Configuring AS-i Master 3RK7137-6SA00-0BC1 in ET 200SP TIA Portal

David Krause13 min read
SiemensTIA PortalTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Configuring AS-i Master 3RK7137-6SA00-0BC1 in SIMATIC ET 200SP with TIA Portal

This technical reference describes how to integrate the AS-i Master 3RK7137-6SA00-0BC1 into a SIMATIC ET 200SP station headed by a CPU 1510SP-1 PN, how to bring GEA process-valve slaves online without GSD files, and how to scale to dense installations of 48 slaves per network using dual-master topologies. The article follows official Siemens engineering guidance for the AS-Interface Safety Engineering Manual collection and the SIMATIC ET 200SP AS-i Master manual.

Scope. AS-i (Actuator Sensor Interface, IEC 62026-2) is a single-master fieldbus that connects binary sensors and actuators over a two-conductor yellow profile cable. Each ET 200SP station may host one or more AS-i Master 3RK7137-6SA00-0BC1 modules, each acting as the single master of its own AS-i segment.

1. AS-i Network Architecture in ET 200SP

An AS-i network always comprises three logical elements: the master, an AS-i power supply unit (AS-i PSU), and the slaves. The master is the only bus arbiter; slaves have no bus-access intelligence of their own. Per the official Siemens Safety Engineering with AS-Interface manual, "a master module collects the process images of all connected AS-i slaves and exchanges them cyclically with the higher-level controller" — see Creating an AS-Interface network.

1.1 Topology Rules

  • AS-i is a single-master system; the 3RK7137-6SA00-0BC1 is the only master allowed per yellow segment.
  • Cable type: 2 x 1.5 mm² mechanically keyed yellow profile cable (piercing technology).
  • Maximum cable length: 100 m per segment without repeater; up to 300 m with two repeaters.
  • Cycle time: 5 ms for 31 standard slaves, 10 ms for 62 extended slaves.
  • AS-i supply voltage: 30 V DC (29.5 V to 31.6 V) from a dedicated AS-i PSU such as 3RX9501-0BA00.

1.2 Logical Channel Model (A and B)

AS-i Version 3 introduced extended addressing. Each base address 1-31 may host two logical sub-addresses: A and B. This doubles the maximum slave count per master from 31 to 62.

Mode Slave Count per Master Cycle Time Bit Width per Slave
Standard (V2.0) 31 (addresses 1-31) 5 ms 4 DI / 4 DQ
Extended (V3.0) 62 (1A-31A and 1B-31B) 10 ms 4 DI / 4 DQ
Important. Not every AS-i slave supports B-channel addressing. Always verify the slave datasheet. If your 48 slaves are mixed (some A-only, some A/B capable), plan the bus layout before commissioning.

2. Hardware Components Required

2.1 Head Station and Interface Module

  • CPU 1510SP-1 PN (6ES7510-1SJ01-0AB0 or higher MLFB): SIMATIC ET 200SP CPU with PROFINET interface. Functions as PROFINET IO controller and ET 200SP head.
  • AS-i Master 3RK7137-6SA00-0BC1: single-master AS-i V3.0 interface module for ET 200SP, occupies one slot in the BaseUnit.
  • BaseUnit BU20-A5 (6ES7193-6BP20-0BA0 or -0DA0 depending on feed) for the AS-i Master slot.

2.2 AS-i Power Supply Unit

The AS-i Master 3RK7137-6SA00-0BC1 does not generate the 30 V DC AS-i supply. You must install a separate AS-i PSU such as 3RX9501-0BA00 or 3RX9503-0BA00. Wire the PSU in parallel with the yellow cable; the master itself taps both data and power from the same two conductors.

2.3 AS-i Slaves (GEA Process Valves)

For process-valve applications the GEA ASi Valve module exposes a standard AS-i slave profile:

  • 2 DI: feedback bits (open / closed position indicators)
  • 1 DQ: command bit (open or close coil drive)
  • Total 48 slaves in the project, each typically on its own pneumatic actuator node.

3. AS-i Master 3RK7137-6SA00-0BC1 Technical Data

Excerpted from the official AS-i Master SIMATIC ET 200SP manual (PDF):

Parameter Value
Article number 3RK7137-6SA00-0BC1
AS-i specification V3.0 (extended addressing)
Slaves per master 62 (A/B), 31 (standard)
Cycle time 5 ms (31 slaves) / 10 ms (62 slaves)
PROFINET interface via ET 200SP backplane bus
Supported PROFINET redundancy R1 (with IM 155-6 PN R1, firmware ≥ V3.0)
Configuration TIA Portal V15.1 or higher
AS-i power consumption < 200 mA from AS-i PSU
Diagnostic LEDs PWR, SF, BF, A-channel, B-channel

4. TIA Portal Hardware Configuration

4.1 Adding the AS-i Master to the Project

  1. Open the device view of the CPU 1510SP-1 PN.
  2. Insert a new slot; the AS-i Master 3RK7137-6SA00-0BC1 must be ordered from the catalog under AS-Interface > AS-i Master > SIMATIC ET 200SP.
  3. Assign a BaseUnit BU20-A5 to the slot. Choose the feed-in variant if the module is the first on the segment.
  4. Confirm the device name and PROFINET device number; the master is a PROFINET device sub-module of the ET 200SP station and inherits the IP configuration from the head.

4.2 Slot and Module Properties

In the inspector window you can edit the following parameters:

Parameter Default Notes
Number of slaves A-channel 31 Reduce if you use only physical slaves < 31
Number of slaves B-channel 31 Set to 0 if no B-channel slaves are present
AS-i cycle monitoring Enabled Generates SF if cycle exceeds 100 ms
Diagnostic interrupt Enabled OB82 fires on slave faults
Process image update Cyclic Toggle to "on change" for slow actuators

5. AS-i Slave Configuration Without GSD Files

AS-i slaves are not engineered via PROFINET GSD files. The master learns the slave catalog at runtime using the AS-i "scan slaves" procedure. The standard says "you do not need to project the AS-i slaves into HW config".

5.1 Scan Procedure

  1. Compile the station and download hardware configuration to the CPU.
  2. Open the AS-i Master's online diagnostics in TIA Portal (Online & diagnostics > AS-Interface).
  3. Click "Scan AS-i slaves". The master enters learn mode and detects all physically connected slaves within ~5 s.
  4. Detected slaves appear in a list with their I/O configuration (input bits, output bits, I/O code, ID code, profile).
  5. Click "Store slave configuration" to write the learned configuration to non-volatile memory on the master.

5.2 Manual Address Assignment

Slaves are auto-numbered during scan, but in dense installations you typically want a deterministic address layout. Use either:

  • AS-i addressing device (e.g. 3RK1904-2AB02) to set addresses before power-on, or
  • Online "Change slave address" function in TIA Portal to overwrite the auto-assigned address.

5.3 Why No GSD Files Are Needed

PROFINET GSD files describe PROFINET devices. AS-i slaves are not PROFINET devices; they are AS-i devices. The only PROFINET-aware element on the bus is the AS-i Master 3RK7137-6SA00-0BC1. The master exposes the AS-i process image to PROFINET as a single sub-module with 16 bytes of input and 16 bytes of output, regardless of how many slaves are connected. Therefore:

  • No GSD import is required for the GEA valve slaves.
  • No I&M data is loaded per valve.
  • No port interconnectors are needed.
  • The PLC program accesses slaves via the master's process image using a fixed slot offset (see Section 7).
Common misconception. AS-i slaves are not PROFINET slaves. The 3RK7137-6SA00-0BC1 is the only PROFINET device; the AS-i slaves appear as plain bit data inside the master's PROFINET payload.

6. Multi-Master Strategy for 48 Slaves

If you have 48 physical slaves and they are all A-only or A/B mixed, you have two architectural options:

6.1 Option A — Single Master with Extended Addressing

If all 48 slaves support A/B sub-addressing and the valve profile permits both sub-addresses per node, you can run 48 slaves on one AS-i Master. The maximum theoretical limit is 62 (31A + 31B). In this case:

  • Configure master in V3.0 mode.
  • Each base address hosts two valves: e.g. 1A and 1B, 2A and 2B, etc.
  • Cycle time: 10 ms.
  • Total AS-i I/O: up to 248 DI + 248 DQ.

6.2 Option B — Dual Master (Recommended for Mixed Populations)

If the valve slaves are A-only, or if you want to separate process zones for safety / maintenance reasons, install two AS-i Master 3RK7137-6SA00-0BC1 modules in the same ET 200SP station:

  • Master 1 manages 24 valves (addresses 1-24, A-channel).
  • Master 2 manages 24 valves (addresses 1-24, A-channel of a separate yellow segment).
  • Each master requires its own AS-i PSU (or one PSU feeding two segments via decoupling).
Option Single Master V3.0 Dual Master V2.0 / V3.0
AS-i PSU count 1 1 or 2
Cycle time per segment 10 ms 5 ms
Address conflict risk Low (A/B disambiguates) None (independent segments)
Failover isolation All 48 slaves lost on master fault Only 24 lost
PROFINET slots used 1 2
Recommended use Homogeneous A/B slaves Mixed or critical applications
Recommendation. The Siemens manual explicitly recommends adding a second master when the slave count exceeds 31 if any slave does not support extended addressing. For the GEA process valves, verify the datasheet before selecting Option A; otherwise deploy Option B as already chosen.

7. PLC Program Access to AS-i Process Image

7.1 Input Image Mapping

The AS-i Master exchanges 16 bytes of input data with the CPU via PROFINET. For each AS-i slave address n (1 to 31), 4 input bits are mapped:


Byte 0..3 = Inputs of slaves 1..4 (4 bits each, packed)
Byte 4..7 = Inputs of slaves 5..8
...
Byte 28..31 = Inputs of slaves 29..31 + reserved

Concretely, slave 1 input bit 0 = %I0.0, slave 1 input bit 3 = %I0.3, slave 2 input bit 0 = %I0.4, etc.

7.2 Output Image Mapping

Same scheme, output direction:


%Q0.0  = Slave 1, output bit 0
%Q0.1  = Slave 1, output bit 1
%Q0.2  = Slave 1, output bit 2
%Q0.3  = Slave 1, output bit 3
%Q0.4  = Slave 2, output bit 0
...

7.3 STL Example: Reading Valve Feedback


// GEA valve at AS-i slave address 12
// Bit 0 = open feedback, Bit 1 = closed feedback, Bit 2 = warning
// Output bit 0 = open command

      L     %I1.4       // Slave 12, bit 0 (open feedback)
      T     "DB_Valve".Feedback_Open_S12

      L     %I1.5       // Slave 12, bit 1 (closed feedback)
      T     "DB_Valve".Feedback_Closed_S12

      U     "DB_Valve".Cmd_Open_S12
      =     %Q1.4       // Slave 12, output bit 0 (open command)

7.4 Symbolic Tag Names with Standard Tags

For better readability, enable the "Standard tags" option in the master's properties. TIA Portal then creates a pre-mapped symbol table:


AS_i_Outputs   BOOL[4]  starting at QB0
AS_i_Inputs    BOOL[4]  starting at IB0
AS_i_Diag      WORD     at IW32

8. Firmware, Redundancy, and PROFINET System Redundancy R1

Current firmware of the 3RK7137-6SA00-0BC1 (≥ V2.0) supports operation under PROFINET System Redundancy R1. This requires:

  • ET 200SP station head: IM 155-6 PN R1 (6ES7155-6AU30-0CN0 or higher) instead of the standard IM 155-6 PN.
  • Two PROFINET controllers (H-system) configured with redundancy role "R1 device" for the station.
  • CPU firmware compatible with the redundancy role (CPU 1510SP-1 PN ≥ V2.8).

When R1 is active, the AS-i Master survives a controller failover without dropping its 48 valves. State of the AS-i process image is preserved in the master's local memory and resynchronized on PROFINET reconnect.

Confirm the firmware version of the 3RK7137-6SA00-0BC1 you receive. Early V1.x firmware did not support R1. Update via TIA Portal (Online & diagnostics > Firmware update) before commissioning redundancy.

9. AS-i Cabling and Power Supply Wiring

Yellow profile cable (AS-i) 3RX9501 PSU 3RK7137 Master Slave 1 Slave 2 ... Slave N

9.1 Wiring Rules

  • Wire the AS-i PSU's two output terminals (ASI+ and ASI-) directly to the yellow profile cable.
  • The master's BaseUnit spring terminals tap ASI+/ASI- internally from the backplane.
  • Do not place a fuse in series with ASI+ — the PSU already limits current.
  • Terminate the cable ends with the AS-i terminating piece (e.g. 3RX9801-0AA00) if reflections are observed on long runs.
  • Maintain > 20 mm separation from VFD power cables.

9.2 Voltage Drop Calculation

For a 100 m loop carrying 24 valves @ 50 mA each plus 200 mA master draw:


Total_current = 24 * 0.05 + 0.2 = 1.4 A
Cable_resistance = 2 * 100 m * 0.0133 ohm/m = 2.66 ohm
Voltage_drop = 1.4 * 2.66 = 3.72 V

If 30 V is supplied and drop is 3.7 V, slave end sees 26.3 V — below the 29.5 V lower limit. Solutions: thicker cable, shorter loop, or a second AS-i PSU mid-cable.

10. Diagnostics and Error Codes

10.1 LED States on the 3RK7137-6SA00-0BC1

LED State Meaning
PWR (green) On 24 V backplane OK
PWR (green) Off No 24 V supply at BaseUnit
SF (red) On Group fault (slave failure, configuration mismatch)
SF (red) Flashing Configuration error during teach-in
BF (red) On AS-i cable fault or no slaves detected
BF (red) Flashing At least one slave missing
A (yellow) On A-channel active, slaves communicating
B (yellow) On B-channel active (extended mode)

10.2 Common Error Codes (per AS-i V3.0 specification)

Code Meaning Remedy
0x01 Slave not in learned list (LPS) Run "Store slave configuration"
0x02 Slave ID code mismatch Replace slave with matching profile
0x04 Slave I/O configuration mismatch Re-teach the slave
0x08 Slave does not respond Check yellow cable connection and 30 V supply
0x10 Address conflict (duplicate) Re-address the conflicting slave
0x20 Overcurrent on AS-i segment Reduce slave count or split into two segments

10.3 Online Diagnostics in TIA Portal

  1. Right-click the AS-i Master in the device view.
  2. Select Online & diagnostics.
  3. Open the AS-Interface tab. The "Configured slaves" and "Detected slaves" tables are shown side-by-side.
  4. For each slave with a fault, click the row to read the diagnostic buffer.

11. Commissioning Checklist

11.1 Pre-Power Checks

  • [ ] AS-i PSU output voltage measured at end of cable: ≥ 29.5 V DC.
  • [ ] Each valve slave address set to expected value with the addressing device.
  • [ ] Yellow cable routed clear of VFD cables and welding circuits.
  • [ ] TIA Portal project compiled without errors.

11.2 Power-On Steps

  1. Power up ET 200SP station.
  2. Verify PWR LED green on every BaseUnit.
  3. Verify PWR + A-channel LED on AS-i Master 3RK7137-6SA00-0BC1.
  4. Open TIA Portal, go online, and run Scan AS-i slaves.
  5. Confirm the detected list equals the planned list (count and addresses).
  6. Click Store slave configuration.

11.3 Functional Verification

  • Force %Q1.4 (open command for slave 12) from the watch table.
  • Verify the valve actuator physically moves within 2 s.
  • Read %I1.4 and %I1.5 to confirm feedback transitions.
  • Repeat for a sample of valves across all 48 addresses.
  • Disconnect one valve, confirm BF LED flashes and OB82 is triggered.

12. FAQ

Do I need a GSD file for AS-i slaves such as the GEA ASi Valve?

No. AS-i slaves are not PROFINET devices and are not configured via GSD. The AS-i Master 3RK7137-6SA00-0BC1 learns all connected slaves via the "Scan AS-i slaves" function in TIA Portal, and you store the configuration with one click. Only the master itself needs to be present in the HW catalog.

Can one AS-i Master 3RK7137-6SA00-0BC1 handle 48 slaves?

A single V3.0 master supports up to 62 slaves using A/B extended addressing. However, if your 48 slaves are A-only or you want fault isolation, install a second AS-i Master in the same ET 200SP station. Each master needs its own yellow cable segment and its own AS-i power supply unit. Siemens recommends dual-master layouts for installations exceeding 31 slaves unless every slave explicitly supports B-channel.

How is a GEA ASi Valve with 2 DI and 1 DQ mapped in the PLC?

The 2 feedback bits appear as inputs at slave address n, bit positions 0 and 1 (%In.0, %In.1). The 1 output command sits at slave address n, bit 0 (%Qn.0). With 4 slaves packed per input byte, slave 12 occupies %I1.4-%I1.7 for inputs and %Q1.4-%Q1.7 for outputs.

Does the 3RK7137-6SA00-0BC1 support PROFINET redundancy R1?

Yes, with firmware V2.0 or higher and a redundant ET 200SP interface module IM 155-6 PN R1. The master survives a controller failover and re-synchronizes the AS-i process image automatically. Update the master's firmware via TIA Portal before commissioning the redundancy role.

What diagnostic data is available when an AS-i slave fails?

The master triggers a diagnostic interrupt (OB82) with the failing slave address and the error code (0x01 to 0x20 per AS-i V3.0). In TIA Portal, navigate to Online & diagnostics > AS-Interface to view the live "Configured vs Detected" tables; missing slaves are highlighted in red and the BF LED on the master flashes until the slave is replaced or the configuration is updated.

Back to blog