FM 458-1 DP Know-How-Protect (6DD16070GA0): Technical Reference for D7-SYS Block Security
The FM 458-1 DP Know-How-Protect module (Siemens order number 6DD16070GA0) is a hardware security key designed for the SIMATIC S7-400 automation platform. It protects intellectual property embedded in user function blocks (FBs) generated with the D7 FB generator inside the D7-SYS engineering framework. This reference documents the architecture, scope of protection, configuration procedure, verification workflow, and operational constraints of the module based on the official Application Module FM 458-1 DP User Manual (A5E01078222-03, Edition 04.2011) and the related Siemens Industry Online Support entries, including the D7-SYS product support index (entry 13854).
1. Product Identification and Scope
| Attribute | Value |
|---|---|
| Product Designation | FM 458-1 DP Know-How-Protect |
| Siemens Order Number (MLFB) | 6DD16070GA0 |
| Parent Module Family | SIMATIC S7-400 FM 458-1 DP Application Module |
| Function | Hardware dongle for protecting D7-SYS user function blocks against unauthorized duplication |
| Engineering Tool | D7-SYS V5.1 (or compatible) |
| Programmable With | D7 FB-Gen (function block generator within D7-SYS) |
| Companion Manual | A5E01078222-03 (FM 458-1 DP Application Module User Manual, 04.2011) |
The module is a physical plug-in subassembly for the FM 458-1 DP rack. When seated in the rack it is interrogated by protected user FBs through a system function call; if the module is missing, or if the unique identification does not match what the FB expects, the FB can be configured to react in a user-defined manner (typically by halting execution, returning an error, or signalling a fault to the supervising S7-400 CPU).
2. Functional Architecture and Placement
The FM 458-1 DP family is a series of computing-intense application modules that mount in the SIMATIC S7-400 rack alongside the CPU. Typical tasks include high-speed closed-loop control, position/speed control of drives, technological preprocessing, and complex arithmetic operations that exceed the throughput of a standard CPU. D7-SYS is the configuration system for these modules and uses CFC (Continuous Function Chart) as the primary programming paradigm.
The Know-How-Protect subassembly (6DD16070GA0) is not a stand-alone CPU; it is a small identification/security module that piggybacks on the FM 458-1 DP main board. Architecturally it occupies a slot on the FM 458-1 DP carrier and provides:
- A unique non-volatile identification (serial-style identifier burned into the module).
- A hardware-presence flag readable by user FBs through the D7-SYS runtime library.
- A matching service used by the D7 FB-Gen to embed the expected identifier into compiled user FBs at build time.
At runtime, every protected FB executes a system function (provided by the D7-SYS runtime) that polls the slot. The system function returns:
-
TRUE+ matching identifier — the FB proceeds with normal execution. -
FALSE— dongle missing, wrong slot, wrong order number, or identifier mismatch.
Detection of the failure is then acted upon by the FB-specific response (see Section 6).
3. Scope of Protection
Understanding exactly what the module protects — and, just as importantly, what it does not protect — is critical before deploying it as a security control.
3.1 What IS Protected
- User function blocks generated by D7 FB-Gen. These are FBs you write in CFC and expose through the D7 FB generator for reuse. Once compiled with Know-How-Protect enabled, the FB runtime contains the dongle check.
- The IP of the technology embodied in the FB. Even if the CFC source, the compiled binary, and the configuration are copied, the FB will refuse to execute productively on a system lacking the matching dongle.
- License-bound deployment. One dongle per machine/line: the integrator can deliver the same configuration to many end users, but only the end user with the dongle can run the protected FBs.
3.2 What is NOT Protected
- CFC charts containing only Siemens library blocks (PID, motor, drive, math, etc.). These are pre-compiled blocks shipped with D7-SYS; they have no slot for the dongle query and therefore cannot be "locked" by this hardware. If you wish to hide a chart, the only barrier is access to the engineering project files.
- The non-protected portions of a mixed chart. If only some FBs in a chart are protected, the unprotected FBs continue to run normally even without the dongle.
- S7-400 CPU logic, HMI screens, drive parameter sets. The dongle's reach is limited to the FM 458-1 DP runtime and the user FBs that explicitly call its system function.
- Reverse engineering at the source level. The dongle cannot prevent a determined attacker from reimplementing the algorithm from behavioural observation. It enforces licensing, not cryptographic secrecy.
4. D7 FB-Gen Workflow with Know-How-Protect
The D7 FB generator (D7 FB-Gen) is the D7-SYS subsystem used to wrap a CFC chart as a reusable, typed FB. The Know-How-Protect option is selected at this stage:
- Open the D7-SYS project and the CFC chart that implements the technology to be protected.
- Launch the D7 FB generator from the D7-SYS menu (Tools → FB Generator).
- Configure the FB interface: inputs, outputs, static tags, and instance parameters as usual.
- In the FB generation dialog, enable the Know-How-Protect option. At this point D7 FB-Gen reads the identifier of the dongle currently plugged into the programming station (or into the target rack) and embeds that identifier as the expected value inside the compiled FB.
- Compile the FB. The resulting block is "tied" to the dongle ID observed at compile time.
- Document the dongle ID and the FB version in your engineering change log. The ID will be required for any future recompilation that targets the same protected asset.
If the dongle is not present during compilation, the FB-Gen will refuse to embed the protection bit, or it will compile the FB in an unprotected state. Always verify the engineering station configuration before starting a build that is intended to be locked.
5. Runtime Behaviour and the Identification Check
Inside each protected FB, the D7-SYS runtime library exposes a system function that interrogates the FM 458-1 DP hardware for the dongle. The function returns three pieces of information:
| Return Code | Meaning |
|---|---|
| 0 / OK, ID matches | Dongle present in correct slot, identifier matches expected value |
| 1 / Dongle missing | No Know-How-Protect module detected in the FM 458-1 DP slot |
| 2 / ID mismatch | Dongle present but identifier does not match the value compiled into the FB |
| 3 / Hardware fault | Module present but reporting an internal fault (replace module) |
Note: Exact return code numbering depends on the D7-SYS version. The D7-SYS V5.1 manual (referenced in the Siemens support index) and the FM 458-1 DP user manual should be consulted for the precise enumerations in your installed version.
6. Configuring the FB Response on Failure
The product documentation states explicitly: "The response in the case of a missing FM 458-1 DP Know-How-Protect module, or if the identification is incorrect, can be predetermined for each user function block individually." This means the developer chooses, per FB, what happens when the check fails. Typical response patterns include:
- Hard stop with output reset — all FB outputs are forced to safe defaults and the FB enters a latched fault state. Recommended for safety-relevant FBs.
- Output clamp with diagnostic bit — outputs held at last value or zero, a status boolean is set so the S7-400 CPU can alarm and the operator can be notified.
- Fault propagation through the FB status word — the FB completes its cycle with a quality code that the upstream logic evaluates, allowing graceful degradation.
- Shutdown request to the CPU — the FB sets a flag that the supervising S7-400 program interprets as a stop request. Use only when the system is designed for cold restart.
Whichever response you choose, document it in the FB header and in the safety/FMEA analysis. The response must be consistent with the risk assessment for the machine or process.
7. Step-by-Step Configuration Procedure
This procedure assumes D7-SYS V5.1, a working FM 458-1 DP application module in the S7-400 rack, and the Know-How-Protect subassembly 6DD16070GA0 physically installed on the FM 458-1 DP board.
7.1 Prerequisites
- SIMATIC S7-400 station with CPU (e.g., CPU 414, 416, 417).
- FM 458-1 DP application module mounted in the rack and configured in HW Config.
- Know-How-Protect subassembly
6DD16070GA0plugged into the FM 458-1 DP module. - D7-SYS V5.1 (or compatible) installed on the engineering station.
- STEP 7 / SIMATIC Manager matching the CPU firmware family.
- Administrative access to the engineering PC for compiling and downloading.
7.2 Procedure
- Hardware verification. Power down the S7-400 station. Confirm the FM 458-1 DP module is seated and that the Know-How-Protect subassembly is correctly installed. Power up and check that the CPU diagnostics do not flag the FM 458-1 DP as faulty.
- Open the D7-SYS project. Launch D7-SYS and open the project containing the technology to be protected.
- Identify the FBs to protect. Decide which FBs you will lock. Remember: only FBs that you yourself generate through D7 FB-Gen can be protected.
- Open D7 FB Generator. Inside D7-SYS, open the CFC chart that defines the FB and launch the FB generator.
- Enable Know-How-Protect. In the generator dialog, set the Know-How-Protect attribute. D7 FB-Gen will read the dongle ID from the connected FM 458-1 DP and embed it in the FB.
- Configure the failure response. Edit the FB body to handle the return code of the dongle-check system function. Wire the response to the FB's status outputs according to your chosen strategy (Section 6).
- Compile. Generate the FB and verify there are no warnings about missing dongle or unmatched identifiers.
- Download to target. Use STEP 7 to download the project (including the FM 458-1 DP configuration) to the S7-400 station.
- Test positive path. With the dongle present, start the CPU and confirm the FB runs. Monitor the FB status word — it should report "protected, OK".
- Test negative path. With the CPU in stop or in a controlled state, remove the dongle (or substitute the wrong dongle), restart the FB, and confirm the FB enters the configured failure response. Restore the dongle and confirm normal operation resumes.
7.3 Verification Checklist
| Check | Expected Result |
|---|---|
| CPU in RUN, dongle present | Protected FB executes normally; status word shows protection OK |
| CPU in RUN, dongle removed | Protected FB enters configured failure response within one cycle |
| Dongle replaced with mismatched unit | ID mismatch path triggers; FB does not execute payload |
| CPU restart with dongle present | Normal operation resumes after restart |
| Project downloaded to second station without dongle | Protected FBs refuse to run on the second station |
| D7-SYS diagnostics buffer | No spurious FM 458-1 DP faults reported |
8. Commissioning Field Notes
From a deployment perspective, treat the dongle as a deliverable line item. The integrator's project plan should explicitly reference 6DD16070GA0 as a separately shipped component that travels with the machine documentation. The end customer must understand that:
- Replacing the FM 458-1 DP module does not require a new dongle (the dongle is keyed to its own ID, not to the host module).
- Replacing the dongle requires re-compiling any FB that was originally tied to the old ID — keep a record of the ID in the project archive.
- Storing spare dongles off-site is recommended to avoid extended downtime after a dongle failure.
9. Limitations and Edge Cases
- Single dongle, single binding. The dongle binds one FB (or one set of FBs compiled at the same time with the same ID) to a specific identifier. To support a fleet, you need one dongle per machine.
- No cryptographic signature. The dongle check is an ID comparison, not a public-key signature. Do not rely on it to defend against a sophisticated reverse-engineering adversary.
- Compile-time vs. runtime ID. The ID is read from the dongle at compile time and embedded into the FB. If the dongle is later swapped without recompilation, the new ID will not match and the protected FB will fail.
- D7-SYS version dependency. Older D7-SYS versions may not support the Know-How-Protect attribute. Verify the FB-Gen dialog exposes the option before assuming a version supports the feature.
- Hardware fault on the dongle. The dongle is a physical component. Electrostatic damage, vibration, or thermal stress can render it unreadable. Spare units should be held in the maintenance stock.
10. Troubleshooting Matrix
| Symptom | Likely Cause | Diagnostic Step | Corrective Action |
|---|---|---|---|
| FB enters fault state immediately on CPU start | Dongle missing from FM 458-1 DP | Visually inspect slot, check S7 diagnostic buffer for FM 458-1 DP entries | Re-seat or replace dongle; verify module with HW Config |
| FB enters fault state although dongle is present | ID mismatch — FB compiled against different dongle | Compare FB compile log against the ID printed on the physical dongle label | Recompile FB against the correct dongle or install the original dongle |
| Intermittent FB fault during operation | Loose contact, vibration, thermal cycling | Inspect seating, check ambient temperature, review cabinet shock specs | Re-seat module; consider lock-tight hardware or cabinet rework |
| Cannot enable Know-How-Protect in FB-Gen | D7-SYS version does not support the option, or dongle not detected by ES | Check D7-SYS version against release notes; verify ES connection to FM 458-1 DP | Upgrade D7-SYS or connect the dongle to the FM 458-1 DP attached to the ES |
| CFC chart does not stop running without dongle | The protected FBs are not the ones driving the chart; only Siemens library blocks are in use | Inspect the chart for D7 FB-Gen blocks vs. Siemens library blocks | Wrap the technology in a user FB and recompile with Know-How-Protect |
| Re-downloaded project runs on a non-dongle station | Protected FBs not enabled, or compile did not embed the ID | Re-check FB generator options; review compile log | Recompile with Know-How-Protect enabled and the correct dongle connected |
11. Relationship to Other Siemens Protection Mechanisms
The Know-How-Protect module is one layer in a broader Siemens IP-protection ecosystem. Comparing it to adjacent mechanisms clarifies when to choose each:
| Mechanism | Scope | Strength | Best Fit |
|---|---|---|---|
| FM 458-1 DP Know-How-Protect (6DD16070GA0) | D7 FB-Gen user FBs on FM 458-1 DP | Hardware dongle, binds FB to physical module | Licensed deployment of high-speed control IP |
| STEP 7 Know-How-Protect (S7-300/400 CPU) | CPU-side FB source | Source-level password protection, easily bypassed at binary level | Casual disclosure protection only |
| S7-1500 Know-How-Protect (TIA Portal) | CPU-side blocks in TIA Portal | Stronger binding in TIA; not interchangeable with S7-400 | New S7-1500 projects |
| SIMATIC Logon / user administration | Engineering project access | Authentication, not code binding | Project-level access control |
| Drive-side parameter protection (e.g., SINAMICS) | Drive parameters and know-how option for BOP | Vendor-specific; not relevant to FM 458-1 DP | Drive tuning IP only |
For an S7-400 with FM 458-1 DP running time-critical technology, the FM 458-1 DP Know-How-Protect module is the strongest binding mechanism that Siemens offers at that layer. STEP 7's CPU-side know-how-protect is appropriate for normal PLC code but offers no enforcement against binary extraction.
12. Migration and Lifecycle Considerations
When planning projects that include protected FBs:
- Archive the dongle ID in the project archive metadata. Without it, recompiling after a lost dongle requires a new dongle plus a code-build event.
- Document the dependency between the FB version and the dongle generation. A dongle should outlast multiple FB revisions, but if the security model changes, plan a coordinated rollout.
-
Plan for spare dongles. Lead time for a replacement
6DD16070GA0may affect service-level commitments. - Coordinate with your Siemens representative for end-of-life notifications on the FM 458-1 DP family and the Know-How-Protect accessory.
13. Quick Reference Summary
| Question | Answer |
|---|---|
| What does 6DD16070GA0 protect? | D7 FB-Gen user function blocks on FM 458-1 DP |
| Does it protect Siemens library blocks? | No |
| Does it protect CFC charts? | Indirectly, only via the protected FBs inside the chart |
| Where is the identifier stored? | On the dongle itself, referenced by ID at compile time |
| Can the FB detect a missing dongle? | Yes, via the system function in the D7-SYS runtime |
| Can the response be customised per FB? | Yes, individually per FB at design time |
| Where do I get the manual? | Shipped with the product; complementary FM 458-1 DP manual at A5E01078222-03 |
14. Frequently Asked Questions
What is the order number of the FM 458-1 DP Know-How-Protect module?
The Siemens MLFB is 6DD16070GA0. It is sold as an accessory to the FM 458-1 DP application module for the SIMATIC S7-400.
Can the Know-How-Protect module lock a CFC chart that contains only Siemens library blocks?
No. Only FBs created with the D7 FB generator expose the Know-How-Protect attribute. Pure Siemens library charts cannot be hardware-bound by this dongle.
How does a protected FB know whether the dongle is present?
The D7-SYS runtime exposes a system function that the FB calls on each execution. The function returns a result indicating dongle presence, ID match, or hardware fault; the FB then enters the failure response configured at design time.
Does the dongle bind to the FM 458-1 DP hardware or to the FB binary?
The dongle carries its own identifier. The identifier is read at compile time and embedded in the FB. At runtime the FB compares its compiled expected ID with the ID reported by the dongle in the slot.
Where can I download the manual for 6DD16070GA0?
Siemens does not publish a stand-alone manual for the Know-How-Protect accessory. Manuals ship with the product on purchase. The companion FM 458-1 DP User Manual is available as A5E01078222-03 (Edition 04.2011), and D7-SYS documentation is listed in the Siemens support entry 13854.