Configuring Pumpsmart for Sensorless Pump Control Systems

Mark Townsend6 min read
Other ManufacturerProcess ControlTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

On the panel, you see motor speed and current but no pressure or flow signal. That is not automatically a fault: Pumpsmart can use configured pump data and motor-loading information to infer an operating point. Treat the result as a calculated estimate, not as an independent measurement of pressure or flow.

Read the symptoms before changing the control

Start here. Identify which values come from physical transmitters and which values the controller calculates. A displayed flow or pressure value can look like an instrument reading even when no corresponding sensor exists.

Panel symptom Likely cause or meaning
Speed and current change, but calculated flow does not respond logically Incorrect pump data, wrong speed reference, invalid current scaling, or operation outside the fitted pump map
Calculated flow is close at the design point but wrong at low flow The model fits the design condition but does not represent the shut-off region or actual installed pump
Estimate shifts after a fluid or process change Density, viscosity, valve position, recirculation, wear, or another hydraulic condition changed the relationship between load and flow
Speed is stable while current oscillates Process instability, electrical measurement noise, mechanical load variation, or drive-control interaction
Calculated pressure or flow looks stable during a blocked or abnormal condition The estimator has no independent process measurement with which to detect the mismatch

Check the drive's actual speed and current feedback first. Bad feedback makes every later adjustment meaningless. PID tuning, curve-point trimming, and control-mode changes waste time until those two signals are credible.

Understand what the estimator calculates

A sensorless pump controller does not create pressure or flow information from nothing. It combines a pump model with measured motor behavior. The configured anchors described for Pumpsmart are design flow, power at design condition, power at shut-off condition, and speed.

For a centrifugal pump operating with the same impeller and a fluid whose behavior remains comparable, the affinity relationships provide the speed correction:

  • Q2 = Q1 × (N2 / N1)
  • H2 = H1 × (N2 / N1)^2
  • P2 = P1 × (N2 / N1)^3

These relationships scale a known operating condition; they do not identify the operating point by themselves. The power anchors add information about where the pump lies between shut-off and the design condition. The controller can fit or reference a relationship between pump power and flow, correct it for speed, and compare it with the observed motor load.

Motor current is only a load indicator. Electrical input power also depends on voltage, power factor, and motor efficiency. Drive-reported current can therefore move without a proportional change in shaft power. The controller's internal motor and drive model must account for that relationship if it uses current to estimate hydraulic power.

Confirm the model inputs

Use data for the installed pump, impeller, motor, and fluid condition. A curve from a similar pump is not a substitute. Small model errors can become large flow errors where the power-versus-flow relationship is flat.

  • Confirm that design flow describes the intended pump operating point, not total plant flow or the combined output of parallel pumps.
  • Confirm that power at design condition uses the power basis expected by the controller. Do not interchange hydraulic power, pump shaft power, motor output power, and drive input power.
  • Confirm that power at shut-off condition represents the same pump configuration and speed as the design data.
  • Confirm that speed uses the controller's required units and reference basis.
  • Check current scaling against the drive or an appropriate electrical measurement. A percentage value entered as engineering units will corrupt the estimate.
  • Check the fluid against the condition used for the pump data. Density and viscosity changes alter absorbed power and invalidate a fixed calibration.

If the power basis is unclear, trace it from the pump curve or test sheet to the controller entry. Do not force the calculated result to match by altering a known-good flow value.

Configure and commission the control

  1. Record the existing configuration. Capture every pump-model input, motor setting, speed limit, control setpoint, and displayed feedback value before editing.
  2. Validate the feedback chain. Compare commanded speed with actual speed. Compare displayed current with the drive's measured current at more than one load condition.
  3. Enter the pump anchors. Load design flow, power at design condition, power at shut-off condition, and speed from one consistent pump dataset.
  4. Check unit consistency. Match flow, power, and speed units to the configuration fields. Verify decimal placement and any scaling applied between the drive and controller.
  5. Run near the design condition. Stabilize the process, record speed and current, and compare the calculated operating point with a temporary or installed reference measurement.
  6. Move through the permitted operating range. Test several stable points from lower flow toward the normal upper range. Do not use a closed discharge valve as a routine calibration method unless the pump procedure specifically allows that test.
  7. Enable automatic control only after validation. Apply conservative output limits and watch for hunting, saturation, or implausible calculated values.

Do not tune the loop around a bad estimator. Aggressive tuning may hide a steady-state error at one point while producing unstable operation elsewhere.

Verify the estimate independently

Use an independent pressure or flow reference during commissioning. A temporary calibrated instrument is enough if it covers the required operating range and installation conditions.

  • Record reference flow or pressure, calculated value, actual speed, motor current, and process state at each stable point.
  • Calculate signed error as estimated value − reference value.
  • Calculate percent error only against a nonzero reference: 100 × (estimated − reference) / reference.
  • Compare the error with the application's acceptance band. Use the required control accuracy and protective function, not an invented universal tolerance.
  • Repeat a previous point after moving through the range. Failure to return to the earlier estimate indicates hysteresis, changing hydraulics, thermal effects, or unstable feedback.

Test abnormal states separately. A valid estimate during normal operation does not prove detection of loss of prime, blocked suction, recirculation, cavitation, mechanical damage, or a changed fluid. Where those conditions can damage equipment or create a process hazard, use independent protective instrumentation.

Avoid recurring sensorless-control mistakes

Do not confuse inference with measurement. Two different hydraulic states can produce similar motor loading, particularly near flat portions of a pump curve or after system resistance changes.

  • Do not copy pump data between different impellers or modified pumps.
  • Do not use motor nameplate power as power at design condition unless the configuration instructions explicitly define that field that way.
  • Do not assume current is shaft power. Check the drive's measurement definitions and motor model.
  • Do not calibrate one point and declare the full range valid. Check low, normal, and upper operating regions.
  • Do not rely on the inferred value as the sole safety trip where failure can damage the pump or process.
  • Do not ignore wear. Impeller erosion, clearance changes, deposits, and recirculation can move the real pump away from its configured model.

Revalidate after pump repair, impeller change, motor replacement, drive replacement, fluid change, or a material piping modification. These changes alter either the hydraulic map or the conversion between current and shaft load.

FAQ

Can I control a pump without a pressure or flow transmitter?

Yes, if the process can tolerate a model-derived operating value. Pumpsmart uses pump characteristics with speed and current information, but independent instrumentation remains necessary where direct measurement or protective coverage is required.

Does motor current directly indicate pump flow?

No. Current reflects electrical loading and is affected by voltage, power factor, motor efficiency, and drive operation. The controller must combine it with the pump model and speed to estimate flow.

Can I use motor nameplate power for the design-power entry?

Only when the configuration documentation defines power at design condition as that exact quantity. Otherwise, obtain the required hydraulic, shaft, motor-output, or electrical-input power from the matching pump and motor data.

Does sensorless pump control replace protective instruments?

No. Stop commissioning when speed or current feedback cannot be validated, the estimator remains outside the application's acceptance band, or abnormal states cannot be distinguished safely. Escalate to official Pumpsmart or Goulds support with the saved configuration, pump data, drive data, and measured test points.

Back to blog