Overview
The Siemens PCS 7 Advanced Process Library (APL) VlvL (Valve Logic) block is the standard type for motor-operated and solenoid valve control. Beginning with APL V9.0 the standard faceplate of a VlvL instance exposes three status indicators immediately to the left of the Permit/Interlock/Protect (PIP) button: a Bypass symbol, a Quality Code indicator, and a Padlock (lock/unlock) symbol. The Bypass symbol is the visible output of the AND-combination of two status bits on the VlvL block: Status1 bit 30 (Permit enabled) and Status3 bit 11 (Hidden bypass signal in Permit). Activating the symbol requires a correctly configured upstream Interlock-02 (Intlk02) block, the proper feature-bit settings on both blocks, valid bypass-license inputs, and a clean PCS 7 signal status of 16#00 on the connected inputs.
The same hidden-bypass naming convention exists across the PCS 7 family; the SIMOCODE pro PCS 7 Library V9.0 SP3 reserves a closely related set of bits in its motor-protection block, where the bit numbering convention differs from VlvL. The SIMOCODE pro manual lists Status3 bit 29 as Hidden bypass signal in Permit and Status3 bit 30 as Hidden bypass signal in Interlock Reverse — see the SIMOCODE pro PCS 7 Library V9.0 SP3 manual for the exact mapping. The VlvL numbering should be re-confirmed against the installed APL manual revision on the Siemens Industry Online Support portal.
Block Architecture: VlvL and Intlk02
The VlvL block implements a Permitted/Interlocked/Protected state machine. The Permit path is the interlock-aggregation result; the Interlock path is the protection path; the Protect path is the safety-critical trip path. In standard PCS 7 usage, the Permit input of VlvL is driven by the aggregated output of an Intlk02 block, which contains the bypass-evaluation logic and the operator-level bypass licenses that the hidden-bypass feature depends on.
Typical CFC topology:
-
VlvL (e.g.,
VLV_001) — receives Permit fromIntlk02.OUT, drives the valve command outputs. -
Intlk02 (e.g.,
INTLK_001) — aggregates two interlock sources (INO1,INO2) and exposes the hidden-bypass status used by VlvL. -
Upstream driver blocks (e.g.,
CH_AI,CH_DI, derived logic blocks) — provide theINO1andINO2Boolean values plus the PCS 7 signal-status attribute.
Feature Bits That Gate the Hidden Bypass
Two feature bits must be set for the hidden-bypass symbol to render and to track state changes in runtime:
| Block | Bit | Effect when set |
|---|---|---|
| Intlk02 | Feature.bit 2 |
Enables the internal bypass evaluation and propagates the hidden-bypass state through Intlk02.OUT to VlvL.Permit. |
| VlvL | Feature2.bit 2 |
Activates the Bypass and Quality Code indicators in the VlvL faceplate left of the PIP button. |
If either bit is not set the Bypass symbol remains hidden regardless of upstream wiring. Both bits are persistent and survive CFC compile / download cycles; they are part of the block instance and are stored in the offline / online database of the S7 AS.
Status Word Bit Mapping
The Bypass symbol in the VlvL V9.0 faceplate is the AND-combination of the following two bits:
- Status1.bit 30 — Permit enabled. Indicates the Permit path is active and not revoked by a Protective trip. This is the master enable for the symbol.
-
Status3.bit 11 — Hidden bypass signal in Permit. TRUE when Intlk02 reports that at least one connected signal (
INO1orINO2) is bypassed while the aggregatedOUTstill carries good quality (16#00).
BypLi01 and BypLi02 Configuration
Intlk02 exposes two bypass-license inputs that gate the operator's ability to bypass each connected signal path independently. The bypass license is the authorization to put a path into the bypassed state from the operator faceplate; it is not the bypass state itself.
| Input | Purpose | Recommended value |
|---|---|---|
BypLi01 |
License to bypass INO1
|
1 |
BypLi02 |
License to bypass INO2
|
1 |
With either BypLi set to 0 the operator cannot perform the bypass, and Intlk02 will not raise the hidden-bypass status to TRUE. The license is typically tied to a role-based authorization in the PCS 7 User Administration and may be driven by a process-condition tag (for example, maintenance mode active).
Signal Status 16#00 Requirement
INO1 and INO2 carry a PCS 7 signal-status attribute propagated from the upstream driver block. The signal status is encoded as a single-byte hexadecimal value in the low byte of the value attribute; the high byte carries the value itself. For the hidden-bypass symbol to indicate a clean bypassed, good quality state, both inputs must carry signal status 16#00 (good). Degraded statuses suppress the hidden-bypass evaluation and surface in the Quality Code indicator of the VlvL faceplate.
| Hex code | PCS 7 quality | Effect on hidden bypass |
|---|---|---|
16#00 |
Good (OK) | Hidden bypass exposed; Quality Code = green |
16#28 |
Uncertain / substituted | Hidden bypass suppressed; Quality Code = yellow |
16#40 |
Bad / device failure | Hidden bypass suppressed; Quality Code = red |
16#60 |
Bad / sensor failure | Hidden bypass suppressed; Quality Code = red |
16#80 |
Bad / out of service | Hidden bypass suppressed; Quality Code = red |
The signal status must be wired through every stage of the CFC chain. A common field error is to pass only the Boolean value from a derived logic block (e.g., a custom AND gate) without the status, which collapses the quality to 16#00 locally but masks any upstream degradation. The recommended practice is to use the APL composition blocks (And02, Or02) which propagate signal status correctly.
Step-by-Step CFC Configuration
- Open the CFC chart that contains the VlvL block in the PCS 7 engineering station (SIMATIC Manager / PCS 7 V9.0).
- Insert an
Intlk02block from the PCS 7 APL library onto the chart sheet. - Connect the upstream interlock sources to
Intlk02.INO1andIntlk02.INO2. Confirm that the signal-status attribute is wired through from the driver block (use the Signal Status column in the CFC interconnection view). - Connect
Intlk02.OUTtoVlvL.Permit. - Open the Object Properties of Intlk02 and set
Feature.bit 2 = 1in the I/Os tab. - Open the Object Properties of VlvL and set
Feature2.bit 2 = 1in the I/Os tab. - Configure
BypLi01 = 1andBypLi02 = 1on Intlk02. These may be hard-wired constants or driven by a maintenance-mode tag. - Compile the chart and download the program to the AS (target system).
- Open the VlvL faceplate in WinCC Runtime and confirm the Bypass and Quality Code indicators appear to the left of the PIP button.
- From the operator's Bypass dialog, set
INO1(orINO2) to Bypassed and verify thatStatus3.bit 11transitions to TRUE in online monitoring of Intlk02.
Online Monitoring Procedure
Use the CFC online view to confirm the hidden-bypass state end-to-end:
- Right-click the Intlk02 block and select Monitor (or press the eye icon).
- Open the VlvL block in the same way.
- In the Intlk02 faceplate, set
INO1to Bypassed via the Bypass dialog (operator right & license required). - Observe the change in
Intlk02.Status3.bit 11— it should transition from 0 to 1. - Observe the change in
VlvL.Status3.bit 11— it should also transition from 0 to 1 because the bit is propagated through the Permit path. - Confirm that
VlvL.Status1.bit 30(Permit enabled) remains 1 during the bypass action. If it drops to 0, the Protect path has been triggered and the Bypass symbol will clear. - Confirm the faceplate Bypass symbol renders green and the Quality Code indicator stays at
16#00.
Verification Checklist
- Symbol visibility: In the standard view of the VlvL faceplate, confirm the Bypass padlock/symbol and Quality Code indicator render to the left of the PIP button.
-
Bypass action: From the operator's Bypass dialog, set the corresponding INO1 or INO2 to Bypassed. In online monitoring,
Status3.bit 11(Hidden bypass signal in Permit) on Intlk02 should transition to TRUE. -
Quality Code: The Quality Code indicator should remain
16#00(green) while both inputs are bypassed with good upstream quality. If quality degrades, the indicator turns yellow or red and the Bypass symbol hides. -
Status1.bit 30: Verify the Permit-enabled bit remains TRUE while the hidden bypass is active. If the Permit input is revoked (for example, by a Protective trip),
Status1.bit 30goes FALSE and the Bypass symbol clears. -
Round-trip release: Releasing the bypass from the operator dialog must drop
Status3.bit 11back to 0 within one PCS 7 scan cycle and re-evaluate the interlock chain.
Troubleshooting Matrix
| Symptom | Likely cause | Corrective action |
|---|---|---|
| Bypass symbol not visible in faceplate |
VlvL.Feature2.bit 2 not set |
Set Feature2.bit 2 = 1 in VlvL object properties, recompile and download |
| Symbol visible but state never changes |
Intlk02.Feature.bit 2 not set |
Set Feature.bit 2 = 1 in Intlk02, recompile and download |
| Operator cannot perform bypass |
BypLi01 or BypLi02 = 0 |
Set both BypLi inputs to 1 or drive them from a maintenance-mode tag |
| Quality Code red or yellow while bypassed |
INO1 / INO2 signal status != 16#00
|
Inspect upstream driver block; resolve channel fault; ensure status propagation through derived logic |
| Bypass symbol clears immediately on activation | Permit revoked by Protect path | Check VlvL.Status1.bit 30; verify Protect inputs on VlvL |
Status3.bit 11 toggles unexpectedly |
Intlk02 wired to wrong inputs | Re-check INO1 / INO2 assignment and signal-status propagation |
| Symbol appears without bypass being applied | Stale online value after recompile | Re-initialize the block or perform AS cold restart |
| Bypass allowed in runtime but symbol absent | WinCC picture has older faceplate version cached | Recompile OS, transfer OS server, restart WinCC Runtime |
| Symbol shows red on first online after project migration | Feature bits reset to default after APL upgrade | Re-apply Feature.bit 2 and Feature2.bit 2 in all migrated instances |
Common Pitfalls
- Setting only one of the two feature bits — the symbol will not render at all.
- Forgetting to wire the signal-status attribute from the driver block to
INO1/INO2— the hidden-bypass evaluation requires16#00to expose the symbol. - Routing multiple interlock sources through a single INO without the appropriate PCS 7 OR/AND composition. Intlk02 expects two distinct connected signal paths.
- Confusing VlvL bit numbering with SIMOCODE pro block numbering. The SIMOCODE pro PCS 7 Library V9.0 SP3 reserves bit 29 for Hidden bypass signal in Permit and bit 30 for Hidden bypass signal in Interlock Reverse — see the SIMOCODE pro PCS 7 Library V9.0 SP3 manual. Always verify VlvL numbering against the installed APL manual revision.
- Assuming the bypass dialog is the same as the hidden-bypass symbol. The dialog drives the bypass state; the symbol is the visible summary. They are linked through
Status3.bit 11on Intlk02. - Authorizing the bypass at the user level but not at the engineering level (BypLi = 0). The two are independent: a user with operator right can still be denied bypass at the CFC layer.
Migration and Version Notes
When upgrading an existing PCS 7 project from APL V8.x to V9.0, the new VlvL faceplate elements (Bypass, Quality Code, Padlock) are introduced without an automatic migration script. Engineering teams should:
- Audit all VlvL instances for the presence of an upstream Intlk02 block. Where the Permit input is wired from a non-Intlk02 source, insert an Intlk02 instance and re-wire.
- Apply
Feature.bit 2on Intlk02 andFeature2.bit 2on VlvL globally using a CFC mass-operation if the engineering volume justifies it. - Recompile the OS server and transfer the runtime to pick up the new faceplate resources.
- Validate each valve loop in the PCS 7 Maintenance Station by performing a controlled bypass / release cycle.
Edge Cases and Field Observations
-
Permit tied to maintenance mode:
BypLi01/BypLi02are often driven by a plant-wide maintenance mode tag. If maintenance mode is reset while a bypass is active, the bypass persists until the operator releases it;Status3.bit 11remains TRUE but the BypLi input returns to 0, blocking further bypasses. - AS cold restart: After an AS cold restart, the bypass state of Intlk02 resets to 0 and the hidden-bypass symbol clears. The operator must re-establish the bypass. This is by design and aligns with safety requirements.
- AS warm restart: After an AS warm restart, the bypass state is retained; the hidden-bypass symbol remains visible if upstream conditions are still met.
- Cross-AS simulation: When using PCS 7 S7-PLCSIM, the signal-status attribute may not propagate identically to physical I/O. Verify the hidden-bypass behavior on the real AS before commissioning.
FAQ
What activates the hidden bypass symbol in the VlvL V9.0 faceplate?
VlvL Feature2.bit 2 must be 1, Intlk02 Feature.bit 2 must be 1, and both BypLi01 and BypLi02 must be 1 with INO1 and INO2 carrying signal status 16#00.
Why does the Quality Code indicator stay red or yellow even with the bypass applied?
The signal status of INO1 or INO2 is not 16#00. Inspect the upstream channel driver, resolve the degraded status, and re-verify. Derived logic blocks that strip the signal status are a common cause.
Which status bit on VlvL represents the hidden bypass in the Permit path?
Status3.bit 11 is the Hidden bypass signal in Permit. Status1.bit 30 is Permit enabled. The Bypass symbol in V9.0 is the AND of both bits.
Do I need an Intlk02 block, or can I drive Permit directly?
The hidden-bypass feature requires Intlk02 because the bypass evaluation and the BypLi licenses live on Intlk02. A direct Permit signal will not expose the hidden-bypass symbol or the Quality Code indicator.
Are the bit numbers the same as in SIMOCODE pro PCS 7?
No. SIMOCODE pro reserves bit 29 for Hidden bypass signal in Permit and bit 30 for Hidden bypass signal in Interlock Reverse. VlvL uses Status3.bit 11 for the Permit hidden bypass. Always confirm against the manual of the installed SP level.
What happens to the hidden bypass after an AS cold restart?
The bypass state on Intlk02 resets to 0, the hidden-bypass symbol clears, and Status3.bit 11 drops to 0. The operator must re-establish the bypass. After an AS warm restart, the bypass state is retained and the symbol remains visible.