Configuring IEC 60870-5-104 on Siemens S7-1200 and S7-1500 PLCs

David Krause19 min read
Industrial NetworkingSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Configuring IEC 60870-5-104 on Siemens S7-1200 and S7-1500 PLCs

IEC 60870-5-104 and IEC 61850 dominate substation telemetry and protection communication in transmission and distribution networks. Embedding these protocols on the SIMATIC S7-1200 and S7-1500 platforms enables a single controller to serve both process automation and supervisory SCADA gateways. This technical reference consolidates protocol fundamentals, data-point mapping, Siemens library options, commissioning parameters, and verification procedures for engineers deploying these stacks in substations, hydro plants, and rail electrification projects.

Overview

IEC 60870-5-104 is the network-access variant of the IEC 60870-5 series. It runs over TCP/IP on the standardized port 2404, transporting Application Service Data Units (ASDUs) from the IEC 60870-5-101 companion standard across a 104 transport interface. IEC 61850, published by the IEC TC57 committee as the Communication Networks and Systems for Power Utility Automation standard, uses an object-oriented information model (LD / LN / DO / DA) with Manufacturing Message Specification (MMS) and optional GOOSE/Sampled Values over Ethernet. A SIMATIC controller can act as a 104 slave (controlled station), a 61850 server (substation IED), a 104 master, or a 61850 client—and S7-1500 CPUs are often configured as a bridge between IEDs and the control center.

Side-by-side protocol comparison for SIMATIC integration
Parameter IEC 60870-5-104 IEC 61850
Transport TCP/IP, port 2404 MMS over TCP (port 102), GOOSE multicast, SV multicast
Data model Flat: IOA + ASDU type Hierarchical: LD → LN → DO → DA
Time synchronisation Optional CP56 time (7 bytes) SNTP / PTP (IEEE 1588) with timestamped reports
Configuration file SCADA-defined point list ICD / CID / SCD / IID in SCL (XML)
Reporting Spontaneous (cause 3) or interrogation (cause 20/21) Buffered (BRCB) and unbuffered (URCB) reports, GOOSE
Commands C_SC, C_DC, C_BO, C_SE with Select/Operate Operate / Cancel / SBO via MMS control services
Typical SIMATIC binding Custom FB or SIPLUS RIC IEC 61850 Option 9LA1110-6PC10-2BB8

IEC 60870-5-104 Protocol Architecture

The 104 protocol layers an Application Function Call on top of a strict supervisory session state machine. Three frame categories share one TCP socket:

  • I-frames (Information): carry ASDUs and increment the send / receive sequence numbers N(S) / N(R). Identified by the lowest two bits of byte 3 being 00b.
  • S-frames (Supervisory): acknowledge received I-frames without payload (N(R) only). Identified by 01b.
  • U-frames (Unnumbered): session control with function codes STARTDT, STOPDT, and TESTFR. Identified by 11b.

The APDU is prefixed by a single 0x68 start byte, followed by two APDU-length octets (length field is the number of body bytes and excludes the start byte and length octets). The TCP connection is normally established by the controlling station; the controlled station supports both passive and, when configured, active roles.

Session control state machine

STARTDT_actU-frame STARTEDdata exchange STOPDT_actU-frame STOPPEDawaiting STARTDT acceptance accept / decline

The session moves through three states: STOPPED, STARTED, plus an idle handling layer based on the t0..t3 timers. STANDARD parameter roles:

  • t0 — Connection establishment timeout; configurable from 1 to 30 s depending on link reliability expectations.
  • t1 — Acknowledgment timeout for an outstanding I-frame; typically 15 s. Expiry forces the controlling station to drop the connection.
  • t2 — Maximum interval the controlled station waits before sending an S-frame when only k−1 I-frames have been received and an explicit acknowledgment is needed; typically 10 s.
  • t3 — Idle test-frame interval for keepalive; typically 20 s. U-TESTFR frames are exchanged past t3 to confirm link health.

The parameter k defines the maximum number of unacknowledged I-frames before the peer must stop transmitting. Common field practice uses k = 6 or k = 12. The receive window value w is the latest N(R) acknowledged. Roll-over of sequence numbers is undefined in 104 — long sessions must be torn down before the 8-bit wrap to avoid ambiguity.

ASDU structure

Every ASDU carries an Information Object Address (IOA, 3 bytes), a Common Address (CA, 2 bytes), an Originator Address (OA, 1 byte), a Cause of Transmission (COT, 2 bytes), a Variable Structure Qualifier (VSQ, 1 byte), the Type ID (1 byte), and a number of information elements whose encoding depends on the type:

  • Type ID: defines information object layout (process value structure).
  • VSQ: SQ bit plus the number of objects (or number of elements when SQ=1).
  • COT: 2 bytes; lower 6 bits encode T (test, spontaneous, requested, etc.); bit 8 is the positive / negative flag, bit 9 is the test flag.
  • OA: 0 from master or per controlling station; some stations require this to be the originator's CA.
  • CA: station address; 1–65534 valid for 104.
  • IOA: 3-byte point address; range 1–16777215.
  • Information elements: process value(s) plus an optional CP56 time tag (7 bytes).

IEC 61850 Protocol Architecture

IEC 61850 divides the substation information model into Logical Devices (LD) composed of Logical Nodes (LN). Each LN groups Data Objects (DO) which are aggregates of typed Data Attributes (DA). The named-physical object is the IED; communication profiles include:

  • MMS (ISO 9506): client-server access for reports, control, configuration over TCP / 102.
  • GOOSE: Layer-2 multicast (IEEE 802.1Q, ethertype 0x88B8) for fast horizontal peer-to-peer messaging; usable in 4 ms-class latency scenarios.
  • Sampled Values (SV): Layer-2 multicast (ethertype 0x88BA) streaming of analog streams from merging units.
  • Web services (later editions): HTTP/SOAP for file transfer and engineering.

Configuration uses Substation Configuration Language (SCL), an XML schema. Four file classes describe the IED and substation:

  • ICD — IED Capability Description; vendor supplies, lists all LNs and DOs.
  • CID — Configured IED Description; project-specific instance with one or more datasets bound.
  • SCD — Substation Configuration Description; full substation including GOOSE / SV routing.
  • IID — Instantiated IED Description; tooled integration output.

SIMATIC S7-1200 / S7-1500 Platform Considerations

The decision to run a 104 or 61850 stack on a SIMATIC PLC is dominated by firmware support, work memory, and CPU cycle budget. The integration approach differs from adding a third-party gateway in that it eliminates an extra device, an extra IP hop, and an extra failure domain. Always reconcile the TIA Portal version, the CPU firmware, and the optional package (HSP) version before download — mismatch is a frequent source of "no symbol" errors on integration.

CPU and memory

SIMATIC CPU families suitable for IEC stack integration
Platform Example CPUs Typical work memory Recommended use
S7-1200 CPU 1215C DC/DC/DC, CPU 1217C 100–250 KB program, 400 KB–750 KB data Small substations, ≤ 500 SP points, single ASDU
S7-1500 CPU 1513-1 PN, CPU 1515-2 PN, CPU 1516-3 PN/DP 300 KB–1.5 MB program, 750 KB–5 MB data Medium substations, ≤ 2 000 points, multi ASDU
S7-1500 (high end) CPU 1517-3 PN/DP, CPU 1518-4 PN/DP 3 MB–6 MB program, 8 MB–20 MB data Large substations; IEC 61850 + 104 bridging
ET 200SP CPU 1510SP-1 PN, CPU 1512SP-1 PN, CPU 1514SP-2 PN 200 KB–1.5 MB program Distributed integration next to IEDs

Consult the official SIMATIC S7-1500 system manual on Siemens Industry Online Support for firmware revision specifics; the SIMATIC S7-1200 system manual is also available on Siemens Industry Online Support.

Programming environment

The SIMATIC world uses TIA Portal as the programming environment. Typical integration version pairs (CPU firmware ↔ TIA Portal HSP) at time of writing are:

  • CPU firmware V2.6 or higher for TIA Portal V15.1+ HSPs.
  • CPU firmware V2.8+ for IEC 61850 ICD import via TIA Portal V16 / V17.
  • CPU firmware V2.9+ for full TIA Portal V18 HSP coverage of IEC 61850.
  • CPU firmware V3.0+ for TIA Portal V19 features including SCL export of datasets.
Compatibility warning: Adding the IEC 61850 option to a project on a CPU whose firmware predates the option package prevents program download. Always reconcile CPU firmware and TIA Portal HSP versions before transferring the configuration to the device.

Official Siemens Library and Option Packages

Siemens provides maintained, supported IEC libraries for the SIMATIC platform. These are licensed options that require a runtime license key delivered through the TIA Portal License Manager or via the web license key delivery service.

Siemens IEC integration packages for SIMATIC
Option Order number Platform Function
IEC 61850 TIA Portal Option 9LA1110-6PC10-2BB8 S7-1500 / ET 200SP, TIA Portal V16+ IEC 61850 server (MMS), GOOSE publisher / subscriber, SCL import
IEC 61850 STEP 7 / PCS 7 Option 9LA1110-6PC10-2BC8 S7-400, STEP 7 V5 / PCS 7 IEC 61850 server for legacy PCS 7 systems
SIPLUS RIC IEC 60870-5 Library Per hardware (refer to Siemens Industry Online Support) S7-1500, S7-1200 (with RIC add-on) IEC 60870-5-101 / -104 client and server function blocks

Each option includes Function Blocks (FBs) for connection management, station control, data-point read/write, time synchronisation, and command handling. Documentation is delivered with the option package and registered in the TIA Portal help under "Optional Packages" after installation.

ASDU Data Point Types

Whether using a vendor library, the Siemens option packages, or a custom PLC implementation, the practical unit of work is the Information Object — a data point carrying a single measured or commanded process value. The ASDU Type ID determines the encoding structure and the size of the information element.

Most-used IEC 60870-5-104 ASDU types
Type ID ASDU name Direction Size (no time) Typical use
1 M_SP_NA_1 Monitoring 1 bit + quality Single-point binary status (breaker, alarm)
3 M_DP_NA_1 Monitoring 2 bits + quality Double-point (e.g., 0/1, 2-bit intermediate)
5 M_ST_NA_1 Monitoring 1 byte + quality Step position with transient bit
7 M_BO_NA_1 Monitoring 32 bits Bitstring (32 protection flags)
9 M_ME_NA_1 Monitoring 16-bit normalised Analog value in %
11 M_ME_NB_1 Monitoring 16-bit scaled Analog value with engineering range
13 M_ME_NC_1 Monitoring 32-bit IEEE 754 float Analog float (kV, MW, °C)
30 M_SP_TB_1 Monitoring + CP56 time 1 bit + 7-byte time Sequence-of-events recording
31 M_DP_TB_1 Monitoring + CP56 time 2 bits + 7-byte time Double-point with timing
34 M_BO_TB_1 Monitoring + CP56 time 32 bits + 7-byte time Bitstring with timing
36 M_ME_TE_1 Monitoring + CP56 time 16-bit scaled + time Analog scaled with timing
37 M_ME_TF_1 Monitoring + CP56 time float + time Analog float with timing
45 C_SC_NA_1 Control 1-bit command Single command (open/close)
46 C_DC_NA_1 Control 2 bits Double command (raise / lower)
50 C_BO_NA_1 Control 32 bits Bitstring command
51 C_SE_NA_1 Control 16-bit normalised Setpoint normalised
100 C_IC_NA_1 Control 1 byte qualifier General / group interrogation
103 C_CS_NA_1 Control 7-byte time Time synchronisation command

CP56 time encodes time as a 7-byte block: milliseconds (2 bytes), minutes (1 byte), hours (1 byte), day + month bit-packed in 1 byte, and year offset from 1900 in 1 byte. Receiving decoders must treat CP56 time as a binary structure rather than a numeric value and must derive the absolute year from the offset + 1900 with care for two-digit rollover conventions used by some SCADA masters (treat years >75 as 19xx; ≤ 75 as 20xx, or follow the SCADA's convention).

Configuration Parameters and Timing

The IEC 60870-5-104 standard lists a set of "system parameters" that must be agreed between controlling and controlled stations. The following table summarises the most frequently configured parameters with typical deployment ranges:

IEC 60870-5-104 link parameters
Parameter Meaning Typical value band
t0 Connection establishment timeout (s) 1 – 30
t1 Acknowledge timeout (s) 5 – 30
t2 No-data S-frame interval (s) 3 – 15
t3 Idle test-frame interval (s) 10 – 30
k Max outstanding I-frames 6 – 12
w Latest acknowledged N(R) 0 – 127
Common address (CA) Station address 1 – 65 534
IOA range Information Object Address per station 1 – 16 777 215
Originator (OA) Originator address (master / per station) 0 typically from master

For IEC 61850, equivalent configuration lives in the SCL files: Datasets bind DOs into named groups, Report Control Blocks (BRCB / URCB) define which datasets to report, and the integrity period (IntegrityTm) plus buffering (Buffered) drive data-flow behaviour. GOOSE control blocks in the GSEControl element of the SCL dictate multicast transmission parameters and VLAN priority.

Example TIA Portal data block for a 104 IOA


// S7-1500 Data Block excerpt for IEC 60870-5-104 IOA 1001 (single-point, no time)
DATA_BLOCK "DB_IEC104_Data"
  STRUCT
    stIOA1001_Sp : STRUCT
       bVal          : BOOL;   // 0 = OFF, 1 = ON
       bQualInvalid  : BOOL;   // quality flags
       bQualitySubst : BOOL;
       bQualityTest  : BOOL;
       bBlocked      : BOOL;
       bTopical      : BOOL;
    END_STRUCT;
  END_STRUCT;
END_DATA_BLOCK

Implementation Architecture

The SIMATIC PLC implementing a 104 / 61850 stack typically follows one of three architectural patterns:

Pattern A — Direct stack on the SIMATIC CPU

The IEC stack runs as Function Blocks inside a cyclic OB (typically OB1) with a connection interrupt for the TCP socket. This is recommended for small substations using S7-1500 with the SIPLUS RIC library, the Siemens IEC 61850 Option, or maintained third-party IEC libraries. Watch OB1 cycle time and increase the OB priority appropriately to keep frame delivery jitter under t2. A typical block-cycle slice under 50 ms is acceptable for substation use; harsher cycle budgets call for time-triggered OBs.

Pattern B — CP boundary with protocol conversion

A SIMATIC CP (e.g., CP 1543-1 for S7-1500) terminates WAN protocols while the CPU handles automation. The IEC stack can still run on the CPU; the CP is reserved for firewalling, VPN, and redundant WAN failover. CP 1543-1 plus CP 1243-1 (S7-1200) both support VPN IPsec and firewall functions; pair the protocol timeouts with the VPN MTU and any Maximum Transfer Unit reduction due to encapsulation.

Pattern C — Bridging IEC 61850 ⇄ IEC 60870-5-104

The SIMATIC controller is configured as an IEC 61850 client reporting from downstream IEDs, then exposes the relevant data as an IEC 60870-5-104 server to a higher-level SCADA. Demand careful dataset design: only publish DOs that the SCADA actually requests as 104 points, because every dataset member is sent with each report. Implement a watchdog signal in the IOA point list to propagate the 61850 link health (t1 timeouts, dataset quality flags) back to the master.

Pattern-to-CPU guidance
Pattern Recommended CPU Library / option Limits to verify
A CPU 1215C / 1217C, CPU 1513-1 PN Third-party IEC 104 FB / SIPLUS RIC ≤ 500 SP, ≤ 90 kB stack buffer
B CPU 1516-3 PN + CP 1543-1 IEC 61850 Option 9LA1110-6PC10-2BB8 + RIC CP firmware match, VPN bandwidth
C CPU 1518-4 PN/DP 9LA1110-6PC10-2BB8 + SIPLUS RIC Dataset size, BRCB dequeuing latency

Network and Topology Recommendations

SCADA MasterControl Center S7-1500 CPUIEC 104 server / 61850 client IEDsIEC 61850 server TCP / 2404 MMS / 102

Both IEC 60870-5-104 and IEC 61850 are sensitive to frame jitter and broadcast storms. Recommended deployment points:

  • Place the SIMATIC CPU on a dedicated VLAN / subnet for power-utility traffic. Do not mix with generic office VLANs.
  • Set the PROFINET port to a dedicated QoS class: DSCP 46 / EF for GOOSE; AF41 for 104 traffic is common.
  • Enable NTP or PTP time sync. IEC 60870-5-104 supports the COT cause time synchronised, while IEC 61850 requires quality-flag q.validTimetoSync on timestamped reports.
  • Lock the port speed and disable auto-negotiation per the IEC 61850-90-4 guidance on time-critical networks.
  • Avoid unmanaged industrial switches in the GOOSE path. Layer-2 QoS and IGMP snooping must be configured explicitly.
Security: The original IEC 60870-5-104 and IEC 61850 profiles carry no native encryption or authentication. When bridging to a WAN, place the IEC stack behind a CP with VPN / IPsec and add a firewall rule allowing only the controlling station IP onto TCP port 2404 (for 104) or TCP port 102 (for MMS in 61850). IEC 62351 mitigations for 104 are increasingly common; align your architecture with the operator's cybersecurity baseline.

Bandwidth and Load Estimation

A practical estimate of link load supports sizing of VPN tunnels, mobile radio paths, and buffering. For each ASDU the typical payload is:

Per-frame byte budget (excluding TCP / IP headers)
Type APDU header Information element CP56 time Total / frame
M_SP_NA_1 12 1 n/a 13 B
M_SP_TB_1 12 1 7 20 B
M_DP_TB_1 12 1 7 20 B
M_BO_TB_1 12 4 7 23 B
M_ME_TF_1 12 4 7 23 B

For N points updated at F Hz the approximate uplink bit rate is:


bps ≈ N × F × (bytes_per_frame + 12 APDU + 20 IP) × 8

Example calculations:

  • 100 SP points, 1 Hz, CP56 time: 100 × 1 × 32 × 8 = 25.6 kbps. Comfortably fits on any WAN link.
  • 1 000 floating-point points (M_ME_TF_1), 10 Hz: 1 000 × 10 × 35 × 8 = 2.8 Mbps. Requires dedicated link or aggregated paths.

Always add 10 – 20 % headroom for TCP / ACKs and U-TESTFR keepalive frames, especially on long-latency links. On paths exceeding 500 ms, raise t1 above 30 s or buffer spontaneous events on the controlled station side.

Testing and Verification

The IEC 61850 community uses IEDScout and MMS Object Explorer (client tools) to drill into the data model. For 104, master simulators exercise the link layer in both directions. Common acceptance procedures for the SIMATIC integrator include:

  1. Link-layer capture — capture the TCP / 2404 socket with Wireshark and verify the 0x68 start byte, length octets, and APDU direction sequence numbers.
  2. Frame-by-frame decode — use a protocol analyser to verify Type ID, IOA, and quality flags.
  3. General interrogation — issue C_IC_NA_1 with qualifier 20 (station interrogation, global) and confirm all configured data points are reported.
  4. Clock synchronisation — broadcast C_CS_NA_1 (Type 103) and verify the PLC accepts the time within ±1 s.
  5. Command flow — issue C_SC_NA_1 with Select-Before-Operate qualifier and confirm the two-step handshake per IEC 60870-5-104.
  6. Stress test — drive spontaneous report rate to 50 Hz on the configured datums and confirm the k window is respected and the link does not exceed t1.
Sample 104 interrogation frame (C_IC_NA_1, CA = 1, IOA = 0)
Byte Hex Meaning
0 68 Start byte
1–2 0E 00 APDU length (14 bytes)
3 00 Control field byte 1 (send sequence = 0)
4 00 Control field byte 2 (recv ack = 0)
5 64 Type ID 100 = C_IC_NA_1, interrogation command
6 01 VSQ, SQ = 0, num = 1
7 14 COT low byte (20 = interrogation, with test flag)
8 00 COT high byte
9 00 Originator = 0
10–11 01 00 Common Address (CA = 1)
12–14 00 00 00 IOA 0 (interrogation qualifier follows)
15 14 QOI = 20 (station interrogation, global)

Limitations and Field Considerations

Recording constraints that should influence any integration decision:

  • No offline buffer. Many compact 104 implementations drop packets on TCP disconnect. Confirm with the library documentation or test by severing the cable at intervals and counting missing spontaneous events.
  • Memory ceiling on S7-1200. The data block that backs each information object occupies roughly 12–28 bytes depending on ASDU type and CP56-time inclusion. A 500-point float dataset with CP56 time consumes approximately 1.4 MB — feasible on a CPU 1215C and beyond, but borderline on a CPU 1214C.
  • Single SPDU TX queue. Many small-footprint stacks use one TCP connection per station. To support multiple controlling stations you must plan for either multiple OB instances or a master-role stack.
  • Time-tagging timing. CP56 time must be appended at the moment of transmission, not at the moment the sample was taken, to comply with sequence-of-events expectations.
  • Lifecycle. Whether using a vendor-supported option or a custom library, prefer solutions with a documented maintenance path. Libraries without an active maintainer introduce risk on multi-year operational systems.
  • TC + IP header overhead. Each APDU encapsulates inside Ethernet + IP + TCP at roughly 54 bytes of overhead, so consider the Egress bandwidth not just the payload size.

Sample Commissioning Checklist

  1. Verify CPU firmware and TIA Portal version against the option package compatibility matrix on Siemens Industry Online Support.
  2. Import the IEC 61850 SCD file or prepare the 104 point list. Build matching data blocks in TIA Portal.
  3. Configure IP address, subnet mask, and VLAN if applicable.
  4. Transfer and start the PLC program. Verify license-key status under PLC > Properties > Protection & Security.
  5. From a test master, drive a General Interrogation and confirm all points return with correct COT and quality.
  6. Issue a Select-Before-Operate pair from the master and confirm the PLC acknowledges both before executing.
  7. Capture the TCP session with Wireshark; export the first 100 frames for the IEC acceptance log.
  8. Document the parameter set (t0, t1, t2, t3, k, w, CA, OA) for the as-built substation record.
  9. Set up a Watch-dog function block to alarm on k-window overruns or t1 timeouts.
  10. Schedule a calendar reminder for library updates and firmware release reviews.

Comparison: Siemens Option vs. Custom or Third-Party Stack

Decision matrix for selecting IEC stack supplier
Criterion Siemens 9LA1110-6PC10-2BB8 + SIPLUS RIC Custom or third-party PLC IEC stack
Support and updates Global Siemens support, MA-N numbered updates Vendor-dependent, may be limited
Documentation Full manual set, SCL imports, sample projects Often brief, sample FB comments only
Compliance certification Tested with industry conformance tools Often untested or only field-tested
Firmware dependency HSP-tied to specific TIA Portal + CPU firmware Runs on generic PLC firmware
Cost License fee per CPU Free or per-developer
Scalability Hundreds of points, multi-station ready Typically limited to ~500–1 000 SP points
Lifetime cost of ownership Lower over 10–20-year operational life Can rise sharply with maintenance turn-over
Recommendation: For greenfield substation projects with multi-decade operational expectations, use the Siemens-supported option. For retrofit or development lab use, a third-party stack may offer a faster route to proof of concept, with a documented migration path to the supported option for production deployment.

Frequently Asked Questions

Which Siemens CPU firmware versions support the IEC 61850 TIA Portal Option (9LA1110-6PC10-2BB8)?

The IEC 61850 TIA Portal Option is delivered through TIA Portal V16, V17, V18, and V19 HSPs. The exact CPU firmware baseline and supported CPU list must be verified against the option's release notes on Siemens Industry Online Support; included CPUs cover CPU 1510SP-1 PN, CPU 1512SP-1 PN, CPU 1513-1 PN, CPU 1515-2 PN, CPU 1516-3 PN/DP, CPU 1517-3 PN/DP, and CPU 1518-4 PN/DP.

What is the default TCP port for IEC 60870-5-104 and can it be changed?

The IEC 60870-5-104 standard assigns TCP port 2404 to the protocol. The port is configurable on the controlled station, but only by mutual agreement with the controlling master. Moving the service off 2404 is sometimes done to integrate with corporate firewall rules; the SCADA point list and firewall policy must then both reference the new port.

Can one SIMATIC CPU serve as both an IEC 61850 client and an IEC 60870-5-104 server?

Yes. High-end S7-1500 CPUs (CPU 1516-3 PN/DP, CPU 1517-3 PN/DP, or CPU 1518-4 PN/DP) coupled with the IEC 61850 Option plus a separate IEC 60870-5-104 implementation can act as a bridge: IEC 61850 client reading DOs from downstream IEDs, then publishing the relevant values over IEC 104 to a higher-level SCADA. Watch the OB1 cycle time, dataset size, and licence compliance.

How many data points can a SIMATIC S7-1200 scale to for IEC 60870-5-104?

Realistic limits fall between 300 and 500 SP points on a CPU 1215C with CP56 time supported, depending on the CPU firmware version and stack overhead. S7-1500 controllers can comfortably exceed 1 000 points. Confirm with a stress-test of the chosen stack before committing to project counts.

Does IEC 61850 GOOSE replace IEC 60870-5-104 for substation automation?

No. GOOSE is a substation-local fast messaging layer that serves inter-IED interlocking and protection tripping. IEC 60870-5-104 is the wide-area telemetry protocol that connects the substation to control centers. Most deployments use both: GOOSE for horizontal protection messaging and 104 for SCADA telemetry.

Back to blog