 5 µs at 24 V / 0.5 A, which gives a clean edge up to about 50 kHz. The 10 kHz software limit is conservative, accounting for cable capacitance and opto-isolator rise times in the receiving drive.
For the FM 352-5, the eight high-speed outputs use differential 24 V line driver topology (RS-422 compatible) with rise times of 1 µs or less, enabling the 1 MHz maximum.
For a deeper discussion of the receiver-side requirements (common-mode range, input voltage tolerance, and cable capacitance limits) consult the Texas Instruments differential PTO interface brief (TIDUC30), which documents the SN75174 / SN75175 line driver/receiver family used in many stepper and servo drives.
Comparison Matrix: Which Solution for Which Application?
| Criterion | ET 200S Pulse Module | FM 352-5 | S7-1500 TM PTO | Smart Servo Drives |
|---|---|---|---|---|
| Max channels per module | 2 | 4 (practical) | 4 | 1 per drive |
| Max frequency | 10 kHz (typ.) | 1 MHz | 1 MHz | Bus-limited (no PTO) |
| Voltage level | 24 V | 24 V diff. | 24 V diff. | Bus / analog |
| CPU scan impact | Low (module is autonomous) | None (autonomous) | None (autonomous) | None (drive is autonomous) |
| Engineering effort | Medium | High (graphical config tool) | Low (TIA Portal tech objects) | Medium-High (per drive family) |
| Per-axis cost | Low | High | Low | Medium-High |
| Backplane slot required | No (distributed) | Yes (1 per module) | Yes (1 per module) | No |
| Best for | Low-speed stepper, packaging | High-speed point-to-point | Modern high-speed motion | Synchronised multi-axis, CNC |
Commissioning and Verification
A structured commissioning sequence avoids the classic "it ran on the bench but not on the machine" surprises. The sequence below applies to the ET 200S pulse module solution; the FM 352-5 follows a similar logic with different parameter names.
- Visual check. Verify the IM 151-1, PM-E, and four pulse modules are clipped into the TM-P or TM-B terminal modules with the bus connector tabs in place. Each pulse module should display a green SF (system fault) and a green BF (bus fault) LED off under normal conditions.
- Profibus address. Confirm the IM 151-1 rotary switches match the configured DP address (e.g. 4). A mismatch is the most common cause of "slave not found" errors during PG online.
- PG online. In STEP 7, go online with the CPU and open the ET 200S slave in HW Config. The slave should show "Module OK" for every slot. If a slot shows "Module not OK" or "Incorrect module in slot", check the article numbers and the terminal module keying (the mechanical coding on the TM-P terminals prevents insertion of the wrong module type).
- Watch table test. Open a VAT watch table and force the output bits for axis 1: set the DIR bit to 0, set the start bit, and write 1000 to the frequency word. The drive should rotate at 1000 / 200 = 5 rev/s = 300 rpm for a 1.8° stepper with no microstepping. Use a handheld tachometer to verify the mechanical speed. Reverse the DIR bit and re-test.
- Frequency sweep. With the drive disconnected (mechanical shaft free), sweep the frequency word from 100 Hz to 9000 Hz in 1000 Hz increments, holding each value for 2 seconds. The pulse module should not report a diagnostic interrupt, and the SF LED should remain off.
- Load test. Reconnect the mechanical load and repeat the frequency sweep under torque. Monitor the drive's following error (or stepper stall flag) and confirm the motion completes without alarming.
- Emergency stop verification. Trigger the E-Stop and confirm that all seven pulse generators stop within one Profibus cycle (typically 5 ms at 1.5 Mbps), and that the drive's STO (Safe Torque Off) input de-energises the motor within the time specified by the drive manual (typically 5 to 25 ms).
- Diagnostic interrupt handling. Confirm that OB82 (diagnostic interrupt) is loaded in the CPU. The pulse module raises a diagnostic interrupt on short circuit, missing load voltage, or frequency overload. The interrupt OB must call the diagnostic FB to clear the condition or the module will remain in fault state.
Troubleshooting Matrix
| Symptom | Likely Root Cause | Diagnostic Check | Corrective Action |
|---|---|---|---|
| ET 200S slave shows "Station failure" on PG online | Wrong Profibus address or termination missing | Check IM 151-1 rotary switches, measure 220 Ω on the bus end terminator | Set the correct address, enable terminating resistor on the last slave |
| Pulse module shows "Incorrect module in slot" | Slot assignment mismatch in HW Config, or wrong terminal module keying | Compare order number on module label with HW Config | Recompile HW Config and download; verify TM-P keying matches module type |
| No pulses on the output, drive does not move | Enable bit not set, load voltage missing | Force the enable bit in the VAT, measure 24 V on the pulse module load supply terminals | Apply load voltage, check the load voltage monitoring parameter in the module properties |
| Motor runs at half expected speed | Microstepping enabled on drive, pulse count per rev higher than expected | Check drive's electronic gearing setting | Adjust either the drive's steps/rev or the frequency setpoint |
| Motor stalls at high speed | Pulse frequency exceeds 10 kHz, or torque insufficient | Measure pulse frequency with oscilloscope on the output | Reduce the commanded frequency or use FM 352-5 for higher rates |
| Position drift over time | Electrical noise on DIR line causes reverse steps | Oscilloscope the DIR line for glitches | Twist the DIR/PULSE pair, add RC filter on the drive input, separate cable from VFD |
| Diagnostic interrupt OB82 fires repeatedly | Short circuit on a pulse output | Read the diagnostic buffer of the pulse module in PG online | Inspect wiring, remove the short, acknowledge the diagnostic interrupt |
| CPU goes to SF (system fault) when starting motion | OB82 or OB121 not loaded, uncalled diagnostic event | Check the CPU diagnostic buffer for the event code | Load OB82 (diagnostic interrupt) and OB121 (programming error) in the CPU |
Frequently Asked Questions
Can the S7-314 2DP generate PTO without additional hardware?
No. The S7-314 2DP (non-"C" variant) has no on-board high-speed pulse outputs. The "C" variants (S7-312C, S7-313C-2DP, S7-314C-2DP) integrate up to four 24 V PTO channels. For a non-"C" 314-2DP, PTO must be added via ET 200S pulse modules, FM 352-5, or migrated to an S7-1500 with TM PTO.
How many ET 200S pulse modules are needed for 7 PTO outputs?
Four modules of type 6ES7138-4DD01-0AB0 provide 8 channels. Use 7 channels for the application and leave the 8th as a spare, or use the 8th for an electronic cam or a handwheel input.
What is the maximum pulse frequency of the 6ES7138-4DD01-0AB0?
10 kHz per channel is the documented limit, although field installations reliably reach 20 kHz on short cables. Above 10 kHz, switch to the FM 352-5 (up to 1 MHz) or the S7-1500 TM PTO (up to 1 MHz per channel).
Can the FM 352-5 produce ramp-up and ramp-down profiles?
Yes. The FM 352-5 configuration tool defines acceleration and deceleration rates in pulses/s², generating trapezoidal or triangular velocity profiles suitable for stepper drives. For S-curve profiles or jerk-limited motion, migrate to S7-1500 TM PTO with TIA Portal technology objects, which support S-curve ramps natively.
Is it possible to keep the S7-314 2DP and add the pulse outputs over Profinet instead of Profibus?
Yes. Use the IM 151-3 PN Profinet interface module in the ET 200S station and connect it to a Profinet subnet. The CPU S7-314 2DP would need a CP 343-1 (e.g. 6GK7343-1EX30-0XE0) for Profinet IO controller functionality, because the onboard Profibus interface does not support Profinet. The pulse module article number 6ES7138-4DD01-0AB0 is identical for both Profibus and Profinet variants of the ET 200S station.
What cable type should be used between the ET 200S pulse module and the drive?
Use 24 AWG to 22 AWG (0.25 to 0.5 mm²) twisted-pair shielded cable, with one pair for PULSE/DIR, plus a separate pair for ENA and 0 V return. Maximum recommended length is 30 m at 10 kHz. Ground the shield at the cabinet entry panel only.
What is the best migration path if the application grows beyond 10 kHz or 7 axes?
Migrate the motion task to an S7-1500 with TM PTO technology modules. The TM PTO delivers 4 channels per module, up to 1 MHz, with integrated S-curve ramps, homing, and PLC open FB interfaces (MC_Power, MC_MoveAbsolute, MC_MoveRelative, MC_Home, MC_Stop). Two modules cover 8 axes with margin for future expansion.