Overview
Siemens SIMATIC controllers are PROFINET-native platforms. EtherNet/IP, defined by ODVA and built on the Common Industrial Protocol (CIP), is the dominant fieldbus in North American and increasingly global machine-builder installations. Engineering a cell that combines a Siemens PLC (S7-300, S7-400, S7-1200, or S7-1500) with non-Siemens EtherNet/IP servo drives and remote I/O requires a deliberate bridging strategy because no SIMATIC CPU ships with an integrated EtherNet/IP scanner (master) port.
This reference covers the three practical integration patterns: PROFINET-to-EtherNet/IP gateway bridging, dedicated EtherNet/IP scanner modules mounted directly in the drive cabinet, and OPC UA-mediated data exchange. The dominant pattern in the field remains a third-party protocol gateway that converts PROFINET IO cyclic data on the Siemens side into CIP connection messages on the EtherNet/IP side.
The reference architecture addressed here is documented in Siemens Application Note Entry ID 32989862 – "How do you connect an S7-300/400 to an EtherNet/IP network?" and is the canonical answer for any control engineer evaluating the same question for non-Siemens drives such as Control Techniques (Nidec), Allen-Bradley Kinetix, Yaskawa Sigma-7, Omron 1S, and Danfoss VLT drives.
EtherNet/IP Support Across the SIMATIC CPU Range
Understanding the boundary between native and bridged EtherNet/IP support prevents wasted commissioning time. The matrix below is current as of STEP 7 V5.7 / TIA Portal V18 firmware families.
| CPU family | PROFINET controller | PROFINET device | EtherNet/IP scanner | EtherNet/IP adapter | Recommended path |
|---|---|---|---|---|---|
| S7-300 (Firmware ≤ V3.x) | Yes (CP 343-1) | Yes | No | No | PROFINET ↔ gateway ↔ EtherNet/IP |
| S7-400 (Firmware ≤ V6.x) | Yes (CP 443-1) | Yes | No | No | PROFINET ↔ gateway ↔ EtherNet/IP |
| S7-1200 (FW 4.4+) | Yes (integrated) | Yes | No | No | PROFINET ↔ gateway ↔ EtherNet/IP |
| S7-1500 (FW 2.0+) | Yes (integrated) | Yes | No native scanner; CIP-capable via CP 1545-1 in limited roles | No native adapter | PROFINET ↔ gateway ↔ EtherNet/IP, or OPC UA bridge |
| ET 200SP CPU | Yes | Yes | No | No | PROFINET ↔ gateway ↔ EtherNet/IP |
Conclusion: every SIMATIC PLC in current production requires an external conversion element to act as an EtherNet/IP scanner. Selecting the right gateway is therefore the single most important decision in the project.
Gateway Architecture Patterns
Pattern A – PROFINET Controller with PROFINET/EtherNet/IP Gateway
This is the most common topology. The SIMATIC CPU owns the PROFINET network as IO Controller. The gateway is a PROFINET IO Device on the Siemens side and an EtherNet/IP Scanner on the field side. Cyclic PROFINET slots are mapped 1:1 to CIP assemblies on the EtherNet/IP side.
┌──────────┐ PROFINET ┌────────────┐ EtherNet/IP ┌──────────────┐
│ S7 CPU │ ─────────► │ Gateway │ ────────────► │ Servo drives │
│ (IO Ctrl)│ │ (IO Device │ │ POINT I/O │
│ │ │ + EIP │ │ Turck I/O │
│ │ │ Scanner) │ │ │
└──────────┘ └────────────┘ └──────────────┘
Suitable gateways include the HMS Anybus X-gateway (EtherNet/IP Scanner / PROFINET device), the Phoenix Contact FL GW EIP PN (catalog reference 1043192 family), the Helmholz CIFX 90E variants, and the Wago 750-366 (EtherNet/IP Scanner, with PROFINET on the field-side coupler as a master for downstream PROFINET devices). Choose based on the number of CIP connections, the maximum cyclic I/O size, and the certification footprint required by the end customer.
Pattern B – EtherNet/IP-First Cabinet with PROFINET Gateway
When the cabinet is built around an EtherNet/IP scanner (e.g., a Control Techniques Unidrive M701 in master mode, an Allen-Bradley CompactLogix L30ER, or a Yaskawa MP3300iec) and a Siemens PLC is added for a higher-level supervisory role, the gateway runs in the opposite direction: EtherNet/IP Scanner on the drive side, PROFINET controller on the Siemens side. This is rarer because it defeats the purpose of having a Siemens controller in the cell, but it is used in retrofit projects where a legacy EtherNet/IP cell is extended.
Pattern C – OPC UA Bridge
S7-1500 controllers with firmware 2.5 or higher expose an OPC UA server. A third-party OPC UA-to-EtherNet/IP bridge (e.g., Kepware, Softing, Inductive Automation Ignition Edge with CIP driver) subscribes to the OPC UA tags and pushes them to EtherNet/IP devices. Latency in this path is generally 100–500 ms and is not suitable for tight servo loops; reserve Pattern C for HMI, mode control, and slow supervisory data.
Required Hardware
| Component | Function | Notes |
|---|---|---|
| SIMATIC S7-300 with CP 343-1 | PROFINET IO Controller | CP 343-1 EX30 or later for GSDML-based configuration |
| SIMATIC S7-1500 (any CPU) | PROFINET IO Controller | Integrated PROFINET interface on most CPUs |
| PROFINET/EtherNet/IP gateway | Bridges the two protocols | Select based on CIP connection count and I/O size |
| Managed Ethernet switch (PROFINET side) | PROFINET real-time line | Must support priority tagged frames (DCP, LLDP); unmanaged switches typically work but limit diagnostics |
| EtherNet/IP managed switch | EtherNet/IP line | DLR ring support recommended for drives; DLR requires 1734-EP24D or similar ring supervisor |
| Control Techniques drive with SM-EtherNet/IP option | EtherNet/IP adapter | Used on Unidrive M600/M700/M701; Digitax HD integrates EtherNet/IP onboard |
| Non-Siemens remote I/O (e.g., POINT I/O 1734-AENTR) | EtherNet/IP adapter | Select I/O blocks based on required signal mix |
Step-by-Step Configuration – S7-300 with HMS Anybus X-gateway
Prerequisites
- STEP 7 V5.5 SP4 or higher (or TIA Portal V13 SP1+ with S7-300 migration)
- HMS IPconfig utility (free download from HMS Networks)
- Anybus X-gateway configuration tool (Anybus Configuration Manager, ACM)
- EDS file for the EtherNet/IP adapter (e.g., Control Techniques SM-EtherNet/IP EDS, or AOI/EDS from Rockwell POINT I/O)
- Siemens GSDML file for the HMS Anybus X-gateway (PROFINET device side)
- Industrial Ethernet cable set, M12 D-coded for EtherNet/IP, RJ45 for PROFINET
Step 1 – Install the GSDML on the Siemens side
- Open STEP 7 / TIA Portal and select the S7 station.
- Open HW Config (STEP 7) or Device View (TIA Portal).
- Choose Options > Manage General Station Description Files (GSD) and install the HMS Anybus X-gateway PROFINET GSDML.
- Drag the gateway from the hardware catalog to the PROFINET line. The gateway appears as a PROFINET IO Device.
- Assign a unique PROFINET device name (e.g.,
gw-eip-01) and an IP address on the PROFINET subnet (e.g.,192.168.0.50).
Step 2 – Configure cyclic PROFINET slots
Insert PROFINET slots in HW Config to match the cyclic I/O that the gateway will expose. For typical servo applications, allocate 16 bytes input / 16 bytes output per drive plus 8 bytes for the gateway's diagnostic interface.
Slot 0: 2 bytes input – gateway status
Slot 0: 2 bytes output – gateway control
Slot 1: 16 bytes in – Drive 1 status + actual position
Slot 1: 16 bytes out – Drive 1 control word + speed ref
Slot 2: 16 bytes in – Drive 2 status + actual position
Slot 2: 16 bytes out – Drive 2 control word + speed ref
...
Step 3 – Configure the gateway EtherNet/IP scanner side
- Connect a Windows PC to the configuration port of the Anybus gateway and launch the Anybus Configuration Manager.
- Set the gateway's EtherNet/IP IP address (e.g.,
192.168.1.50) – a different subnet from the PROFINET side is recommended. - Import the EDS file for each EtherNet/IP adapter: Tools > Import EDS.
- Add each drive / I/O block to the scan list. For Control Techniques drives, the EDS exposes assemblies 100 (basic speed) and 101 (extended speed). POINT I/O uses assemblies 1 and 2 for default digital I/O mapping.
- Map each EtherNet/IP assembly instance to the corresponding PROFINET slot configured in Step 2. Pay attention to byte order; Anybus gateways typically default to little-endian, while Siemens expects little-endian on PROFINET, so most data lines up without swapping, but 32-bit status words with sign bits may need explicit byte-swap on the Siemens side.
- Set the Requested Packet Interval (RPI) for each CIP connection. Start with 5 ms for drives and 10–20 ms for digital I/O. The PROFINET update time should be set to match or be slightly faster than the longest RPI to avoid data-age buffer overflows.
Step 4 – Compile, download, and verify
- Compile the STEP 7 / TIA configuration and download to the S7 CPU.
- Download the gateway configuration via ACM.
- Power-cycle the EtherNet/IP devices in the order: gateway → switches → drives → I/O blocks.
- Observe the gateway LEDs: SF (System Fault) off, BF (Bus Fault) off, and the LINK LED steady on for each connected device.
- Open the Anybus web server (default
http://192.168.1.50) and confirm that all CIP connections report Established with the configured RPI.
Control Techniques Drive Integration Detail
Control Techniques drives (now under Nidec) are the canonical example of non-Siemens EtherNet/IP devices integrated with SIMATIC. The relevant product families are:
- Unidrive M600 / M700 / M701: use the SM-EtherNet/IP option module plugged into one of the three option slots. EDS file and AOI libraries are available from the Nidec / Control Techniques support site.
- Digitax HD M751 / M753: have an integrated EtherNet/IP port. Two ports, DLR-capable, support up to 8 CIP connections natively.
- Commander C200 / C300: lower-power drives, optional EtherNet/IP via SK-EtherNet/IP option.
Recommended assembly mapping for an M700 with SM-EtherNet/IP
| Direction | Assembly instance | Length | Contents |
|---|---|---|---|
| Output (PLC → drive) | 100 (Basic speed) | 8 bytes | Control word (2B) + Speed reference (4B) + Pad (2B) |
| Input (drive → PLC) | 101 (Basic speed feedback) | 8 bytes | Status word (2B) + Actual speed (4B) + Pad (2B) |
| Output (PLC → drive) | 120 (Extended speed) | 16 bytes | Control word + Reference + Torque limit + Ramp + Pad |
| Input (drive → PLC) | 121 (Extended speed feedback) | 16 bytes | Status + Actual speed + Actual torque + Output current + Pad |
Choose assembly 100/101 for simple velocity-controlled applications (fan, pump, conveyor, basic traverse). Choose 120/121 when torque limit, ramp rate, or actual torque must be written/read every cycle.
Control word decoding (assembly 100, byte 0–1)
| Bit | Name | Function |
|---|---|---|
| 0 | Enable | 1 = drive enabled, 0 = drive disabled (ramp stop if bit 1 active) |
| 1 | Run forward | 1 = run in positive direction |
| 2 | Jog | 1 = jog reference applied |
| 3 | Run reverse | 1 = run in negative direction |
| 4 | Reverse speed reference | 1 = invert speed reference sign |
| 5–6 | Preset select | 0/1/2/3 = preset 1/2/3/4 |
| 7 | Fault reset | Rising edge clears drive faults |
| 8 | Quick stop | 1 = enable quick stop ramp |
| 9–15 | Reserved | 0 |
Remote I/O Integration Detail
Remote I/O over EtherNet/IP is a more straightforward exchange than drives because most I/O blocks are pure adapters with fixed assembly mappings. Common choices in industrial systems:
- Allen-Bradley POINT I/O (1734 series) with 1734-AENTR adapter. Two ports, DLR-capable. Default assembly 1 (input) and assembly 2 (output) provide auto-sized I/O mapping based on installed modules. CIP connection RPI 10–20 ms is typical.
- Turck TBEN-S / TBEN-S2 blocks. IP67, multi-protocol (PROFINET + EtherNet/IP via a switch), 8-port variants. RPI down to 1 ms is supported.
- Phoenix Contact Axioline F (AXL F BK EIP). EtherNet/IP bus coupler, supports up to 63 Axioline modules per station.
- Wago 750 series with 750-363 (EtherNet/IP fieldbus coupler). Up to 250 I/O points per node; suitable for dense I/O panels.
For most cells, the gateway will dedicate one CIP connection per I/O block. A 32-block POINT I/O installation consumes 32 CIP connections, well within the limit of mainstream gateways (HMS Anybus X-gateway supports up to 32 scanner connections; Phoenix Contact FL GW EIP PN supports up to 64).
SIMATIC ET 200clean in EtherNet/IP Cells
The SIMATIC ET 200clean is Siemens's decentralized I/O system for hygiene-sensitive environments such as food processing, pharmaceutical filling lines, and clean-room packaging. It carries IP69K protection, a stainless or PPS housing, and is fully PROFINET-integrated.
When an ET 200clean station must operate inside an EtherNet/IP-dominated cell (typical when the line is owned by a North American OEM that specifies EtherNet/IP throughout), the same gateway pattern applies: the ET 200clean connects to the Siemens side of the gateway via PROFINET, and its I/O is then exposed as CIP assemblies. The key installation constraints to verify with the Siemens product team are:
- Maximum PROFINET update time for ET 200clean: 1 ms with the right GSDML, 4 ms default.
- Hygiene approvals: NSF/ANSI 169, EHEDG, FDA-compliant materials – unchanged when the cell is bridged through a gateway because the gateway sits in the cabinet, not in the wash-down area.
- Cable routing: M12 push-pull connectors on ET 200clean must terminate at an IP65/IP67 cabinet gland before the gateway. Do not place the gateway inside the wash-down zone.
Note that ET 200clean is not an EtherNet/IP-native device; it always speaks PROFINET to the SIMATIC CPU. The gateway does the heavy lifting if EtherNet/IP is required upstream.
Configuration Parameters Reference
| Parameter | Typical value (drives) | Typical value (digital I/O) | Notes |
|---|---|---|---|
| PROFINET update time | 2 ms | 4 ms | Must be ≤ EtherNet/IP RPI to avoid data aging |
| EtherNet/IP RPI | 5 ms | 20 ms | Lower bound is 1 ms for most adapters |
| PROFINET watchdog | 3 × update time | 3 × update time | Drives usually use 192 ms minimum |
| CIP timeout multiplier | × 4 (16) | × 4 (16) | Encodes 4 RPI periods as the connection timeout |
| Byte order | Little-endian (no swap) | Little-endian | Siemens and CIP both default to little-endian |
| EDO (Electronic Data Overlay) | Optional per drive | Rare | For non-EDS drives, use EDO configuration in the gateway |
Verification and Diagnostics
Gateway-level checks
- LED pattern: green LINK on every CIP connection, no red SF, no red BF.
- Web server (default
http://<gateway IP>): Status > Connections shows every CIP connection in state Established with the last RPI in milliseconds. - Event log: no entry 0x01 (connection timeout) or 0x04 (configuration mismatch) within the last hour of operation.
Siemens-side checks
- Online > Accessible Nodes (TIA) or PLC > Ethernet Nodes (STEP 7): the gateway appears with its PROFINET name and IP.
- Watch table: PROFINET slots update at the configured update time without quality code 0x38 (provider stopped) or 0x39 (substitute values active).
- CPU diagnostic buffer: no PROFINET IO Device Failure entries for the gateway.
Drive-side checks
- Control Techniques / Nidec Unidrive: parameter
0.20.021(EtherNet/IP status) reportsInactive= 0 /Active= 1; parameter0.20.022reports the active assembly instances. - Digitax HD: web server Diagnostics > CIP Connection Status page.
Wire-level checks (Wireshark with CIP dissector)
Install Wireshark on a laptop connected to a mirrored port on the EtherNet/IP switch. Apply the display filter cip && ip.addr == 192.168.1.10 (replace with the drive IP). Verify:
- CIP Forward Open (service
0x54) appears once at connection start and again after any reset. - CIP Forward Close (
0x4E) only appears at planned shutdowns. - I/O messages (transport class 0/1) appear at the configured RPI within ±10 %.
- No CIP error responses (general status
0x01resource unavailable,0x05invalid parameter,0x1Fvendor-specific) under normal operation.
Troubleshooting Matrix
| Symptom | Likely cause | Fix |
|---|---|---|
| Gateway SF LED steady red, BF flashing | PROFINET device name not assigned | Use PRONETA or TIA to assign the PROFINET name to the gateway |
| Gateway PROFINET link up but all CIP connections in Timeout | EtherNet/IP devices on wrong subnet or VLAN | Verify gateway EtherNet/IP IP and the drive / I/O IPs are in the same subnet; disable QoS / VLAN tagging for the CIP VLAN |
| CIP connection establishes for ~30 seconds, then times out | RPI / PROFINET update mismatch, or QoS re-marking by switch | Set PROFINET update ≤ RPI; force PROFINET priority on the switch (DCP VLAN 0 priority 6) |
| Drives accept control word but no motion | Reserved bits high in control word, or wrong assembly selected | Reset all reserved bits; confirm assembly 100 vs 120 vs 150 in drive parameter 0.20.022
|
| Actual speed reports as huge negative value | Byte order swap on 32-bit speed word | Apply explicit byte-swap in the S7 FB or set the gateway to swap 32-bit words |
| Some POINT I/O blocks report fault 0x1F | EDS file mismatch with the block firmware revision | Update the EDS library to the latest ACD/EDS bundle; re-import the connection |
| Gateway cycles every ~90 s with no error in TIA | Watchdog from the gateway to the CPU times out | Set PROFINET update time ≥ 1 ms; check that CPU is in RUN, not STOP during a download |
| S7-1500 in STOP, gateway reports normal | Expected: gateway continues scanning; CIP connections persist but output data is frozen | Confirm PROFINET IO Device behaviour: outputs go to substitute values when CPU is STOP; drives must be configured to fall back to safe state on substitute |
Safety, Certification, and Sourcing Considerations
- Functional safety: PROFINET PROFIsafe and CIP Safety are not interchangeable. A PROFINET-to-EtherNet/IP gateway does not bridge PROFIsafe frames. Safety devices must remain on the same network family. If a SIL-rated drive must run on EtherNet/IP, use the drive's native CIP Safety on Scanner (e.g., Allen-Bradley GuardLogix) or its PROFIsafe-capable Siemens equivalent in a separate cell.
- ODVA conformance: Purchase EtherNet/IP devices from vendors that publish an ODVA Declaration of Conformity. Unbranded or cloned adapters frequently fail CIP Forward Open and behave inconsistently across firmware revisions.
- Cybersecurity: Enable the gateway's built-in firewall. Disable the CIP router advertisement service. Restrict the EtherNet/IP subnet at the managed switch port level. Apply Siemens' PCS 7 / TIA security patches on the standard cycle, and update the gateway firmware at least annually.
- Sourcing: The Siemens IE/PB Link PN IO (6GK1411-5AB00) is a PROFIBUS-to-PROFINET gateway, not an EtherNet/IP gateway. Do not confuse it with the IE/AS-i Link PN IO. For true EtherNet/IP scanning, use a third-party gateway as listed in the hardware table above.
Commissioning Checklist
- Pre-power checklist: ring topology verified, DLR supervisor assigned, PROFINET device names pre-loaded in PRONETA or topology editor.
- Power up sequence: cabinet PSU → managed switches → gateway → drives → I/O blocks → SIMATIC CPU last.
- Network scan: PRONETA shows all PROFINET devices with green status; Anybus ACM shows all CIP connections Established.
- Functional test: hand-drive each axis through the Siemens FB; verify status word bit 0 (Drive ready) toggles correctly.
- Safety test: trigger drive STO, verify drive enters safe state, verify the SIMATIC FB reports the fault within one PROFINET cycle.
- Soak test: run the cell for ≥ 4 h at full motion, log CIP connection uptime, gateway temperature, and CPU cycle time to ensure no drift.
Frequently Asked Questions
Does the SIMATIC S7-300 or S7-1500 support EtherNet/IP natively?
No. Every current SIMATIC CPU family requires an external gateway or an OPC UA bridge to act as an EtherNet/IP scanner. The CP 1543-1 / CP 1545-1 modules provide limited CIP server functions but cannot be used as a full scanner for drives and remote I/O. Refer to Siemens Entry ID 32989862 for the official guidance.
How many EtherNet/IP drives can one gateway support?
It depends on the gateway. The HMS Anybus X-gateway (PROFINET device / EtherNet/IP scanner) supports up to 32 CIP connections. The Phoenix Contact FL GW EIP PN supports up to 64. Each drive typically consumes one CIP connection, so plan the gateway headroom at 1.3 to 1.5 times the number of physical drives.
What is the right RPI for a Control Techniques Unidrive M700 over EtherNet/IP?
Start with a 5 ms RPI for the assembly 100/101 basic speed and a 5 ms PROFINET update time. For tight CNC-style applications using assembly 120/121, you can drop to 2 ms RPI on the gateway and 1 ms PROFINET update time, but verify the CPU has the bandwidth and the drive firmware revision supports the rate.
Can I bridge PROFIsafe safety frames through an EtherNet/IP gateway?
No. PROFIsafe is a PROFINET-only safety protocol and is not translated by commercial PROFINET/EtherNet/IP gateways. Safety-rated drives on EtherNet/IP must use CIP Safety on Scanner (GuardLogix family) or be placed in a separate PROFINET safety subnet.
Is the SIMATIC ET 200clean usable inside an EtherNet/IP cell?
Do I need a managed switch on the PROFINET side?
An unmanaged switch will work for small cells with one CPU and one gateway, but you lose LLDP, DCP, and port diagnostics. Use a managed switch (e.g., SCALANCE XC-200, Cisco IE-3300, or Phoenix Contact FL SWITCH 2300) for any cell with more than two PROFINET devices, and enable prioritized handling of PROFINET frames (VLAN 0, priority 6) on the switch.