Configuring BOP20 RPM Display on Sinamics G130 CU320-2PN

David Krause16 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Configuring BOP20 RPM Display on Sinamics G130 CU320-2PN: p0005 / p0006 Parameter Reference and Access-Lock Recovery

This technical reference covers commissioning of the BOP20 (Basic Operator Panel 20) on a Sinamics G130 chassis drive with CU320-2PN Control Unit so the panel displays motor speed (RPM), output current, and output voltage. The article directly addresses a common field symptom: the drive runs correctly, the engineering tool (Starter or TIA Portal with Startdrive) shows the correct actual speed on r0021, but the BOP20 2-line LCD remains pinned to a non-speed value (typically r0000 or r0020) and the parameters p0005[0], p0005[1], and p0006 appear read-only. The root cause is almost always a parameter-access condition on the Control Unit drive object, not the value selection itself.

1. Problem Statement and Symptom Map

Typical field observation on a Sinamics G130 chassis unit (315 kW class) with CU320-2PN Control Unit and a BOP20 plug-in operator panel:

  • Drive accepts run command from PLC or terminal, motor accelerates to setpoint, Starter / Startdrive online trace shows r0021 (speed actual value, smoothed) and r0022 (unsmoothed) updating correctly.
  • BOP20 2-line LCD does not display RPM. The display shows r0000 (operating display / status word) or toggles between r0000 and r0020 (setpoint) and never shows r0021 (smoothed actual speed).
  • Writes to p0005[0], p0005[1], p0006 are rejected. Parameters appear "fixed" at p0005[0] = 0 and p0006[0] = 4 even when p0003 is cycled between standard (1), extended (2), and expert (3).

The correct value pair for a customer RPM display is known: p0005[0] = 21, p0005[1] = 27, p0006 = 0. The problem is that the write to these parameters fails or is masked before the value is applied. The drive rejects the access, not the value.

2. BOP20 Display Architecture on the G130

The BOP20 connects to the front of the CU320-2PN via the operator-panel serial interface. Two parameters control what is shown:

Parameter Function Indices Default on G130
p0005 BOP display value selection (r-number) [0], [1] [0] = 0
p0006 BOP display mode (run / ready behavior) - 4
p0003 Parameter access level - 1 (standard)

p0005 has two indices so the BOP20 can show two different r-parameters when toggled with the FN key:

  • p0005[0] - value shown at the first FN press
  • p0005[1] - value shown at the second FN press

p0006 controls what the BOP20 displays during operation versus the ready state:

p0006 Operation (run) Ready (stop)
0 r0021 Toggles r0020 ↔ r0021
1 r0021 r0020
2 p0005 Toggles p0005 ↔ r0020
3 r0002 Toggles r0002 ↔ r0020
4 (default) p0005 p0005

With the factory default p0005[0] = 0 and p0006 = 4, the BOP20 always shows r0000 (operating display) - on the G130 in normal state this is the active command / fault word, not motor speed. The user must change at least p0005[0] to expose any meaningful process value.

3. Standard p0005 Values for the Sinamics G130

From the G130 / G150 List Manual (LH2 firmware family), the supported p0005 selections for the BOP20 are:

p0005 value Display content Source signal Unit
0 Operating display r0000 -
21 Speed actual value, smoothed r0021 RPM (1/min)
25 Output voltage, smoothed r0025 V
27 Current absolute value, smoothed r0027 A

Recommended customer-facing configuration:


p0005[0] = 21   ; speed (RPM) shown in operation
p0005[1] = 27   ; motor current shown after FN toggle
p0006    = 0    ; in operation show r0021, otherwise toggle r0020<->r0021
p0003    = 2    ; extended access (use 3 only if 2 still blocks a write)

Reference: SINAMICS G130/G150 List Manual (LH2), parameter section p0000-p0100.

4. Why p0005 and p0006 Are Not Writable: Five Field-Proven Root Causes

4.1 Drive is still in a commissioning state (p0010 ≠ 0)

The G130 / CU320-2 has a top-level commissioning parameter p0010. When p0010 ≠ 0, several display and control parameters change write behavior. In particular, after a quick-commissioning wizard (p0010 = 1) finishes and writes p3900 > 0, the drive does an internal reset of the operator panel interface. If a write to p0005 arrives within 1-2 seconds of p3900, the write can be silently dropped. Always set p0010 = 0, confirm p3900 = 0, wait 2-3 seconds, then write p0005 / p0006.

4.2 Parameter access level p0003 not at the required level

On most firmware builds, p0005 and p0006 are writable at standard access (p0003 = 1). On G130 LH3.x and later, certain display values are gated to extended (p0003 = 2) or expert (p0003 = 3). When p0003 is changed, the change itself is accepted but the parameter filter does not re-evaluate the writable list until the next parameter read. Power-cycle the CU, or perform a parameter reload, before retrying.

4.3 BOP20 local-control key lock is active

The BOP20 has a local key lock: pressing and holding P + FN for more than 3 seconds toggles the lock. When locked, the BOP20 display continues to update from the drive but every key press (P, +, -, >>) is ignored. The lock state is not stored in any r-parameter and is not visible in Starter. Symptoms are exactly what the user describes: the panel does not respond to edits. To clear, power-cycle the BOP20 by removing it from the CU front connector for 5 seconds, then re-seat it.

4.4 Drive is in Operation while the edit is attempted

On LH1 and early LH2 firmware, p0006 and p0005 are only writable in the "Ready to switch on" or "Operation disabled" state. If the drive is running under load with the ON/OFF1 command asserted, the BOP20 will silently reject the write without showing an error. Stop the drive, remove the ON command at the terminal / PLC, wait for r0002 to read 0 ("Operation disabled") or 1 ("Ready to switch on"), then perform the edit.

4.5 Know-How Protection (KHP) is active on the Control Unit drive object

Sinamics supports a password-based parameter protection (p7766, p7767, p7768). When KHP is enabled on the Control Unit drive object, protected parameters read back as the factory default and reject writes regardless of p0003. This matches the user's observation: p0005[0] always returns 0 and p0006 always returns 4, even after a confirmed write attempt. KHP must be disabled (p7766 = 0 with the correct password) before the BOP20 display parameters can be reconfigured.

Diagnostic tip: In Starter / Startdrive, navigate to the Control Unit drive object, right-click and select Properties → Know-how protection. If KHP is active, the panel will show "Activated" with an asterisk where the password field is. KHP on a different drive object (e.g., the Vector drive object) does not affect p0005 because p0005 lives on the Control Unit DO, not the Vector DO.

5. Step-by-Step Resolution Procedure

Apply these steps in order. Each step must be confirmed before moving to the next.

5.1 Confirm the drive is in a writable state

  1. Read r0002 on the BOP20 or in Starter. r0002 must report 0 ("Operation disabled") or 1 ("Ready to switch on").
  2. Remove the ON / OFF1 command source: de-assert the digital input wired to p0840 (ON/OFF1) at the PLC or terminal, or set p0840 = 0 from Starter.
  3. Read r0046.0 - it must be 0 (no missing enable).

5.2 Clear all active faults and alarms

  1. Read r0947[0..7] (current fault codes) and r2122[0..63] (current alarm codes).
  2. Resolve any active F-class fault. Active faults typically do not block p0005 writes, but firmware inconsistencies have been observed where a stuck fault on a non-active drive object holds the Control Unit DO in a "partial commissioning" state and rejects display writes.
  3. Acknowledge with p3981 = 0 -> 1 or via the BOP20 FN key (long press).

5.3 Power-cycle the BOP20 to clear the local key lock

  1. De-energize the drive (or use the CU320-2PN's removable terminal strip to de-couple control power if the cabinet supports it).
  2. Remove the BOP20 from the front of the CU320-2PN.
  3. Wait at least 5 seconds.
  4. Re-install the BOP20. The CU320-2PN performs a re-initialization of the operator-panel interface (the BOP20's backlight flashes during re-init).

5.4 Verify and raise the parameter access level

  1. From the BOP20, press P to enter parameter mode.
  2. Use the up / down arrow keys to scroll to p0003.
  3. Press P; the value field blinks.
  4. Use up / down to set p0003 = 3 (expert).
  5. Press P to confirm.

If the BOP20 will not accept the p0003 change, perform the same write from Starter / Startdrive where the access-level change is explicit and the result is observable. The relevant Starter action is: online → write p0003 = 3 → Copy RAM to ROM.

5.5 Write the display parameters from the BOP20

  1. Scroll to p0005, press P.
  2. Press >> (right arrow) to expose the index field; the display toggles between [0] and [1].
  3. With [0] selected, press P; use up / down to set 21; press P to confirm.
  4. Press >> to select [1], press P, set 27, press P.
  5. Scroll to p0006, press P, set 0, press P to confirm.

If the BOP20 rejects a write, the display will return to the parameter number without a value change. There is no explicit error code on the BOP20; the silent reject is the error. Diagnose via section 4.

5.6 Alternate write path: Starter / Startdrive

When the BOP20 cannot be made to accept the write, use the engineering tool. The procedure is identical in Starter and TIA Portal with Startdrive:

  1. Open the project, go online with the CU320-2PN.
  2. Navigate to the Control Unit drive object (not the Vector DO).
  3. Open the parameter list and filter on p0005, p0006, p0003.
  4. Set p0003 = 3 first and click "Write" (RAM only).
  5. Click "Copy RAM to ROM" to commit the access-level change non-volatilely.
  6. Set p0005[0] = 21, p0005[1] = 27, p0006 = 0.
  7. Click "Write" and then "Copy RAM to ROM" again.
  8. Cycle the BOP20 (remove and re-seat) to refresh the operator-panel display.
Note on persistence: Writes from Starter that remain in RAM are lost on the next CU320-2PN power-cycle. The "Copy RAM to ROM" action writes the values to the non-volatile memory on the CF card. This step is required for the new p0005 / p0006 values to survive a power-cycle.

6. Commissioning-State Lock Map (p0010)

Reference: SINAMICS G130 / G150 List Manual (LH2), p0010 description.

p0010 Commissioning state Effect on p0005 / p0006
0 Ready / operation All values writable per p0003
1 Quick commissioning Display params writable; p0003 filter may differ
2 Power section definition Topology-related only
3 Drive / motor settings Closed-loop tuning only
4 Encoder commissioning Encoder parameters
5 Technological application / units Application settings
15 Data sets (DDS, CDS, EDS) Data set configuration
17 Safety Integrated Safety parameter set
29 Sensorless control tuning Sensorless commissioning
30 Parameter reset / factory settings All params writable in sequence

After any p0010 != 0 sequence, set p0010 = 0 explicitly and observe r3996 (commissioning status word) return to 0 before editing display parameters.

7. Know-How Protection Recovery (p7766, p7767, p7768)

When KHP is active on the Control Unit drive object, the affected parameters read back as the factory default and reject writes. To disable KHP:

  1. In Starter / Startdrive, go online with the CU320-2PN.
  2. Select the Control Unit drive object.
  3. Right-click -> Know-how protection -> Deactivate...
  4. Enter the OEM password (matches p7766 of the original commissioning).
  5. Click OK. Parameters become visible and writable immediately.
  6. Set p0003 = 3, write p0005 / p0006 per section 5.

If the OEM password is lost, contact Siemens technical support with the drive serial number (r7841) and the Control Unit serial number (on the CU's nameplate) to obtain a factory-level release. A factory reset (p0010 = 30, p0970 = 1) clears KHP but erases all commissioning data and is destructive.

8. Verification Procedure

8.1 BOP20 display check

  1. Issue the ON / OFF1 command. The drive runs.
  2. BOP20 first line should display a number followed by "1/min" - this is r0021 in RPM.
  3. Press FN - display toggles to a value followed by "A" - this is r0027 in amperes.
  4. Press FN again - display returns to r0021.
  5. Remove the run command; display should hold the last speed value (p0006 = 0) or toggle to r0020 (setpoint) per the p0006 setting.

8.2 Cross-check with Starter

  1. In Starter / Startdrive, read r0021 (smoothed) and r0022 (unsmoothed) via the trace or the parameter list.
  2. Compare r0021 with the BOP20 reading. The values should match within the smoothing time constant p0045 (default 5 ms) and the filter selection in p0046.
  3. If Starter shows the correct value but the BOP20 does not, the issue is the BOP20 / p0005 binding, not the drive's speed calculation.

8.3 Persistent save verification

  1. Confirm "Copy RAM to ROM" was performed in Starter.
  2. Power-cycle the CU320-2PN.
  3. After restart, the BOP20 should still display the speed in operation - the saved p0005 / p0006 values were retained.
  4. If the display reverts to r0000, the RAM-to-ROM save did not occur; repeat it from the engineering tool.

9. Field Commissioning Checklist

# Check Pass criteria
1 CU320-2PN firmware version Read r0018 - confirm firmware supports the LH2 / LH3 features used
2 CF card present, non-corrupt CF LED on the CU is green or off (red = error)
3 BOP20 physically connected and seated BOP20 backlight active, characters visible
4 Drive state is OFF, no active faults r0002 = 0, r0947[0] = 0, r2122[0] = 0
5 p0010 = 0, p3900 = 0, p3996 = 0 Drive fully out of commissioning
6 BOP20 key lock cleared Power-cycle BOP20, confirm P and arrow keys respond
7 p0003 = 3 set and saved Read p0003 returns 3 after power-cycle
8 Know-how protection disabled on Control Unit DO p7766 = 0, no password prompt in Starter
9 p0005[0] = 21, p0005[1] = 27, p0006 = 0 written and saved Read-back confirms new values after CU power-cycle
10 BOP20 displays RPM during run r0021 reading visible on BOP20
11 Starter reads same r0021 as BOP20 Values match within 1 RPM
12 Display retained after CU power-cycle BOP20 still shows RPM after restart

10. Related Parameters for Extended BOP20 Display

Beyond the standard p0005 values listed in section 3, the G130 exposes the following connector outputs that are commonly mapped to the BOP20 via BICO for custom displays:

Parameter Function Unit Smoothing (default)
r0020 Speed setpoint RPM p0045 (5 ms)
r0021 Speed actual value, smoothed RPM p0045 (5 ms)
r0022 Speed actual value, unsmoothed RPM -
r0024 Output frequency, smoothed Hz p0045
r0025 Output voltage, smoothed V p0045
r0026 DC link voltage, smoothed V p0045
r0027 Current absolute value, smoothed A p0045
r0031 Torque actual value, smoothed Nm p0045
r0032 Active power, smoothed kW p0045
r0035 Motor temperature °C -
r0036 Power section overload utilization % -
r0037 Power section temperature °C -

The standard p0005 list only exposes a subset of these via direct numeric selection. For OEM-specific displays (e.g., kW, torque, motor temperature), use a free connector via BICO and a user-defined display list, or replace the BOP20 with an AOP30 (Advanced Operator Panel 30) which supports user-defined screens. Reference: SINAMICS BOP20 / AOP30 Operating Instructions.

11. Safety, Lockout, and Working-State Considerations

  • Display parameter changes (p0005, p0006, p0003) are non-safety-relevant. They can be performed in any operating state without disabling safety functions.
  • If Safety Integrated (SI) is active on the drive, KHP on the Safety DO (separate from KHP on the Control Unit DO) does not affect p0005. p0005 lives on the Control Unit DO, not the Safety DO.
  • Setting p0003 = 3 (expert) is a UI/UX feature, not a safety feature. It does not change the safety state, the Safety Integrated bit, or the stop behavior.
  • Editing p0005 / p0006 while the drive is running under load does not affect the load, the motor, or the process. The BOP20 does not have a "control source" that competes with the PLC / terminal command source (p0700) for display edits. The risk is the key-lock being toggled by an unintended long-press on P + FN during the edit.
SAFETY WARNING - High-Power Chassis Drive: A 315 kW Sinamics G130 chassis unit operates at line voltages up to 690 V AC 3-phase with substantial stored energy in the DC link. De-energize the cabinet, follow local lockout / tagout (LOTO) procedure, wait a minimum of 5 minutes after power-off for the DC link to discharge, and verify with a properly rated meter at the DC-link test points before physical access to the drive. Do not remove the BOP20 with the drive in operation. Confirm r0002 = 0 ("Operation disabled") and the DC-link voltage r0070 is below 50 V before any physical access.

12. Frequently Asked Questions

Why does my BOP20 show 0 or just the operating display instead of RPM on a G130 with CU320-2PN?

p0005[0] is at the factory default of 0, which maps the BOP20 to r0000 (operating display / status word). Set p0005[0] = 21 to display r0021 (smoothed actual speed in RPM) and p0006 = 0 or 1 for correct run / ready behavior. The BOP20 will not show RPM until p0005[0] is changed from 0 to a speed-related value.

p0005 and p0006 appear read-only on the BOP20. What unblocks them?

Set p0003 = 3 (expert), ensure the drive is not running (r0002 = 0 or 1), confirm p0010 = 0 and p3900 = 0, disable Know-How Protection (p7766 = 0 with the correct password) if active, and power-cycle the BOP20 to clear the operator-panel key lock. If a write is silently rejected, switch to Starter / Startdrive and write from the engineering tool where the access path is more explicit.

Do p0005 and p0006 settings survive a CU320-2PN power-cycle?

Only if "Copy RAM to ROM" is performed in Starter / Startdrive or the values are explicitly saved to the CF card. RAM-only writes are lost on the next power-cycle. The Save / Load function on the Control Unit drive object writes the parameters to the non-volatile memory and the CF card; without this step, the drive reverts to the factory defaults on restart.

Can I use TIA Portal with Startdrive instead of Starter for the G130 CU320-2PN?

Yes. Startdrive supports the same CU320-2PN G130 configuration. The parameter list, p0005 / p0006 / p0003 access, and online / offline behavior are equivalent. Startdrive is the recommended tool for new G130 deployments integrated into a TIA Portal project; Starter remains the standard for legacy G130 / LH2 firmware and for service on installed bases.

Why does the BOP20 show a different RPM value than Starter online?

p0005[0] = 21 displays r0021 (smoothed actual speed), while Starter may show r0022 (unsmoothed) or r0061 (rotor speed) in the trace. The difference is the smoothing time constant p0045 (default 5 ms) and the filter selection in p0046. To match the BOP20 exactly, configure Starter to monitor r0021 on the same drive object as p0005[0] - the Control Unit drive object, not the Vector drive object.

What is the difference between BOP20 and AOP30 for the G130?

BOP20 is a 2-line x 16-character basic operator panel that supports the p0005 / p0006 display selection only. AOP30 is a backlit 4-line x 24-character advanced operator panel that supports user-defined screens, parameter set selection, fault memory, and language switching. For OEM-specific displays beyond the p0005 list, replace the BOP20 with an AOP30 or connect a higher-level HMI via PROFINET.

Back to blog