1. Overview: Profibus to IEC 104/61850 Conversion on S7-400 Systems
Industrial substations and process plants that historically relied on PROFIBUS field networks must often expose their data to external SCADA, EMS (Energy Management Systems), or DMS (Distribution Management Systems) using the IEC 60870-5-104 (commonly called IEC 104) telecontrol protocol or the IEC 61850 substation communication standard. A typical scenario involves a Siemens S7-400H redundant station (CPU 414-4H with CP 443-1 Ethernet communications processor) wired in a ring topology that must publish its process image, alarms, and measurands to a third-party control center speaking IEC 104 over TCP/IP.
Direct conversion inside the PLC firmware is not possible with stock S7-400 firmware. The standard, manufacturer-supported approach is to deploy a protocol gateway — most commonly SICAM PAS (Siemens Power Automation System) — that sits between the S7-400 station and the IEC 104/IEC 61850 network. The gateway runs on a Windows server, reads the S7 process image using S7 OPC or SIMATIC NET Softnet with a CP 1613/CP 1623, and republishes the values on the IEC 104 / IEC 61850 side.
2. Protocol Stack Fundamentals
2.1 PROFIBUS DP / S7 Communication
PROFIBUS DP is a master/slave fieldbus running on RS-485 (copper) or fiber optics at rates from 9.6 kbit/s to 12 Mbit/s. The S7-400H station typically integrates PROFIBUS DP via the CP 443-5 Extended module. The CP 443-1 (Ethernet) provides the upstream LAN connection for OPC/Softnet and for IEC 104 traffic.
2.2 IEC 60870-5-104
IEC 60870-5-104 is the network-access layer variant of the IEC 60870-5 series, running over TCP/IP (default port 2404). It uses a balanced/unbalanced client-server model. The gateway is the controlled station (server); the upstream control center is the controlling station (client). ASDUs carry M_SP_NA_1 (single-point information), M_DP_NA_1 (double-point), M_ME_NC_1 (measured value, short floating point), and M_IT_NA_1 (integrated totals). Refer to IEC 60870-5-104:2016 (Webstore).
2.3 IEC 61850
IEC 61850 is the international standard for substation communication (IEC 61850-1:2013). Data is structured as Logical Devices (LD) → Logical Nodes (LN) → Data Objects (DO) → Data Attributes (DA). Engineering is done with SCL (Substation Configuration Language) files; the gateway's IEC 61850 server uses the SCL ICD/SSD file describing the IED.
3. Required Hardware and Software
| Item | Catalog Number / Designation | Role |
|---|---|---|
| S7-400H CPU | 6ES7 414-4HM14-0AB0 (CPU 414-4H, firmware V6.0 or V7.x) | Redundant controller; PROFIBUS DP master via CP 443-5 |
| Ethernet CP | 6GK7 443-1EX30-0XE0 (CP 443-1, 4 ports, ISO/TCP, S7 communication) | Upstream LAN to engineering station and gateway |
| PROFIBUS CP | 6GK7 443-5DX05-0XE0 (CP 443-5 Extended) | PROFIBUS DP fieldbus |
| PC CP for S7 connection | 6GK1 161-3AA01 (CP 1613) or 6GK1 162-3AA00 (CP 1623) | Hard-link to gateway server for SIMATIC NET Softnet |
| Gateway software | SICAM PAS V8.xx with option IEC 60870-5-104 and IEC 61850 | Protocol conversion engine |
| SIMATIC NET | SIMATIC NET Softnet-S7 (V13 or later) | S7 OPC server running on the gateway PC |
| PCS 7 (optional) | SIMATIC PCS 7 V9.0 SPx | Used when gateway functions are split between AS and OS |
4. Reference Architecture: SICAM PAS Gateway in Ring Topology
The S7-400H station and the SICAM PAS gateway are deployed in a redundant ring — typically MRP (Media Redundancy Protocol) with SCALANCE XC-200/XB-200 managed switches, or HRP (High-availability Seamless Redundancy) when using SCALANCE XR-300. The CP 443-1's four-port switch (EX30) can also be used in stand-alone ring configurations. The IEC 104 control center sits on a separate upstream network segment reached via a router or firewall.
Engineering and runtime traffic: PROFIBUS DP at 1.5 Mbit/s carries process data from the CP 443-5 to the I/O. The CP 443-1 publishes S7 variables to the SICAM PAS OPC server over ISO-on-TCP (port 102). The OPC tags are mapped 1:1 to IEC 104 information objects and to IEC 61850 data objects.
5. Alternative Path: S7-400 / PCS 7 with Added Software Packages
When a separate Windows gateway is undesirable, the conversion logic can be embedded in the S7-400 itself using:
- SIMATIC PCS 7 with the SIMATIC PCS 7 TeleControl option package and the IEC 60870-5-104 master/slave blocks (FB TELECONTROL_104). This requires PCS 7 V9.0 or later and a CP 1243-1 / CP 1542SP-1 for ET200 stations; the S7-400 uses CP 443-1 plus PCS 7 add-on.
- SIMATIC S7-400 + AddOn IEC 61850 via the S7-400 IED configured with SICAM SCC or third-party IED configurators. The CPU 414-4H cannot run the IEC 61850 stack directly; a sub-station controller (RTU 8x70, SICAM A8000) is required.
For the topology described (ring of S7-400H with a single IEC 104 control center), the SICAM PAS gateway is the lowest-risk path. It keeps the S7 firmware stock, decouples protocol changes from PLC code, and supports both IEC 104 and IEC 61850 from one platform.
6. CP 443-1 Configuration for the Gateway
6.1 STEP 7 / TIA Settings
Open the CP 443-1 properties in HW Config (STEP 7 V5.6) or in the device configuration (TIA Portal V17) and assign the following parameters:
| Parameter | Value | Comment |
|---|---|---|
| IP address | 192.168.10.1 (CPU A) / 192.168.10.2 (CPU B) | Station segment; same subnet as the gateway |
| Subnet mask | 255.255.255.0 | — |
| Router address | 192.168.10.254 | For cross-segment IEC 104 access |
| S7 communication | Enabled, port 102 ISO-on-TCP | Needed by SIMATIC NET Softnet |
| OP/PG access | Enabled | Engineering access |
| Time-of-day synchronization | NTP, 192.168.10.50 | Gateway acts as NTP source |
| Connection resources | ≥ 8 OP connections + 4 S7 connections | Reserve for OPC browse, alarms, and S7-Redundancy |
7. SICAM PAS Engineering Workflow
7.1 Step 1 — Install and License
- Install SICAM PAS V8.20 (or current release) on a Windows Server 2019 / 2022 machine. ISO 27001 hardening is recommended for control-center facing deployments.
- Apply the license key for: SICAM PAS Core, IEC 60870-5-104 Server, IEC 61850 Server, S7 OPC Client.
- Install SIMATIC NET PC software V17 with Softnet-S7 Lean/Standard. The CP 1613 / CP 1623 driver binds the S7 protocol to the dedicated NIC.
7.2 Step 2 — Build the S7 OPC Project
- Launch SICAM PAS Manager → Project → New. Add an S7 OPC channel.
- Configure the S7 connection to CPU 414-4H: rack 0, slot 3 (CPU), MPI/PROFIBUS or ISO-on-TCP. Use S7 HMI connection for redundancy.
- Browse the S7 symbol table or import the STEP 7 project export (XML via SIMATIC Manager → Options → Export to Other Tools). Each DB bit/word is exposed as an OPC item, e.g.
S7:[S7-400H_CPU414]DB100,BYTE0.
7.3 Step 3 — Map OPC Items to IEC 104 Information Objects
Open SICAM PAS IEC 104 Editor and create the data points. Example mapping table:
| OPC Item (S7 source) | IEC 104 ASDU Type | IOA (hex) | Direction |
|---|---|---|---|
| S7:DB100,DBX0.0 — Circuit breaker position | M_DP_NA_1 (type 3) | 0x0001 | Monitor (uplink) |
| S7:DB100,DBX0.1 — Protection trip | M_SP_NA_1 (type 1) | 0x0002 | Monitor |
| S7:DB100,DBW2 — Line voltage L1, kV | M_ME_NC_1 (type 13, float32) | 0x0010 | Monitor |
| S7:DB100,DBW4 — Active power, MW | M_ME_NC_1 (type 13, float32) | 0x0011 | Monitor |
| S7:DB100,DBD6 — Energy total, MWh | M_IT_NA_1 (type 15) | 0x0020 | Monitor |
| S7:DB200,DBW0 — Setpoint raise/lower | C_SE_NC_1 (type 50, float32) | 0x0100 | Command (downlink) |
Configure IEC 104 common address (CA), link address, originator address, and a Scan Period of 1000 ms for measurands and 200 ms for status. Enable General Interrogation (GI) on startup so the control center receives the full process image after connection establishment.
8. IEC 61850 Server Modeling
For the IEC 61850 server, define an SCD/ICD file with one Logical Device per CPU. Logical Nodes mirror the data model:
<LDevice inst="LD_A">
<LNode lnClass="LLN0" inst="">
<DO name="Mod" type="OPC_OpSt/OpSt_t/>
<DO name="Beh" type="ENS/>
</LNode>
<LNode lnClass="XCBR" inst="1">
<DO name="Pos" type="DPC/> <!-- from DB100.DBX0.0 -->
</LNode>
<LNode lnClass="MMXU" inst="1">
<DO name="TotW" type="MV/> <!-- from DB100.DBD6 -->
<DO name="PhV" type="WYE/> <!-- A/B/C phase -->
</LNode>
<LNode lnClass="PIOC" inst="1">
<DO name="Str" type="ACT/> <!-- from DB100.DBX0.1 -->
</LNode>
</LDevice>
Upload the ICD to SICAM PAS, bind each Data Object to the OPC item using the IEC 61850 Binding Editor, and enable MMS over TCP (default port 102) or dedicated port 102 for IEC 61850. Bind DAItems with FCDA references.
9. Ring Topology and High-Availability Settings
9.1 MRP (preferred for IEC 104/61850 LAN)
- Configure one SCALANCE switch as MRP manager and all others as MRP clients in the Web-Based Management interface.
- Set the Reconfiguration time to < 200 ms. SCALANCE XC-200 defaults to ~50 ms; verify in the log.
- Connect CP 443-1 ports in the ring only if MRP is enabled on the CP 443-1 EX30 firmware ≥ V3.x. Otherwise keep the CP 443-1 in star.
9.2 HRP (when the gateway is also redundant)
Use HRP if the SICAM PAS node is a fault-tolerant pair with two network adapters. HRP supports seamless reconfiguration (< 300 ms) and is the recommended redundancy for the IEC 104 LAN in transmission substations.
10. Data Throughput and Timing Considerations
| Parameter | Typical Value | Notes |
|---|---|---|
| S7 OPC read cycle (status) | 500 ms | Configure per group |
| S7 OPC read cycle (analog) | 1000 ms | — |
| IEC 104 t1 (send/receive ack timeout) | 15 s | Default per IEC 60870-5-104 |
| IEC 104 t2 (ack of unnumbered) | 10 s | — |
| IEC 104 t3 (test frame period) | 20 s | — |
| IEC 104 k (max unacked APDUs) | 12 | — |
| IEC 104 w (latest ack after k frames) | 8 | — |
| MMS report scan | 1000–2000 ms | Match control center requirements |
End-to-end latency for one measurand: S7 acquisition (≤ cycle time) + OPC read (cycle / 2) + IEC 104 ASDU build (≤ 50 ms) + LAN delay. Typical total: 600 ms – 1.5 s for cyclic measurands on a healthy ring.
11. Commissioning and Verification
-
Step 1 — S7 reachability. From the gateway PC, run
ping 192.168.10.1andping 192.168.10.2. Open SIMATIC NET Diagnostics and confirm both CPUs visible. -
Step 2 — OPC browse. Use SICAM PAS OPC Test Client to browse the S7 server. Verify a known value, e.g.
DB100.DBW2for line voltage, returns the expected raw value. - Step 3 — IEC 104 connection. From a control-center simulator (e.g. PCM600 / ITT600), initiate a TCP connection to port 2404 of the gateway. The log should show STARTDT act / con exchange within 15 s.
- Step 4 — General Interrogation. Trigger Interrogation GI (cause of transmission = 20). The gateway must respond with all configured data points using the configured ASDU types.
- Step 5 — Spontaneous events. Force a status change in the S7 program; verify an M_SP_NA_1 with cause 3 (spontaneous) arrives at the control center within 1 s.
- Step 6 — IEC 61850 MMS association. Use IEC 61850 client (e.g. Siemens SICAM SCC) to associate. Browse the data model; verify all logical nodes and the live values.
- Step 7 — Failover test. Power down CPU A. Verify the OPC connection fails over to CPU B in < 1 s and that no GI / data is lost on the IEC 104 channel.
- Step 8 — Ring break test. Disconnect one ring cable. Confirm MRP reconfiguration completes (LEDs on SCALANCE) and IEC 104 reports STARTDT remains connected.
12. Troubleshooting Matrix
| Symptom | Likely Root Cause | Diagnostic Step | Fix |
|---|---|---|---|
| OPC tags show BAD_QUALITY | S7 connection resource exhausted on CP 443-1 | Check CP diagnostic buffer in STEP 7 | Increase OP connection resources, reload CP |
| IEC 104 control center sees STARTDT act but no con | Firewall on gateway PC blocking port 2404 |
netstat -an | findstr 2404 on Windows; telnet from remote |
Open Windows firewall rule for inbound TCP 2404 |
| GI returns only 1 data point | Cause-of-transmission bit masked or object address duplicate | IEC 104 server log | Re-verify IOA uniqueness in the 104 point list |
| MMS association aborts after a few seconds | Time sync out of tolerance (> 1 s) | Check ACSE Authentication log | Configure NTP and ensure time sync ≤ 500 ms |
| CPU B does not take over data after CPU A failure | OPC client not configured for S7 H connection | Check SIMATIC NET S7 Helper configuration | Switch OPC connection to HMI S7 Connection |
| Ring break brings down IEC 104 for > 1 s | MRP not enabled on all switches | SCALANCE WBM: Information → Redundancy → MRP | Assign one manager, all others clients |
| Measurand value freezes at last good value | OPC subscription lost | SICAM PAS Log Viewer → OPC errors | Reduce subscription count, raise keep-alive |
| IEC 104 t1 timeout in control center | LAN congestion or gateway CPU overload | Check Performance Monitor on gateway | Raise t1 to 20–30 s in negotiation; tune scan groups |
13. Security and Hardening Checklist
- Place the gateway on a DMZ between the S7 LAN and the IEC 104 WAN; restrict source IP in the firewall.
- Use IEC 62351-3 for TLS-secured IEC 104 channels where supported by the control center (SICAM PAS supports TLS 1.2 for IEC 104 in V8.20+).
- Disable unused S7 ports on the CP 443-1 (S7, FETCH/WRITE) once OPC is stable.
- Restrict Windows RDP access to the gateway to a maintenance VLAN.
- Enable logging to a central SIEM; configure NTP from a trusted source.
- Patch the gateway OS quarterly and follow Siemens ProductCERT advisories.
14. Long-Term Operation Notes
During operation, monitor:
- OPC subscription quality and resync count.
- IEC 104 message rate (control center typically expects stable throughput; spikes indicate bursts).
- MRP reconfiguration counters on SCALANCE switches.
- Gateway host CPU and RAM (PAS is single-threaded; OPC + 104 + 61850 typically needs < 4 GB RAM and one core).
Plan for firmware updates: CP 443-1 EX30 firmware V3.0.28 or later is recommended for stability with the OPC bridge; check the latest release in Siemens Support entry 109749628. SICAM PAS follows a yearly release cadence; track SICAM PAS release notes.
What is the simplest way to expose S7-400 PROFIBUS data as IEC 104?
Install SICAM PAS on a Windows server, connect to the S7-400 via SIMATIC NET Softnet (CP 1613 or CP 1623), map the S7 OPC tags to IEC 104 information objects (ASDU types 1, 3, 13, 15, etc.), and open TCP port 2404 to the upstream control center. The S7-400 acts as a data source only; the gateway runs the IEC 104 server.
Can the S7-400 CPU 414-4H run an IEC 104 server natively?
No. The CPU 414-4H firmware does not include an IEC 60870-5-104 server task. For embedded IEC 104, use a dedicated substation controller (e.g., SICAM A8000) or the SIMATIC PCS 7 TeleControl add-on. For mixed IEC 104 and IEC 61850 with a single engineering base, SICAM PAS is the standard Siemens path.
How is redundancy handled on the S7-400H side?
Configure the OPC connection in SIMATIC NET as an S7 HMI connection pointing to both CPUs. The OPC server fails over automatically within ~500 ms when the active CPU changes. Verify with a power-down test on the primary CPU and check that the IEC 104 channel stays connected without triggering GI.
Which default TCP port does IEC 104 use?
IEC 60870-5-104 uses TCP port 2404 by default. The protocol stacks exchange STARTDT/STOPDT act/con and monitor frames (test APDU with ASDU 100) every t3 seconds. Configure t1 = 15 s, t2 = 10 s, t3 = 20 s, k = 12, w = 8 unless the control center requires different values.
What cabling or topology changes are needed for a ring?
Use SCALANCE XC-200/XB-200 managed switches. Designate one as MRP manager, the rest as MRP clients. The CP 443-1 EX30 can sit on the ring if MRP is enabled on the CP firmware. Reconfiguration time is < 200 ms, which is fast enough to keep IEC 104 sessions alive because t1 is 15 s by default.