Configuring PROFIBUS Between SINUMERIK 840D sl and S7-1200

David Krause13 min read
ProfibusSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Configuring PROFIBUS Between SINUMERIK 840D sl and S7-1200 with CM 1242-5

Overview

Integrating a legacy SINUMERIK 840D sl (solution line) NCU into a new auxiliary station built around a SIMATIC S7-1200 requires a PROFIBUS DP segment that is independent of the existing drive bus. The S7-1200 is extended with a CM 1242-5 communications module so it can appear as a DP slave on the 840D sl's PROFIBUS network. This guide covers the GSD file, port selection (X126 vs. X136), TIA Portal device configuration, SINUMERIK commissioning, PLC programming, verification, and field diagnostics.

The link supports DP-V0 cyclic I/O exchange and S7 communication over PROFIBUS when both sides are configured consistently. The 840D sl integrated PLC (a S7-300 compatible CPU inside the NCU) acts as DP master; the S7-1200 with CM 1242-5 acts as DP slave.

Functional role: The CM 1242-5 is a slave module only. If you need the S7-1200 to be a DP master you must use the CM 1243-5 (6GK7243-5DX30-0XE0) instead. For the topology in this article the 840D sl remains the master.

Hardware Prerequisites

Confirm the following before starting:

  • SINUMERIK 840D sl NCU (NCU 710.3 PN, NCU 720.3 PN, or NCU 730.3 PN) with running PLC firmware and accessible PROFIBUS port (X126 or X136).
  • SIMATIC S7-1200 CPU, firmware V4.2 or later (recommended V4.5+) so that CM 1242-5 is fully supported in the TIA Portal device catalog.
  • CM 1242-5 communications module. Article number: 6GK7242-5DX30-0XE0 (legacy) or the current release listed in the Siemens Industry Online Support catalog.
  • PROFIBUS cable (purple, twisted pair, shielded) terminated with 9-pin D-sub PROFIBUS connectors.
  • Two PROFIBUS terminating resistors (typically integrated in the connectors, switched ON at the two physical ends of the segment).
  • TIA Portal V15.1 or later installed on the engineering station.
  • SINUMERIK commissioning access: SINUMERIK Operate, HMI Advanced, or the SINUMERIK PCU/NCU toolbox (CFGDEPRO / plcsim and the cross-commissioning tools).

CM 1242-5 Key Specifications

Parameter Value
Article number (legacy) 6GK7242-5DX30-0XE0
Function PROFIBUS DP-V0/V1 slave
Max. baud rate 12 Mbps
Supported DP versions DP-V0, DP-V1
Power supply Via S7-1200 backplane bus (5 V DC)
Current consumption approx. 150 mA (5 V) from backplane
Connector 9-pin D-sub female (PROFIBUS standard)
Configuration TIA Portal, GSD-based
Max. I/O data (DP-V0) 244 bytes input / 244 bytes output per slave
Diagnostic LEDs SF, BF, ON

SINUMERIK 840D sl PROFIBUS Architecture

The 840D sl NCU integrates an S7-300 compatible PLC that communicates with drives, I/O, and HMI via two principal PROFIBUS interfaces located on the NCU housing:

  • X126 (DP/MPI): the primary PROFIBUS DP interface. By default this is the drive bus plus distributed I/O. The pin assignment conforms to PROFIBUS standard RS-485.
  • X136 (MPI/DP): a multipurpose port that defaults to MPI for programming/HMI connection but can be reconfigured as a second PROFIBUS DP master or DP slave segment using the SINUMERIK PLC and NCK configuration tools.

On NCU 730.3 PN variants, additional PROFIBUS-capable slots are populated by CP option modules (for example, CP 5603 / PROFIBUS option boards) that bring up further segments. For NCU 710.3 PN and NCU 720.3 PN, two PROFIBUS interfaces are available (X126 + X136), with X136 the only spare for a new auxiliary network.

Critical warning: Do not parallel two terminators or place them at intermediate nodes. Only the two physical endpoints of the segment may have terminators enabled. On a 9-pin D-sub PROFIBUS connector the terminator is a slide switch labelled ON / OFF; verify it is OFF at every node except the two ends.

PROFIBUS Port Selection on the NCU

Your choice of X126 versus X136 dictates the scope of the integration work:

Port Default Use Reconfigure to DP? Impact on existing bus
X126 PROFIBUS DP (drives + I/O) Already DP, no reconfigure needed Sharing the drive bus — high risk of disturbing motion / drive communication
X136 MPI (HMI / programming) Yes, switchable to DP in PLC/NCK configuration Isolated segment; existing HMI over MPI must be re-routed or replaced by PROFINET

Recommended approach: configure X136 as a DP master and build a new isolated PROFIBUS segment that contains only the new S7-1200 station(s). This keeps the drive bus on X126 untouched and avoids interfering with safety-integrated drive communication.

Topology Diagram

SINUMERIK 840D sl NCU Integrated PLC (DP Master) X126 Drive Bus (existing) X136 DP Master (new) X130/X127 PROFINET X120 Digital I/O SIMATIC S7-1200 (DP Slave) CPU 1215C FW V4.5 CM 1242-5 DP Slave Addr 4 / 1.5 Mbps Term Term PROFIBUS DP segment

GSD File Requirements

The CM 1242-5 is delivered with its GSD file integrated into the TIA Portal device catalog from V14 SP1 onward. If the engineering station cannot locate the device:

  1. Open TIA Portal.
  2. Menu Options → Manage general station description files (GSD).
  3. Browse to the GSD file shipped with the CM 1242-5 (the file is also downloadable from the Siemens Industry Online Support portal — search by article number 6GK7242-5DX30-0XE0).
  4. Install and verify the device appears under Other field devices → PROFIBUS DP → Siemens AG → CM 1242-5.
GSD for the 840D sl: you do not need a GSD for the 840D sl NCU on the S7-1200 side. The NCU is configured as a Siemens master (CPU 317 in the NCU) and recognized automatically by the CM 1242-5 once its PROFIBUS address is set. The 840D sl side does not import the CM 1242-5 as a slave via GSD either when using S7 communication over PROFIBUS — STEP 7 / TIA handles the connection through the standard S7 connection configuration as documented in the Siemens TIA Portal manual — Configuring a PROFIBUS S7 Connection.

Selecting the Correct PROFIBUS Port on the 840D sl

Two questions drive the choice:

  1. Do you need an additional interface module? No hardware option module is required when X136 is configured as DP. The NCU's integrated PROFIBUS interface controller supports both X126 and X136 simultaneously. If both ports must operate as DP masters concurrently and the NCU is a 710.3 variant with limited resources, install a CP 5603 or PROFIBUS option board to gain a third DP segment — but for a single S7-1200 station this is unnecessary.
  2. Can X136 be configured as DP without disturbing the existing network? Yes. X136 is independent of X126 at the bus level. The only side effect is that any device currently using X136 in MPI mode (typically the programming PG and the SINUMERIK HMI over MPI) must be re-routed to PROFINET or to X126 before the change is committed.

Procedure on the 840D sl side

  1. In SINUMERIK Operate → Commissioning → Network → PROFIBUS, switch X136 from MPI to DP Master.
  2. Set the master's PROFIBUS address (commonly 3 for the NCU PLC on the new segment — must differ from any address on X126).
  3. Set the transmission rate (recommended 1.5 Mbps for cabinet-length segments with one slave, up to 12 Mbps for short premium segments).
  4. Compile and load to NCK.
  5. Verify in Menu Select → Diagnostics → Bus → PROFIBUS that the segment shows OK.

TIA Portal Device Configuration

On the S7-1200 side the CM 1242-5 is inserted as a slave to the master represented by the 840D sl NCU's integrated PLC. Use the TIA Portal project structure already present for the loading/unloading station.

Step 1 — Add the CM 1242-5 to the device

  1. Open the S7-1200 station in Device view.
  2. Drag the CM 1242-5 from the catalog onto the left of the CPU (slot 101 or matching slot for the S7-1200 system).
  3. Open the CM 1242-5 Properties.
  4. PROFIBUS address: set to a free address on the new segment (e.g. 4). Must not collide with any 840D sl address.
  5. Transmission rate: set to match the 840D sl configuration (1.5 Mbps in this example).
  6. Highest PROFIBUS address: keep at 126 unless you intentionally use HSA optimisation.

Step 2 — Configure the S7 connection (optional, for S7 communication)

If the goal is bi-directional S7 communication (PUT/GET) rather than pure DP I/O, configure an S7 connection from the S7-1200 side toward the NCU PLC.

  1. Open Devices & Networks.
  2. Select the CM 1242-5 and from the connection list choose S7 connection.
  3. Set the partner to the NCU PLC with the IP-style identifier of its PROFIBUS address (TIA Portal uses PROFIBUS addressing under the Partner field).
  4. Tick Establish an S7 connection; leave the local ID at default; the partner ID is assigned by the NCU project.
  5. For details follow the official Configuring a PROFIBUS S7 Connection procedure.

Step 3 — Map I/O areas (for DP-V0 cyclic exchange)

Open the Device view → CM 1242-5 → Module parameters → I/O addresses. Assign input and output ranges that fit your application; the S7-1200 limits the total to the DP-V0 max of 244 bytes in / 244 bytes out per slave.

Slot Direction Length (example) Address range Purpose
1 Inputs 16 bytes IB 100 ... IB 115 Status from NCU PLC
1 Outputs 16 bytes QB 100 ... QB 115 Commands to NCU PLC
2 Inputs 32 bytes IB 116 ... IB 147 Axis / handshakes
2 Outputs 32 bytes QB 116 ... QB 147 Axis / handshakes

840D sl Commissioning Steps (PLC side)

  1. Open the SINUMERIK PLC project in STEP 7 (matching the NCU PLC version, typically V5.x for the integrated S7-300).
  2. Configure X136 as the new DP master using HW Config: insert a DP master system and define its PROFIBUS parameters.
  3. Add the CM 1242-5 as a DP slave on this master system. Either import the GSD manually in STEP 7 (older toolchains) or browse the catalog.
  4. Match the I/O address layout byte-for-byte to the S7-1200 side so that PUT/GET or DP I/O areas align.
  5. If S7 communication is used, open NetPro → S7 Connection, select the S7-1200 partner, and confirm the partner slot is the CM 1242-5 with the configured PROFIBUS address.
  6. Compile, download to NCU PLC, and perform an NCK reset if required by the PLC program changes.
PLC version mismatch risk: the integrated PLC in the 840D sl is a S7-300 class CPU (CPU 317 family). STEP 7 V5.x is the natural toolchain; TIA Portal can also configure the 840D sl PLC in mixed deployments but requires the SINUMERIK PLC add-on package. Mixing TIA on the S7-1200 and STEP 7 V5.x on the NCU is the most common pattern and is fully supported by Siemens.

S7-1200 PLC Programming for DP Slave I/O

For pure DP-V0 cyclic I/O no special function block is required: the CPU writes the configured output addresses automatically and updates the input addresses once the slave is in data exchange. For S7 communication use the standard PUT/GET blocks.

Example: Reading 16 bytes from the NCU PLC

// Reading 16 bytes from NCU PLC into DB100
// Triggered by a 1 Hz clock bit from the S7-1200 cyclic OB
// "REQ"   := clock_1Hz;
// "ID"    := W#16#1;       // connection ID from TIA connection configuration
// "ADDR_1":= P#DB100.DBX0 BYTE 16; // any pointer to a data area on the S7-1200
// "RD_1"  := P#M100.0 BYTE 16;     // source area on the partner (NCU PLC)
// "DONE"  := done_flag;
// "BUSY"  := busy_flag;
// "ERROR" := error_flag;
// "STATUS":= status_word;
CALL "GET" , DB106;

Example: Writing 16 bytes to the NCU PLC

// Writing 16 bytes to NCU PLC
CALL "PUT" , DB107;
//  REQ   := write_trigger;
//  ID    := W#16#1;
//  ADDR_1:= P#M200.0 BYTE 16;
//  SD_1  := P#DB101.DBX0 BYTE 16;
//  DONE  := done_flag;
//  BUSY  := busy_flag;
//  ERROR := error_flag;
//  STATUS:= status_word;
DB allocation: background DBs for PUT/GET must be created in the S7-1200 project before compiling. The exact ID shown in the call interface is the one assigned by the TIA Portal connection configuration dialog.

Verification and Diagnostics

Verification must be performed on both sides.

S7-1200 side (TIA Portal)

  1. Go online with the S7-1200 station.
  2. Open Online → Diagnostics → Device information on the CM 1242-5.
  3. Confirm: Status = OK, DP state = Data exchange.
  4. Watch the input addresses — values should change when the master toggles its output data.

CM 1242-5 LED indications

LED State Meaning
ON Green Power OK
SF Off No module fault
SF Red Configuration error or diagnostic event pending
BF Off Bus OK, data exchange active
BF Red flashing No communication — check cable, address, baud rate
BF Red steady Physical bus error — termination or wiring

840D sl side (SINUMERIK Operate)

  1. Commissioning → Bus → PROFIBUS → X136.
  2. Verify Bus state OK and Slaves connected = 1 (the CM 1242-5).
  3. Open Diagnostics → PLC → Status and confirm the connection state to the partner is established.
  4. Force a single bit on the S7-1200 and watch it appear in the NCU PLC input image to prove end-to-end data flow.

Troubleshooting Matrix

Symptom Likely cause Action
BF LED steady red on CM 1242-5 Cable break, no termination, short circuit Check PROFIBUS connector pin-out (3 = B, 8 = A); verify terminator ON at both ends only
BF LED flashing red Address or baud-rate mismatch Compare CM 1242-5 PROFIBUS address vs. 840D sl X136 configuration; ensure both sides use identical baud rate
SF LED red, BF off Configuration mismatch (slot count, I/O length) Reconcile I/O mapping between STEP 7 NCU PLC project and TIA Portal CM 1242-5 configuration
S7 connection error STATUS = 0x0001 Partner not reachable Verify the NCU PLC project has loaded an S7 connection to the S7-1200; check rack/slot for the CM 1242-5 (slot 101 of S7-1200)
S7 connection error STATUS = 0x000A Resource problem on partner Reduce the number of simultaneously active S7 connections on the NCU PLC
Data exchange but values stuck Byte order / endian mismatch Use SWAP block on the S7-1200 side, or align Word/DWord boundaries in DBs
Intermittent dropouts EMI, missing shield bonding, terminator at intermediate node Verify shield bonded at both connector shells to cabinet ground; re-check termination positions
NCU PLC compile rejects the new DP master X136 already used as MPI by HMI Re-route the HMI to PROFINET (X130/X127) before reconfiguring X136 to DP

Field-Proven Tips

  • Set the NCU PLC PROFIBUS address on X136 to a value that does not conflict with any X126 node — keep a written record in the cabinet drawing.
  • Document the baud rate on the cabinet label: it is the most common source of communication failure after physical wiring.
  • Reserve at least 10 % spare CPU load on the NCU PLC for the new communication load; DP masters consume noticeable scan time when many slaves are attached.
  • For long segments (above 100 m), use 12 Mbps only on short premium cable; otherwise default to 1.5 Mbps or 500 kbps for robustness.
  • When migrating in stages, commission the new segment with the S7-1200 alone (no other slaves) to isolate faults to that station.

Do I need a GSD file from the 840D sl for the S7-1200 configuration?

No. The CM 1242-5 only requires its own Siemens GSD file (already present in TIA Portal V14 SP1 and later). The 840D sl integrated PLC is a S7-300 master and is configured natively in STEP 7 or TIA Portal — no GSD import from the NCU is needed.

Can I use X136 instead of X126 so I do not touch the existing drive bus?

Yes. X136 can be reconfigured from MPI to DP master in the SINUMERIK commissioning menus. The existing X126 drive bus remains untouched. Re-route any HMI currently on X136 to PROFINET (X130/X127) before switching X136 to DP.

What is the part number of the CM 1242-5 module?

The legacy article number is 6GK7242-5DX30-0XE0. Always confirm the current revision in the Siemens Industry Online Support catalog before ordering because mid-life updates change the suffix.

Can the S7-1200 act as a PROFIBUS master in this setup?

No — the CM 1242-5 is a DP slave only. To make the S7-1200 the master you must replace it with the CM 1243-5 (6GK7243-5DX30-0XE0). In the topology described here the 840D sl NCU remains the master.

Which baud rate should I use on the new segment?

1.5 Mbps is the safest default for cabinet and short field segments with one or two slaves. 12 Mbps is reserved for very short, well-terminated segments with premium cable. Always set the same baud rate on the CM 1242-5 in TIA Portal and on X136 in the SINUMERIK configuration.