Overview
This technical reference describes how to configure a Siemens ET200S distributed I/O station equipped with an IM-151-8 PN/DP interface module as an S7-300-class controller in STEP 7 V5.7, and use the MODBUSPN function-block library to poll energy meters (e.g. Schneider Electric PM710, PM5000, PM8000 families) over Modbus TCP. The procedure covers hardware configuration, library installation, TCON_IP_V4 connection setup, the MB_CLIENT call structure, multi-drop addressing through the Modbus Unit Identifier, and the practical constraints imposed by the ET200S firmware when working as an S7-300 station rather than an S7-1200/1500 controller.
The IM-151-8 PN/DP (order numbers 6ES7151-8AB01-0AB0 and later -0BB0x releases) is unique because it can operate either as an I/O device on PROFINET/PROFIBUS or as a stand-alone PLC-like station. When used in PLC-mode it is programmed from STEP 7 V5.x with classic S7-300 function blocks, which means the modern S7-1200/1500 Modbus blocks (MB_CLIENT, MB_SERVER from the TIA Portal libraries) are not available. Instead the older MODBUSPN library (also referred to in Siemens documentation as the "MODBUS_PN" / "Modbus/PN-CP" library for S7-300 / ET200S CPU-mode) provides the equivalent functionality.
Prerequisites
- STEP 7 V5.7 (or V5.6 with SP2) installed and licensed. STEP 7 V5.7 is the last classic version; floating or single-user licenses are valid. See the STEP 7 V5.7 release notes for installation and license requirements.
- MODBUSPN library package downloaded from the Siemens support portal (entry ID 23923230 or 26662490 depending on revision). Extract the archive into a working folder; the library file is typically named
S_MODBPNorModbus_PN_CPU. - ET200S station with IM 151-8 PN/DP CPU-mode enabled, firmware ≥ V3.0 (firmware ≥ V3.2 recommended for stable Modbus TCP polling).
- Ethernet connection between the IM-151-8 PN/DP PROFINET port and the Modbus TCP gateway or the energy meter if it has an embedded Ethernet port.
- Energy meter documentation listing Modbus register map (function code, register start address, scaling, units). Schneider PM710 default Modbus parameters: Unit ID 1, 19200 8N1 for RS-485; for Ethernet gateway these are translated to Modbus TCP holding registers starting at 40001.
- Network access to assign a valid IP address to the IM-151-8 PN/DP CPU interface (PN IO port, X1).
Hardware & Software Requirements
| Item | Specification | Notes |
|---|---|---|
| Interface module | 6ES7151-8AB01-0AB0 / 8BB01 | IM-151-8 PN/DP CPU, 3 PROFINET ports (X1/X2 switch) + 1 PROFIBUS DP |
| Firmware | ≥ V3.0.1 (latest V3.3) | Required for MODBUSPN FC11 stability |
| STEP 7 | V5.7 (or V5.6 SP2) | Classic STEP 7, not TIA Portal |
| Library | MODBUSPN (S7-300 compatible) | Free from Siemens support, entry ID 23923230 |
| Modbus TCP port | 502 | Standard IANA assignment; configurable on meter |
| Energy meters | Schneider PM710 / PM5000 / PM8000 series | 10/15/15 devices per gateway typical |
| Gateway (optional) | Schneider EGX100 / EGX300 / Link150 | RS-485 ↔ Modbus TCP gateway if meters are serial |
ET200S IM-151-8 PN/DP Architecture
The IM-151-8 PN/DP differs from the lower-end IM-151-1 / IM-151-3 PROFINET heads because it includes an internal backplane CPU capable of executing a STEP 7 V5.x user program. From STEP 7's perspective it behaves as an S7-314/315-class CPU with restricted work memory (work memory 128 KB–384 KB depending on firmware revision). The PROFINET port X1 of the interface module is the only Ethernet interface available for Modbus TCP communication; it must be configured with a fixed IP address in the same subnet as the energy-meter gateway.
Key architectural constraints:
- The PROFINET stack and the user TCP connections share the same physical port. Up to 8 open TCP connections are supported concurrently (this is the limit imposed by the Open Communication Wizard / TCON resources of the CPU).
- Modbus TCP polling must use the Open Communication Services (OC) via TCON, TSEND, TRCV, TDISCON blocks. The MODBUSPN library wraps these into dedicated function blocks.
- No hardware Modbus TCP CP (e.g. CP343-1 Lean) is required — the integrated PN interface handles the TCP traffic natively.
MODBUSPN Library Installation
- Download the library archive (e.g.
Modbus_PN_CPU_Vxx.zip) from the Siemens support portal, entry ID 23923230. - Extract to a local working directory. The archive contains the program files of standard S7 blocks such as
FC11 "MODBUSPN"(Modbus PN client),FB11 "MODBUSPN_DB"(instance DB), andUDT1 / UDT2for parameter structures. - Open the SIMATIC Manager and your S7 project.
- From the menu choose Options → Install Library and select the extracted
*.s7lor*.zipfile. - The library MODBUSPN appears in the library navigator (left pane) under "Standard Library → MODBUSPN".
STEP 7 V5.7 — Step-by-Step Configuration
1. Hardware Configuration
- Open HW Config for the ET200S station.
- Insert the IM 151-8 PN/DP in slot 0 of the ET200S rack. Double-click the module to open its properties.
- Assign a fixed IP address (e.g.
192.168.10.50/ mask255.255.255.0) to the PROFINET interface X1. - If the PROFINET port is part of an IO-controller relationship with an upstream PLC, ensure the Modbus TCP traffic does not collide with PROFINET IRT cycles. Set the update time of the PROFINET connection to 1 ms and place the Modbus TCP TCON connections in a higher priority OB (e.g. OB35 cyclic interrupt 100 ms).
- Save and compile the hardware configuration; download to the IM-151-8 PN/DP CPU.
2. Create the Modbus Data Buffer DB
Create a shared DB (e.g. DB100 — "Modbus_Buffer") to hold the read data. A practical layout for 15 PM710 analyzers at 100 registers each is shown below:
| Offset | Symbol | Type | Description |
|---|---|---|---|
| DBW 0 | REQ_START | BOOL | Edge-triggered start request |
| DBW 2 | BUSY | BOOL | FB11 in progress |
| DBW 4 | DONE | BOOL | Read completed without error |
| DBW 6 | ERROR | BOOL | Error flag |
| DBW 8 | STATUS | WORD | Modbus/TCP status (16#xxxx) |
| DBW 10 | CONN_ID | WORD | Local connection ID (must be unique per gateway) |
| DBW 12 | UNIT_ID | BYTE | Modbus Unit Identifier 1…247 |
| DBW 14 | START_ADDR | DWORD | Modbus holding-register start (e.g. 40001 = 0) |
| DBW 18 | LENGTH | WORD | Number of 16-bit registers to read (max 124) |
| DBW 20 | DATA_PTR | DWORD | Pointer to destination area in DB110 |
| DBW 24 | METER_INDEX | INT | 0…14 — selects the meter currently polled |
3. Create the TCON_IP_V4 Connection DB
The TCON parameter structure is required for every Modbus TCP connection. Create one DB per gateway (e.g. DB200 — "Modbus_Connection_1") with a UDT of type TCON_IP_V4. The UDT is not visible in the dropdown list of STEP 7 V5.7 — type the symbol manually; the compiler recognizes it from the type catalog.
Typical values for an EGX100 gateway at 192.168.10.20:
DATA_BLOCK "Modbus_Connection_1"
TITLE = "Modbus TCP connection to EGX100"
VERSION : 0.1
STRUCT
InterfaceId : BYTE := B#16#1; // PN interface (X1) of IM-151-8
Connect_Type : BYTE := B#16#11; // TCP active connection
ActiveEstablished : BOOL := TRUE;
LocalPort : WORD := W#16#0; // 0 → assign automatically
RemoteAddress : IP_V4 := '192.168.10.20'; // gateway IP
RemotePort : WORD := W#16#1F6; // 502 decimal
LocalAddress : IP_V4 := '192.168.10.50'; // IM-151-8 IP
END_STRUCT;
END_DATA_BLOCK
The local connection ID (CONN_ID) is a WORD you assign yourself; keep it unique across the project. For 15 meters behind a single gateway, only one TCON connection is required, but the Modbus UNIT_ID inside each poll changes per meter.
4. Wire the MB_CLIENT Call (FC11)
The MODBUSPN library exposes FC11 "MODBUSPN" as the Modbus TCP client. Use a cyclic interrupt OB (recommended: OB35 at 100 ms; minimum cycle 50 ms for stable 15-meter polling). Insert FB11 "MODBUSPN_DB" with instance DB DB11, and wire it from DB100.
CALL FB11, DB11
REQ := "Modbus_Buffer".REQ_START
ID := "Modbus_Buffer".CONN_ID // e.g. W#16#0001
UNIT_ID := "Modbus_Buffer".UNIT_ID // 1…247, one per PM710
START := "Modbus_Buffer".START_ADDR // e.g. 0 (= Modbus 40001)
LENGTH := "Modbus_Buffer".LENGTH // e.g. 100, max 124
DONE := "Modbus_Buffer".DONE
BUSY := "Modbus_Buffer".BUSY
ERROR := "Modbus_Buffer".ERROR
STATUS := "Modbus_Buffer".STATUS
DATA_PTR:= P#DB110.DBX0.0 BYTE 200 // pointer to destination area
5. Cycle Through the 15 PM710 Meters
Because only one MODBUSPN instance is active at a time, build a sequencer in OB35 (or a separate FC) that increments METER_INDEX after each DONE = TRUE. The sequencer changes START_ADDR, LENGTH, UNIT_ID, and DATA_PTR for the next meter.
Example mapping (PM710 default register layout, 100 registers each):
| Index | Unit ID | Modbus Start | Length | Dest DB110 Offset |
|---|---|---|---|---|
| 0 | 1 | 40001 | 100 | 0 |
| 1 | 2 | 40001 | 100 | 200 |
| 2 | 3 | 40001 | 100 | 400 |
| … | … | … | … | … |
| 14 | 15 | 40001 | 100 | 2800 |
Total cycle time for 15 meters × 100 registers at a 100 ms OB35 poll = ~1500 ms (well within the 1.5 s refresh tolerance for energy measurement).
Modbus Function Codes Used
| FC | Name | Typical Use | PM710 Reference |
|---|---|---|---|
| 03 (0x03) | Read Holding Registers | Energy, power, demand, min/max | Registers 40001–40100 |
| 04 (0x04) | Read Input Registers | Instantaneous measurements | Registers 30001–30100 |
| 06 (0x06) | Write Single Register | Reset energy, set parameters | Register 40531 (energy reset) |
| 16 (0x10) | Write Multiple Registers | Batch configuration | Setup registers 40201–40210 |
MODBUSPN FC11 supports FC03, FC04, FC06, and FC16 out of the box. The function code is implicit in the direction of the request — for reading, set the input MODE = B#16#03 (or 0x04 for input registers). For writing, switch to FC06/FC16 mode via the dedicated FC13 / FC14 blocks included in the MODBUSPN library.
PLCSIM Simulation
STEP 7 PLCSIM (V5.4 SP8 or later) supports S7-300 programs but does not virtualize the PROFINET stack of the IM-151-8 PN/DP. The TCON instruction will return STATUS = 16#80A7 ("connection not established") or 16#80C4 ("temporary communication error").
To develop and commission without physical hardware, use one of the following:
- PLCSIM + 3rd-party Modbus simulator: Run a Modbus TCP server on the engineering PC (e.g. Modbus Poll, Modbus Slave, or the open-source diagslave tool) and bridge PLCSIM to it using NetToPLCSIM. NetToPLCSIM is an open-source tunneling tool that maps PLCSIM's virtual Ethernet port onto the host's network so external TCP/UDP traffic is reachable by the simulated CPU.
- PLCSIM Advanced (≥ V2.0) + Modbus Slave: PLCSIM Advanced supports simulating S7-1500/ET200SP CPUs with real network interfaces; for S7-300/IM-151-8 the same NetToPLCSIM technique applies.
- Real hardware bench: Use a single physical PM710 or a Modbus TCP simulator (e.g. Modbus Tools) and the actual IM-151-8 PN/DP; this is the most reliable commissioning method.
ping from the engineering PC to the simulated CPU before troubleshooting the application code.Verification & Commissioning
- Online → PLC → Operating Mode → ensure the IM-151-8 PN/DP is in RUN with no SF/BF diagnostic LEDs.
- Open DB100 online and trigger
REQ_START = TRUEfor the first meter (Index 0). - Watch
DONErise within 200–500 ms;STATUSshould equal16#0000. - Open DB110 and confirm the first 100 registers contain valid PM710 data (e.g. Voltage L-L in register 0 should be around 400 V ± 10 % for a European installation).
- Disable
REQ_START(set to FALSE) before switching to the next meter; rising-edge triggered calls are mandatory per the MODBUSPN manual. - Repeat for all 15 meters; verify the cycle completes within 2 s end-to-end.
- Capture a Wireshark trace on the engineering PC with display filter
tcp.port == 502to confirm MBAP/PDU sequence: Tx → Rx → Tx → Rx … without retransmissions.
Troubleshooting Matrix
| Symptom | STATUS Code | Likely Cause | Action |
|---|---|---|---|
| DONE never rises, BUSY remains TRUE | — | REQ not edge-triggered, no re-trigger after DONE | Set REQ = TRUE on a rising edge, reset on DONE |
| ERROR = TRUE, STATUS = 16#80A7 | Connection resource not available | CONN_ID already used or TCON never called | Verify CONN_ID uniqueness; call TCON first in OB100 |
| STATUS = 16#8187 | Modbus exception 0x02 (illegal data address) | START_ADDR out of meter range or wrong Unit ID | Verify PM710 register map; check Unit ID matches the polled device |
| STATUS = 16#8188 | Modbus exception 0x03 (illegal value) | LENGTH > 124 or zero | Reduce LENGTH; maximum 124 registers per request |
| STATUS = 16#80C4 | Temporary TCP error | Gateway offline, cable issue, firewall blocking 502 | Ping gateway; check Windows firewall on engineering PC; verify VLAN |
| BF LED on, SF blinking | — | PROFINET cable broken, duplicate IP, gateway subnet mismatch | Check X1 link LEDs; verify IP / mask; use a switch with port-mirror to Wireshark |
| Data returns zeros after poll | — | DATA_PTR null or wrong DB opened | Use symbolic pointer P#DB110.DBX0.0 BYTE 200; open DB110 in online view |
| Sequencer stalls on meter 7 | 16#80A1 | CPU work-memory overflow, instance DB too small | Check DB11 size (≥ 256 bytes); reduce LENGTH per meter |
| PLCSIM cannot reach Modbus device | — | NetToPLCSIM not started or wrong IP mapping | Run NetToPLCSIM, map PLCSIM IP 192.168.10.50 to host NIC |
Migration Considerations
If you anticipate migrating the application to a S7-1200 (CPU 1215C, CPU 1217C) or S7-1500 (CPU 1511, ET200SP CPU 1510SP-1 PN), the MODBUSPN library is replaced by the TIA Portal libraries MODBUS_TCP (S7-1500) or the MODBUS TCP blocks of MB_CLIENT / MB_SERVER (S7-1200). These provide a more efficient MBAP stack and dynamic connection pools. For systems designed today, the IM-151-8 PN/DP + MODBUSPN path remains supported but is considered a legacy path; new installations are encouraged to use ET200SP with CPU 1510SP/1512SP and TIA Portal V18+.
Performance & Timing Notes
- A single poll of 100 registers on a 100 Mbit/s Ethernet typically completes in 25–60 ms (round-trip including TCP ACK).
- OB35 at 100 ms with a sequencer of 15 meters yields a worst-case refresh latency of ~1.5 s; this is suitable for energy measurement, not for transient power-quality monitoring (use a faster OB for that).
- The PROFINET IRT update time should be set to ≥ 1 ms when the same port carries both IRT and Modbus TCP traffic; 500 µs updates can starve the OC stack.
- Do not exceed 8 concurrent TCON connections on the IM-151-8 PN/DP. If you need more, use a CP343-1 Lean/Advanced module in slot 1 of the ET200S rack (firmware permitting).
Safety & Reliability Notes
Energy meter polling is non-safety, non-deterministic network traffic. Do not rely on the polled values for SIL-rated protective functions. If the Modbus connection fails, the destination DB110 values should be either zeroed, frozen at the last good value, or marked with a quality byte — implement this in the sequencer FB to prevent downstream control logic from acting on stale or corrupted data.
FAQ
What is the difference between MODBUSPN and the TIA Portal MB_CLIENT?
MODBUSPN is the legacy library for S7-300 CPUs and the IM-151-8 PN/DP CPU-mode, distributed as free function blocks (FC11, FB11). MB_CLIENT / MB_SERVER are the TIA Portal native blocks for S7-1200/1500 with a more modern MBAP stack and dynamic connection pools. Both implement Modbus TCP over Open Communication Services; MODBUSPN requires manual TCON_IP_V4 setup, while MB_CLIENT manages its own connections.
How do I poll multiple energy meters behind a single gateway?
Open one TCON_IP_V4 connection to the gateway IP and increment the Modbus UNIT_ID (1…247) on each MB_CLIENT call. The gateway routes the request to the matching serial port or IP/port pair. Avoid opening separate TCON connections for each meter unless they sit on different IP addresses.
Can I read more than 124 registers in a single MB_CLIENT call?
No. The Modbus Application Protocol (MAP) limits the PDU to 253 bytes; for 16-bit registers that is 124 words. Any request above 124 registers must be split into two or more calls with different START_ADDR values.
Why does the connection fail when I run STEP 7 PLCSIM?
Standard PLCSIM does not expose the simulated PROFINET port to external network devices. Use NetToPLCSIM (Siemens-supported open-source utility) to bridge the virtual PLC's Ethernet port to the host's NIC, then point the gateway or Modbus Slave at the simulated IP address.
Do I need an additional license to use MODBUSPN?
No. The MODBUSPN library is delivered as free function-block source from the Siemens support portal (entry ID 23923230). A valid STEP 7 V5.7 license is sufficient — no per-block runtime license is required on the IM-151-8 PN/DP.