Overview
Driving a SINAMICS G120C from a SIMATIC S7-1500 (or S7-1500T) is a common configuration for conveyors, mixers, pumps, and basic winder applications. The drive receives closed-loop speed control commands over PROFINET using PROFIdrive telegrams (typically Telegram 1 for speed control, or Telegram 3 with supplementary torque). The PLC side uses a Technology Object (TO) that either bypasses the PLC's own speed controller and writes setpoints directly to the drive (TO_SpeedAxis), or runs a full position control loop locally (TO_PositioningAxis / TO_SynchronousAxis).
One of the most frequent engineering questions in this architecture is: How do I make the ramp up and ramp down time a variable that the PLC program can change at runtime? The answer depends on which technology object you selected, which CPU you are using, and which TIA Portal version is installed. This reference walks through the supported methods, the math, and the commissioning checks needed to make dynamic ramps reliable on a G120C with S7-1500.
Prerequisites
Before configuring dynamic ramps, verify that the following conditions are met:
- PLC hardware: SIMATIC S7-1500 CPU (any S7-151x, S7-152x, S7-1505S) or ET 200SP CPU (S7-151xSP). Firmware version 2.5 or higher is recommended for full motion control feature coverage; V2.9 adds MC_ChangeDynamic to selected S7-1500 CPUs (see notes below).
- Drive hardware: SINAMICS G120C with PROFINET interface (article numbers 6SL3210-1KE1x-xUFx for the PN variants). Firmware V4.7 or higher is recommended for clean PROFIdrive compliance.
- Engineering software: TIA Portal V15.1, V16, V17, or V18 with the SINAMICS Startdrive option installed.
- Communication: PROFINET IRT or RT configured between the PLC and the G120C. Standard Telegram 1 (speed setpoint, 16-bit status / 16-bit control) is the minimum for closed-loop speed control. Telegram 3 adds a 32-bit speed setpoint and 16-bit torque reduction, often used with TOs.
- Configuration: The G120C is configured in the project as a PROFINET IO device with a PROFIsafe slot only if safety is required. Set the ramp-function source to "Ramp-Function Generator inside the PLC" in the drive's commissioning wizard, or alternatively leave the ramp generator inside the drive and use the drive's own parameters P1120 (ramp-up) and P1121 (ramp-down). Both approaches are valid; the choice determines where the jerk-limited profile is computed.
Architecture: TO_SpeedAxis vs. TO_PositioningAxis
The choice of technology object is the most important decision in the dynamic ramp discussion because it changes the location of the speed controller and the way ramps are produced.
| Aspect | TO_SpeedAxis | TO_PositioningAxis / TO_SynchronousAxis |
|---|---|---|
| Position controller in PLC | No | Yes (IPO and position controllers run on the CPU) |
| Speed controller | Inside the G120C (closed loop on the drive) | Inside the G120C (closed loop on the drive); PLC supplies a position-derived speed setpoint |
| Ramp generation | Setpoint is written directly to the drive's speed setpoint input; ramps come from the drive's internal ramp-function generator (RFG), or are approximated by the TO based on the configured acceleration/deceleration if the drive's RFG is bypassed | PLC generates the complete motion profile (velocity, acceleration, deceleration, jerk) and the resulting speed setpoint is sent to the drive |
| Dynamic parameters in TO configuration | Velocity (rpm), Acceleration, Deceleration, Jerk. These are sent to the drive as PROFIdrive setpoints when the corresponding "Ramp-Function Generator inside the PLC" mode is selected | Same set, but enforced by the position-control loop on the PLC side |
| Resource usage on CPU | Low (no position controller) | Higher (additional motion control resources for the position controller) |
| Typical use case | Pumps, fans, simple conveyors where only speed setpoint control is required | Positioning axes, synchronized axes, camming, complex motion profiles |
Because TO_SpeedAxis does not run a position controller, many of the high-level dynamic-change functions behave differently than with TO_PositioningAxis. The Motion Control function manual is explicit on this point: TO_SpeedAxis inherits the drive's own closed-loop speed control, and the PLC-side motion control merely commands the setpoint trajectory.
Why MC_ChangeDynamic Is Not the Default on S7-1500
The function block MC_ChangeDynamic is the most ergonomic way to update ramp parameters at runtime. It is documented in the SIMATIC S7-1200 Motion Control manual and is fully supported on S7-1200 CPUs. On S7-1500, the equivalent function became available in selected CPU firmware revisions and TIA Portal versions, but it is not the standard recommended path for setting dynamic values on a moving command.
On S7-1500 (and S7-1500T), Siemens documents a different, more flexible approach: every motion control command that initiates motion (such as MC_MoveAbsolute, MC_MoveRelative, MC_MoveVelocity, MC_MoveJog, MC_Halt, MC_Stop) exposes four connectors that take effect for that single call:
-
Velocity(LREAL) — target velocity in the unit configured in the TO (typically rpm for rotational drives, mm/s for linear) -
Acceleration(LREAL) — acceleration in (unit)/s² -
Deceleration(LREAL) — deceleration in (unit)/s² -
Jerk(LREAL) — jerk in (unit)/s³
Each connector accepts either a positive value or the special value -1.0. Writing -1.0 tells the TO to use the default value from the axis configuration for that call. This allows a program to issue identical motion commands while passing dynamic values from a process data block (DB) — exactly the "dynamic ramp up/down value" the original question asked about.
Configuring the Technology Object for Variable Ramps
To make ramp times variable, configure the TO with sensible default dynamic values, then override those values on the call to the motion block. Follow this procedure in TIA Portal:
- Open the technology object in the project tree (e.g.,
TO_SpeedAxis_1). - Navigate to Configuration > Extended Parameters > Dynamic defaults (the exact path depends on the TIA Portal version, but it is the page where Velocity, Acceleration, Deceleration, and Jerk are listed as default values).
- Enter the maximum safe velocity and acceleration values. The defaults act as ceilings when an
-1.0is passed. - Compile the project. The compiled TO data block exposes a member such as
TO_SpeedAxis_1.DynamicDefaults.Velocity,...Acceleration,...Deceleration,...Jerk. These members are read-only at runtime and reflect what the TO was commissioned with. - In your user program, allocate a global DB (e.g.,
DB_MotionParams) and create LREAL tags for runtime ramps:RampUpTime_s,RampDownTime_s,TargetVelocity_rpm,Acceleration,Deceleration,Jerk.
Conversion Math: Ramp Time to Acceleration
The PLC expects an acceleration value in the engineering unit unit/s². Operators and most application programs are more comfortable thinking in ramp times (the time it takes to go from zero to target velocity). Convert the two as follows:
| Quantity | Formula | Units |
|---|---|---|
| Acceleration (ramp up) | a = v / t_up |
rpm/s |
| Deceleration (ramp down) | d = v / t_down |
rpm/s |
| Jerk (optional) |
j = a / t_jerk (or simply 0 for trapezoidal profiles) |
rpm/s² |
For example, to reach 1500 rpm in 5.0 s and decelerate from 1500 rpm in 7.5 s, the values passed to the motion block are:
a = 1500 rpm / 5.0 s = 300 rpm/sd = 1500 rpm / 7.5 s = 200 rpm/sv = 1500.0 (rpm)j = 0.0 (or leave as default; -1.0 uses the configured default jerk)
If the user engineering unit is mm/s for a linear axis, the same math holds, with mm/s and mm/s² in place of rpm and rpm/s.
Deceleration is invalid and the TO will reject the command.
Implementation: Structured Text Example
The following SCL snippet shows a typical pattern. It reads ramp time values from a global DB, converts them to the acceleration / deceleration form, and uses them on an MC_MoveVelocity call. The same pattern works for MC_MoveJog, MC_MoveRelative, and MC_Halt.
// Global DB "DB_MotionParams"
VAR
TargetVelocity_rpm : LREAL := 1500.0; // desired speed
RampUpTime_s : LREAL := 5.0; // ramp-up time
RampDownTime_s : LREAL := 7.5; // ramp-down time
UseDynamicOverride : BOOL := TRUE; // TRUE = use DB values, FALSE = TO defaults
END_VAR
// Local computation in the motion FC
VAR
dynAccel : LREAL;
dynDecel : LREAL;
dynJerk : LREAL := 0.0;
END_VAR
IF UseDynamicOverride AND RampUpTime_s > 0.0 AND RampDownTime_s > 0.0 THEN
dynAccel := TargetVelocity_rpm / RampUpTime_s;
dynDecel := TargetVelocity_rpm / RampDownTime_s;
dynJerk := 0.0;
ELSE
dynAccel := -1.0; // use TO default
dynDecel := -1.0; // use TO default
dynJerk := -1.0; // use TO default
END_IF;
// Issue the motion command
MC_MoveVelocity_1(
Axis := TO_SpeedAxis_1,
Execute := StartMove,
Velocity := TargetVelocity_rpm, // rpm
Acceleration := dynAccel, // rpm/s
Deceleration := dynDecel, // rpm/s
Jerk := dynJerk, // rpm/s^3
Direction := mcPOSITIVE_DIR,
Busy => ,
CommandAborted=> ,
Error => ,
ErrorID =>
);
The MC_MoveJog block in TIA Portal V16 exposes the same Velocity, Acceleration, Deceleration, and Jerk inputs and supports the -1.0 = "use default" convention. This means the same DB-driven mechanism also covers manual jogging modes.
Where Ramp Generation Actually Happens
When the G120C is configured with Ramp-Function Generator inside the PLC (the path most users want when they ask for "dynamic ramps"), the G120C accepts the PLC's PROFIdrive setpoint directly without applying its own ramp limiter. The PLC's TO, using the Acceleration and Jerk inputs, computes the time-discrete speed trajectory and writes it to the drive each bus cycle (typically 1 ms or 4 ms depending on PROFINET configuration). In that case the drive's P1120 and P1121 ramp-time parameters are inactive.
Alternatively, when the drive's internal RFG is used (default for many commissioning wizards), the PLC writes a target velocity and the drive's P1120 (ramp-up) and P1121 (ramp-down) parameters control the slope. To change ramps dynamically in that mode you have three choices:
- Use the SINAMICS parameter access via the function block
WR_REC/RD_REC(non-cyclic parameter read/write over PROFINET) to writeP1120andP1121at runtime. This is a low-frequency change (a few times per second maximum) and adds acyclic bus load. - Use the supplementary PROFIdrive setpoints in Telegram 7 or 9 (if configured) to override ramp parameters cyclically.
- Switch the configuration to PLC-side ramp generation as described above. This is the recommended path for variable ramps.
Jerk value produces an S-curve profile that reduces mechanical stress. The S7-1500 motion control interpolates the velocity trajectory inside its IPO cycle, so set Jerk only if the axis mechanics and the cycle time can support it. For drives with low encoder resolution, leaving jerk at zero (trapezoidal profile) often gives better low-speed behavior.
Verification and Commissioning
Validate dynamic ramp behavior with the following checks before the line is released to production:
-
Watch table test: In TIA Portal, open the TO's online diagnostics and trigger
MC_MoveVelocityfrom a watch table with three different combinations ofAccelerationandDeceleration. Plot the actual speed trace via the trace function and confirm the slope matches the calculated value within ±5%. -
HMI ramp parameter screen: Add an HMI faceplate that exposes
RampUpTime_s,RampDownTime_s, and the calculatedAcceleration/Decelerationvalues. Operators should never see the rawdynAccelvalue without the conversion factor displayed nearby. -
Edge cases:
- Target velocity = 0 — the axis should not move;
AccelerationandDecelerationbecome irrelevant but must not generate a TO error. - Ramp time = 0 — division by zero. The application must clamp to a minimum ramp time (e.g., 0.05 s) before computing acceleration.
- Reversal — the deceleration of the outgoing motion is reused as the acceleration of the incoming motion when both are passed on the same command. Test reversal at the configured maximum velocity.
- Target velocity = 0 — the axis should not move;
- Drive-side trace: Startdrive can record the drive's actual speed, the PROFIdrive setpoint, and the torque. Trigger a record during a controlled ramp to confirm the drive sees a smooth setpoint slope and does not enter a current-limit condition.
Troubleshooting Matrix
| Symptom | Likely cause | Corrective action |
|---|---|---|
Axis ignores Acceleration and Deceleration values; ramp appears to be a fixed slope |
Drive's internal RFG is still active (default in the commissioning wizard) | In the G120C commissioning wizard, switch "Ramp-Function Generator" to inside the PLC. Re-compile and download. |
| Axis stops abruptly or returns "Invalid value at parameter Acceleration" | Negative or zero Acceleration passed by the application |
Clamp the input to > 0.0. Replace the -1.0 "use default" sentinel only at the motion-block input, never at the application level. |
| Axis accelerates and decelerates correctly in jog, but HMI-entered ramp times are ignored | HMI tags point to the wrong DB or the PLC-side conversion is bypassed | Verify the HMI connection points to DB_MotionParams.RampUpTime_s and that the motion FC reads from that DB on every call, not at startup only. |
| Speed oscillates around the target | Jerk is too high for the mechanical system, or the cycle time is too coarse for the configured acceleration | Lower Jerk by a factor of 10; reduce the IPO cycle time; or move the ramp generator into the drive and rely on the drive's tuned ramp response. |
| CPU reports "Axis: not enough resources" | TO_PositioningAxis was selected; the position controller consumes more motion control resources than TO_SpeedAxis | Switch to TO_SpeedAxis if no position control is required, or upgrade to an S7-1515 / S7-1516 CPU for additional motion control resources. |
| MC_ChangeDynamic is not visible in the instructions catalog | CPU firmware is older than V2.9 or the TIA Portal version is older than V16 | Update the CPU firmware to V2.9 (or later) and the project to TIA Portal V16 or later, or use the connector-based approach described above. |
Best Practices for Field-Ready Dynamic Ramps
- Validate inputs at the HMI boundary. Reject negative or zero ramp times at the HMI; never trust a panel operator to enter 0.
-
Use a single source of truth for the active ramp time. A dedicated DB (e.g.,
DB_MotionParams) referenced by all motion blocks prevents drift between axes. -
Decouple the application from the engineering unit. Pass ramp times in seconds; let the FC convert to
unit/s²right before the motion call. - Keep jerk at zero unless the mechanics require it. Trapezoidal profiles are easier to commission and cause fewer surprises at low speeds.
-
Document the unit on every HMI tag. "Ramp-up (s)" displayed on the panel prevents operators from typing the value in
unit/s²by mistake. -
Make the default value path explicit. Use
-1.0only where the motion block expects it. If the FC substitutes defaults, write a clear comment so the next maintainer does not "fix" the constant.
FAQ
Can I change ramp times on a running TO_SpeedAxis at runtime?
Yes. Pass the new acceleration and deceleration values on the next call to a motion block such as MC_MoveVelocity or MC_Halt. The TO applies the new values to the next ramp, not retroactively to the ramp that is already in progress. There is no need to stop the axis first.
Why does my TO_SpeedAxis appear to ignore Acceleration and Deceleration inputs?
The most common reason is that the G120C's internal ramp-function generator is still active. In the drive commissioning wizard, select "Ramp-Function Generator inside the PLC" and re-download the project. The drive's P1120/P1121 then become inactive, and the PLC-side dynamic values take full control.
Is MC_ChangeDynamic available on S7-1500?
MC_ChangeDynamic was introduced on S7-1200 and has been progressively added to S7-1500 CPUs from firmware V2.9 with TIA Portal V16 and later. For broadest compatibility, the connector-based approach (passing Velocity, Acceleration, Deceleration, Jerk directly to the motion block) is the recommended path and works on every S7-1500 motion-capable CPU.
What is the relationship between ramp-up time in seconds and Acceleration in rpm/s?
Acceleration equals target velocity divided by ramp-up time: a = v / t_up. For example, 1500 rpm reached in 5 seconds yields 300 rpm/s. The same formula with the appropriate units applies to linear axes (mm/s and mm/s²).
Do I need a TO_PositioningAxis to use variable ramp times?
No. A TO_SpeedAxis accepts variable acceleration, deceleration, velocity, and jerk on every motion command through its connectors. The TO_PositioningAxis is only required if you need closed-loop position control, synchronization, or camming on the PLC side.