Problem Overview
The CP 343-1 (6GK7 343-1EX30-0XE0) used as a PROFINET IO controller on an S7-300 station fails to exchange process data when the configured PROFINET device I/O start address differs from byte 0 of the CPU's process image. Inputs mapped to IB 380 and outputs mapped to QB 95 remain inactive (always 0) or never get set, even though the PNIO_RECV (FC12) and PNIO_SEND (FC11) calls return error-free status. The same configuration works correctly when the start address is set to 0.0.
This is not a fault of the FC blocks themselves. It is a mismatch between the CPU process image input/output size, the PROFINET device slot address in HW Config, and the RECV/SEND pointer in the user program. Each of these three locations must be brought into agreement.
Affected Hardware and Firmware
| Component | Order Number / Designation | Notes |
|---|---|---|
| CP 343-1 | 6GK7 343-1EX30-0XE0 (1EX30) | PN IO controller, supports up to 128 PN IO devices |
| CPU (typical) | 6ES7 315-2EH14-0AB0 (CPU 315-2 PN/DP) | Any S7-300 CPU with PN interface or separate CP |
| STEP 7 | V5.5 + SP2 / HFx or STEP 7 Professional (TIA Portal) V13+ | Function blocks identical across versions |
| FC11 / FC12 | PNIO_SEND / PNIO_RECV | Supplied in the CP 343-1 function block library |
Root Cause Analysis
The CP 343-1 operates a local address space that is logically independent from the CPU's process image. Internally, the CP transfers PROFINET process data starting at offset 0 of its own working buffer, and FC11/FC12 are responsible for copying that buffer between the CP and the CPU memory area selected by the RECV and SEND pointer parameters.
Three parameters must agree for the transfer to succeed:
- Configured slot address of the PN IO device in HW Config (or in the PROFINET IO topology of the TIA Portal).
- Length of the process image input/output area on the CPU (Object > Properties > Cycle/Clock Memory).
- RECV / SEND pointer used in FC12 / FC11 of the user program.
If the PN IO device is configured at I 380.0 with 66 bytes of input data, the CPU's process image must be at least 446 bytes (380 + 66). If it is configured at I 0.0, only 66 bytes are needed. The CP cannot write data to a memory area that is not part of the process image, and the FC blocks will still return BUSY = 0 and DONE = 1 with no error code because the copy operation succeeds in RAM — but the source data on the CP side is never refreshed until the process image is large enough to cover the configured slot.
Symptom Matrix
| Symptom | Probable Cause | Action |
|---|---|---|
| Inputs always 0 starting at configured address, FC12 returns DONE=1 | Process image too small, CP cannot refresh slot | Increase CPU process image size |
| Outputs never set on PN IO device, FC11 returns DONE=1 | Process image too small or RECV/SEND pointer misaligned | Align pointers and resize process image |
| Inputs correct at IB 0..65 but start of buffer is wrong | RECV pointer address differs from HW Config slot | Set RECV pointer to the same address configured in HW Config |
| FC returns STATUS W#16#80A1 or W#16#80A2 | CPLADDR mismatch or DP/PN interface error | Verify CPLADDR (typical 16#18E for the integrated PNIO interface) |
| CP reports "IO device not reachable" in diagnostic buffer | Device name or PROFINET cable fault, not address issue | Check PROFINET device name assignment and topology |
Prerequisites
- STEP 7 V5.5 or TIA Portal V13+ installed with the CP 343-1 (1EX30) GSD file or HSP.
- CPU 315-2 PN/DP or comparable S7-300 with PROFINET capability.
- PN IO device GSD file imported (e.g. ET 200SP, ET 200MP, ET 200AL).
- PNIO_SEND (FC11) and PNIO_RECV (FC12) function blocks from the CP 343-1 library installed in the S7 program.
- Online connection to the CPU for download and diagnostics.
Step-by-Step Resolution
Step 1 — Confirm the PN IO Device Slot Address
- Open the SIMATIC S7 project in STEP 7.
- Open HW Config and double-click the PN IO device assigned to the CP 343-1.
- Note the configured Input start address and Output start address (e.g.
IB 380/QB 95). - Note the configured Input length and Output length (e.g. 66 input bytes, 32 output bytes).
Step 2 — Resize the CPU Process Image
- In HW Config, double-click the CPU (e.g. CPU 315-2 PN/DP).
- Open the Cycle / Clock Memory tab.
- In the Process image section set:
| Direction | Recommended Value | Reason |
|---|---|---|
| Size of process image input area | ≥ (highest input byte + length of PN IO slot) | Ensures CPU copies PN data into I area |
| Size of process image output area | ≥ (highest output byte + length of PN IO slot) | Ensures CPU reads back PN output data |
For the example values IB 380 / 66 bytes and QB 95 / 32 bytes set the process image to at least 446 input bytes and 127 output bytes. A practical round value is 512 / 512 bytes.
Step 3 — Align the FC11 / FC12 Pointers
Open the instance DB or shared DB that contains the FC11 / FC12 calls. The two critical parameters are RECV for FC12 and SEND for FC11.
For the example above the call must read exactly:
PNIO_RECV(
CPLADDR := W#16#18E, // or actual diagnostic address of the CP
MODE := B#16#0,
LEN := 66, // must equal HW Config input length
RECV := P#I380.0 BYTE 66 // must point to the same start address configured in HW Config
);
For the outputs:
PNIO_SEND(
CPLADDR := W#16#18E,
MODE := B#16#0,
LEN := 32, // must equal HW Config output length
SEND := P#Q95.0 BYTE 32 // must point to the same start address configured in HW Config
);
The RECV / SEND pointer must match the slot address byte for byte. Setting RECV := P#I0.0 BYTE 66 while HW Config has the slot at IB 380 means the CP copies data into the wrong memory area and the application sees stale data.
Step 3a — Resolving the Address Conflict with Existing Modules
If the CPU process image is already populated up to IB 380 by other local or PROFIBUS modules, the PN IO slot must be placed either:
-
Above the highest existing byte plus its length (e.g.
IB 380requires the previous module to end at or belowIB 379). - In an unused gap between modules if the process image is large enough.
Use HW Config > PLC > Edit Ethernet Node or PROFINET IO Topology to renumber slots. STEP 7 automatically rejects overlapping addresses and warns the engineer at compile time.
Step 4 — Download and Reset
- Save and compile the HW Config and the S7 program.
- Download the HW Config first, then the S7 program to the CPU.
- Perform a complete restart (STOP → MRES → RUN) so the CP re-initialises the PROFINET IO subsystem with the new process image.
Verification
| Check | Procedure | Expected Result |
|---|---|---|
| Process image table (PIP) | Online > Monitor/Modify > PI | Inputs from PN IO device update in real time |
| FC11 / FC12 status | Monitor RETVAL and STATUS of the call | DONE = 1, ERROR = 0, STATUS = W#16#0000 |
| PN IO diagnostic buffer | CPU > Diagnostic Buffer / PN IO Diagnostics | No "station failure", no "process image mismatch" events |
| Web server (if enabled) | CP 343-1 > Information > PROFINET Diagnostics | Device in "data exchange" state |
| Force test on output | Monitor & Modify the SEND area and observe PN IO device output | Physical output follows forced value within one PROFINET update cycle (default 1 ms) |
Common Pitfalls
Pitfall 1 — Using the Wrong FC Number
The CP 343-1 (1EX30) uses FC11 (PNIO_SEND) and FC12 (PNIO_RECV). Older CP 342-5 documentation that uses FC1/FC2 (DP_SEND/DP_RECV) is not directly applicable to PROFINET, although the principle of process image size and pointer alignment is identical. Refer to the function block help inside STEP 7 for the correct block number.
Pitfall 2 — Leaving MODE ≠ 0
For cyclic PROFINET IO data exchange the MODE parameter must be B#16#0. A non-zero MODE triggers a one-time read/write service and will appear to "work" once but then stop updating.
Pitfall 3 — Ignoring the Update Time
Even with the process image correctly sized, the PN IO device must be configured with a sensible send clock (typically 1 ms). A send clock of 0 or an unsupported value causes the CP to keep the slot in "not exchanged" state without raising an error code.
Pitfall 4 — TIA Portal vs Classic STEP 7 Conversion
When migrating an S7 project from STEP 7 V5.5 to TIA Portal, the CP 343-1 (1EX30) GSD file is loaded through the device library. The function block instances FC11/FC12 remain identical, but the underlying data type of CPLADDR may be displayed as HW_IO. Always verify the value (typically 16#18E or 16#18F) against the diagnostic address visible in the device properties.
Extended Diagnostic Procedure
If the slots still do not update after following the steps above:
- Open Online & Diagnostics on the CP 343-1 and read the diagnostic buffer.
- Select PROFINET Diagnostics > Station and confirm each PN IO device shows "OK".
- Use Trace on the FC11 / FC12 calls to record RETVAL and STATUS over several seconds. Look for transient W#16#80C3 (timeout) which indicates the update time is too short for the device.
- Temporarily reduce the PN IO device update time to 4 ms and observe whether data flow resumes; if so the original value of 1 ms was unsupported by the device firmware.
- As a last resort, remove the PN IO device from HW Config, recompile, download, perform a complete restart, then re-add the device. This forces the CP to rebuild the AR (Application Relationship) from scratch.
Why I0.0 Always Works
The default process image size of any S7-300 CPU is 128 bytes for inputs and 128 bytes for outputs. Setting a PN IO slot at IB 0 therefore always fits inside the default image regardless of CPU type, and the FC12 copy succeeds in RAM even when the CP has not yet refreshed the buffer. With non-zero start addresses, the slot may fall outside the default image; the CP cannot refresh the data because the CPU never scans it during OB1 cycle update.
This is why the symptom appears only when the slot address is moved away from byte 0 and not because the FC blocks impose an internal address restriction. The CP itself has no such limitation — it can address the full OB1 process image up to the CPU maximum.
Field-Commissioning Checklist
| Item | Action | Sign-off |
|---|---|---|
| CPU process image input bytes set | Verify in CPU properties | [ ] |
| CPU process image output bytes set | Verify in CPU properties | [ ] |
| PN IO slot addresses in HW Config | Note start address and length | [ ] |
| FC11 SEND pointer | Matches HW Config output start address | [ ] |
| FC12 RECV pointer | Matches HW Config input start address | [ ] |
| FC11/FC12 LEN parameter | Matches HW Config configured length | [ ] |
| FC11/FC12 MODE parameter | Set to B#16#0 | [ ] |
| CPLADDR parameter | Matches CP diagnostic address | [ ] |
| Send clock | 1 ms (or device-supported value) | [ ] |
| Complete restart after download | STOP → MRES → RUN | [ ] |
| PN IO device online diagnostic | Shows "data exchange" | [ ] |
| Force/observe test on one input and one output | Physical I/O follows within 1 cycle | [ ] |
Can FC11 and FC12 of the CP 343-1 (1EX30) only operate at I0.0 / Q0.0?
No. The function blocks support any start address inside the CPU process image. The default 128-byte process image of every S7-300 CPU fits I0.0 by default; non-zero start addresses require the CPU process image to be resized in HW Config > CPU > Cycle/Clock Memory so the slot is fully covered.
How many process image bytes are needed for a PN IO slot at IB 380 with 66 input bytes?
At least 446 input bytes (380 + 66). Round up to a power of two (512) for practical use, and verify the CPU supports that size — CPU 315-2 PN/DP supports up to 2048 bytes per direction.
What is the correct CPLADDR value for the CP 343-1 (1EX30)?
The CPLADDR is the diagnostic address of the PROFINET interface. It is visible in HW Config under the CP properties. For the integrated PROFINET interface of a CPU 315-2 PN/DP it is typically W#16#18E; for an external CP 343-1 it may be W#16#18E or W#16#18F depending on slot. Always confirm via the device properties.
Do FC11 and FC12 still work when MODE is set to a value other than 0?
Only for one-shot services. For continuous cyclic PROFINET IO exchange the MODE parameter of both FC11 (PNIO_SEND) and FC12 (PNIO_RECV) must be B#16#0, otherwise the buffer is only transferred on the rising edge of REQ.
Does the PN IO device send clock affect FC11 / FC12 data flow?
Yes. The send clock defines how often the CP refreshes the PROFINET IO buffer. A send clock that the device firmware cannot honour (for example 0.25 ms on a 1 ms device) keeps the slot in "not exchanged" state and the FC blocks return DONE=1 with stale data. Typical values are 1 ms or 4 ms.