Overview
The S7-200 CPU family does not expose a native PROFIBUS interface. To exchange cyclic process data with a PROFIBUS DP master such as an S7-300 CPU 317-2DP, the S7-200 must be expanded with the EM 277 PROFIBUS-DP slave module. The EM 277 attaches to the right side of the S7-200 CPU and behaves as a DP-V0 slave, advertising its I/O through the standard Siemens GSD file SIEM081D.GSD. The S7-300 master maps the slave's inputs and outputs into its own process image or peripheral area, and the S7-200 user program reads/writes those locations in the V-memory area using a configuration data block generated by the STEP 7 Micro/WIN PROFIBUS wizard.
This article walks through the full commissioning path:
- EM 277 mechanical installation and rotary address selection.
- GSD file import into STEP 7 (classic or TIA Portal).
- Master-side hardware configuration of the EM 277 DP slave.
- Micro/WIN PROFIBUS wizard configuration on the S7-200 side.
- Byte-aligned I/O mapping rules and bit extraction in user code.
- Resolution of the "Invalid parameter was specified in configuration information" error reported by the Micro/WIN wizard.
- Online verification with status tables, watch tables, and LED diagnostics.
Hardware Prerequisites
| Component | Typical Order Number | Role | Notes |
|---|---|---|---|
| S7-300 CPU 317-2DP | 6ES7317-2AK14-0AB0 | DP-V1 master, second PROFIBUS interface | DP master port on X2; MPI/DP on X1 reserved for programming |
| S7-300 backplane and PS 307 | 6ES7307-1EA01-0AA0 | Mounting and 24 V supply | Minimum PS 2 A for CPU 317 plus I/O |
| S7-200 CPU 226 | 6ES7216-2BD23-0XB0 (AC/DC/RLY) | DP slave controller | 24 inputs / 16 outputs onboard; no native PROFIBUS |
| EM 277 PROFIBUS-DP slave | 6ES7277-0AA22-0XA0 | PROFIBUS interface | Right-side expansion module |
| PROFIBUS cable (FC, violet) | 6XV1830-0EH10 | Segment media | Shielded twisted pair, characteristic impedance 150 Ω |
| PROFIBUS D-sub connector with PG port | 6ES7972-0BB12-0XA0 | Bus termination and diagnostics tap | Switch termination ON at end nodes only |
| STEP 7 V5.5 + SP (classic) | 6ES7810-4CC10-0YA5 | Master engineering | TIA Portal V13+ accepts the same GSD |
| STEP 7 Micro/WIN V4.0 SP9 | 6ES7810-2BS03-0YX0 | Slave engineering | Final released service pack for the S7-200 |
Reference manuals for the components above are published on the Siemens Industry Online Support portal:
- SIMATIC S7-200 EM 277 PROFIBUS-DP Module Manual
- SIMATIC S7-200 Programmable Controller System Manual
- SIMATIC S7-300 CPU 317-2DP Device Manual
- Siemens FAQ 2615830 - Communicating data between S7-200 and S7-300 via PROFIBUS DP
EM 277 Mechanical and Address Setup
The EM 277 mounts on the right side of the CPU 226 and locks in place with the captive thumb screw on top. It draws 24 V DC from the S7-200 base unit's expansion bus; no separate power supply is required for the module itself, although the PROFIBUS connector shell must be tied to a low-impedance ground through the D-sub backshell to maintain shield continuity.
Rotary Address Switches
Two rotary switches on the front of the EM 277 set the PROFIBUS node address. The high-order switch is the tens digit (x10) and the low-order switch is the units digit (x1). Valid range is 1 through 99; address 0 is reserved and addresses > 99 are not supported by the rotary inputs. The address must:
- Be unique on the PROFIBUS segment.
- Match the address assigned to the EM 277 in STEP 7 hardware configuration.
- Match the address declared in the Micro/WIN PROFIBUS wizard.
Address changes take effect only after a power cycle of the S7-200 + EM 277 stack. A change made online will not be picked up by the master until the slave re-initializes.
PROFIBUS Connector and Termination
Use a 9-pin D-sub PROFIBUS connector with integrated termination resistor (e.g., 6ES7972-0BB12-0XA0). The EM 277 does not supply terminator power; if the segment ends at the EM 277, the on-connector termination switch must be set to ON. If the segment continues, leave termination OFF. Always leave terminator power ON at the CPU 317-2DP end of the segment as well so both ends of the segment are terminated.
Baud Rate
The EM 277 auto-detects baud rate during DP parameterization. Supported rates range from 9.6 kbps to 12 Mbps. For a single-slave segment between the CPU 317-2DP and one CPU 226 + EM 277, a 1.5 Mbps profile provides ample bandwidth and tolerates a 200 m segment. Maximum segment lengths per EN 50170:
| Baud Rate | Max Segment Length (m) |
|---|---|
| 9.6 / 19.2 / 45.45 / 93.75 kbps | 1200 |
| 187.5 kbps | 1000 |
| 500 kbps | 400 |
| 1.5 Mbps | 200 |
| 3 / 6 / 12 Mbps | 100 |
GSD File Import in STEP 7
The EM 277 is integrated into STEP 7 through its GSD file, SIEM081D.GSD, plus the bitmap file SIEM081D.BMP. Both files ship with STEP 7 Micro/WIN under C:\Program Files\Siemens\Automation\Microwin\GSD or can be obtained from the Siemens Industry Online Support page for the EM 277. A direct summary of how the data block is laid out and what parameters are exposed to the master is given in Siemens FAQ 2615830 - "How can you communicate data between the S7-200 and the S7-300 via PROFIBUS DP?".
To install in STEP 7 V5.x:
- Launch HW Config.
- Open Options > Install GSD File....
- Browse to the directory containing
SIEM081D.GSDand confirm. - Restart HW Config if the EM 277 does not appear under PROFIBUS DP > Additional Field Devices > I/O > SIMATIC > EM 277 PROFIBUS-DP Slave.
For TIA Portal V13 and later, the same GSD file is supported via Options > Manage general station description files (GSD). The EM 277 then appears in the hardware catalog under Other field devices > PROFIBUS DP > I/O > SIMATIC > EM 277.
SIEM081D.GSD exist. Use the revision that matches the EM 277 firmware. The EM 277 front-panel label states the hardware version (e.g., "ES 02") and the firmware version ("FW Vx.x"). A mismatch between GSD revision and firmware can cause the slave to refuse parameterization without showing a useful diagnostic.STEP 7 Master Hardware Configuration (S7-300 Side)
Insert the EM 277
- In HW Config, drag the EM 277 from the catalog onto the PROFIBUS DP master system that corresponds to the CPU 317-2DP's DP port (X2).
- Assign the same PROFIBUS address as set on the EM 277 rotary switches.
- Open the EM 277 slot configuration (double-click the slot table). The EM 277 exposes one configurable slot with selectable I/O sizes as listed below.
| Slot | Selection | Bytes | Peripheral Address (PI/PQ range example) |
|---|---|---|---|
| 1 | 8 Bytes In / 8 Bytes Out (default) | 8 in, 8 out | PI 0..7 / PQ 0..7 |
| 2 | 16 Bytes In / 16 Bytes Out | 16 in, 16 out | PI 8..23 / PQ 8..23 |
| 3 | 32 Bytes In / 32 Bytes Out | 32 in, 32 out | PI 24..55 / PQ 24..55 |
| 4 | 64 Bytes In / 64 Bytes Out | 64 in, 64 out | PI 56..119 / PQ 56..119 |
The maximum total throughput of the EM 277 is 244 bytes of inputs and 244 bytes of outputs, but in practice the master's slot configuration must match the wizard configuration byte-for-byte. Most installations use either 8 or 16 bytes in each direction; the 32/64 byte profiles are reserved for high-throughput data concentrators.
Compile and Download
Save the configuration back to the S7-300 station and download the hardware configuration. The CPU 317-2DP will start the DP parameterization of the EM 277 as soon as the master enters RUN. If the EM 277 BF LED begins flashing immediately after download, see the troubleshooting matrix below before assuming a cable fault.
Micro/WIN PROFIBUS Wizard (S7-200 Side)
The Micro/WIN PROFIBUS wizard generates a configuration data block (typically DB1) that the EM 277 reads on power-up. This data block must agree with the STEP 7 master configuration in three fields:
- PROFIBUS node address.
- Total input bytes (sum of all configured input slots).
- Total output bytes (sum of all configured output slots).
To run the wizard:
- Open the S7-200 project in STEP 7 Micro/WIN.
- Select Tools > PROFIBUS Wizard.... (In Micro/WIN V4.0 SP9 the wizard is titled simply "PROFIBUS".)
- Set the EM 277 node address to match the rotary switches and the STEP 7 master project.
- Select the I/O profile (e.g., 8 bytes in / 8 bytes out) to match the STEP 7 slot configuration.
- Allow the wizard to generate the configuration subroutine (typically a SBR_x sub called from the main scan cycle).
- Compile and download the program to the CPU 226 over PPI/MPI/USB-PPI.
Byte Alignment and Bit Packing
PROFIBUS DP exchanges I/O at byte granularity. The minimum transferable unit is one byte (8 bits). It is not possible to map a single bit such as V100.0 or Q0.1 across the bus. A frequent configuration mistake is to assign:
-
V100.0←I0.0(master input bit). -
Q0.1→Q4.5(master output bit).
The Micro/WIN wizard will reject this with the same "Invalid parameter was specified in configuration information" error if the underlying data block expects bit-level exchange. Always transfer whole bytes and extract bits in user code.
Correct Byte Mapping
Instead of mapping V100.0 ← Q0.1, map:
-
Output (master → slave):
VB100←QB0(entire byte). -
Input (slave → master):
IB0→VB200(entire byte).
To bring Q0.1 from the master to a specific bit in the slave program, write:
// Network 1 - unpack bit Q0.1 (master) into V100.1 (slave)
LD SM0.0
MOVB VB100, VB300 // copy the master output byte
// User logic can now reference V300.1 as the desired bit
Conversely, to send bit V100.0 to the master:
// Network 1 - pack V100.0..V100.7 into a byte the master can read
LD SM0.0
// Bit-pack V100.0..V100.7 into VB100 (already byte-aligned)
//
// The EM 277 advertises VBxxx to the master as input byte 0
// depending on the configured slot offset and V-range.
Address Assignment Convention
| Direction | S7-200 Memory (example) | Master Peripheral I/O (S7-300 example) | Notes |
|---|---|---|---|
| Master → Slave (outputs) | VB100..VB107 (8 bytes) | PQ 0..PQ 7 | Starting V-address is configurable in the wizard |
| Slave → Master (inputs) | VB200..VB207 (8 bytes) | PI 0..PI 7 | Starting V-address is configurable in the wizard |
Resolving "Invalid parameter was specified in configuration information"
This message is raised by the Micro/WIN PROFIBUS wizard's pre-download validator when the configuration data block does not match either the wizard inputs or the master's projected I/O. The systematic debug path is:
- Confirm the wizard has been run. Reopen Tools > PROFIBUS Wizard; if the fields are blank, the project has no PROFIBUS configuration at all. Run the wizard with the correct address and I/O size.
- Confirm the CPU family in the wizard. The wizard's first screen asks for the EM 277 model. Selecting a model that does not match the order number on the hardware will produce this error on download.
-
Confirm byte alignment. Any attempt to map a bit (
V100.0) or to map fewer than 8 bits across the wizard is rejected. Convert to a byte map and unpack in user code. - Confirm total I/O size. The wizard reports total bytes; the STEP 7 master slot table must show exactly the same total. 8 in / 8 out on the master must be 8 in / 8 out on the wizard. If the master is 16 in / 16 out but the wizard is 8 / 8, the EM 277 accepts the wizard's configuration, but the master refuses to enter cyclic exchange and the error surfaces on the next Micro/WIN download as the wizard validates against the cached configuration data.
- Re-download both sides. After correcting the wizard, perform a full download of the S7-200 project (program blocks, data blocks, system blocks) and a fresh download of the S7-300 hardware configuration.
- Power-cycle the EM 277. The EM 277 latches the wizard configuration only on power-up. A corrected download without a power-cycle leaves the old parameters in effect.
Verification Procedures
LED Diagnostics on the EM 277
| LED | State | Meaning |
|---|---|---|
| PWR (green) | ON | 24 V supply and internal logic OK |
| SF (red) | OFF | No configuration or diagnostic fault |
| SF (red) | ON | Configuration mismatch, watchdog trip, or fatal firmware error |
| BF (red) | OFF | Cyclic data exchange with master active |
| BF (red) | ON | No PROFIBUS link or slave not in cyclic exchange |
| BF (red) | Flashing | Slave detected on bus but parameterization failed |
Master-Side Verification (S7-300)
- In STEP 7 HW Config, right-click the DP master system and select PROFIBUS > Diagnose to view the live slave list.
- Open a VAT or watch table and force/observe the peripheral I/O words assigned to the EM 277 (for example
PQW 0for outputs,PIW 0for inputs). - From the S7-300 user program, write a known pattern to
PQB 0and verify the same pattern appears at the S7-200'sVB100(or whichever address the wizard chose).
Slave-Side Verification (S7-200)
- In Micro/WIN, open Status Chart and add the configured V-memory bytes (input and output).
- Toggle
PQB 0from the S7-300 watch table; the correspondingVBbyte should update within one DP cycle (typically 5-10 ms at 1.5 Mbps). - Force a bit in the S7-200 input byte and verify the corresponding
PIBon the S7-300 reflects the change.
Troubleshooting Matrix
| Symptom | Likely Cause | Action |
|---|---|---|
| Micro/WIN download fails with "Invalid parameter was specified in configuration information" | Wizard not run; CPU mismatch in wizard; bit-level mapping attempted; I/O size mismatch with master | Re-run Tools > PROFIBUS Wizard, validate byte mapping, ensure sizes match STEP 7 master, re-download |
| EM 277 BF LED steady ON after power-up | PROFIBUS cable fault, terminator missing, wrong address on master, duplicate address on segment | Verify connector pinout, enable termination at both end nodes, recheck addresses in HW Config |
| EM 277 BF LED flashing | Slave detected but parameterization failed - usually configuration mismatch | Compare I/O sizes in HW Config slot table vs. Micro/WIN wizard; verify GSD revision |
| EM 277 SF LED ON, BF OFF | Slave parameterization OK but configuration data block on S7-200 is corrupt or wrong | Re-run wizard, full Micro/WIN download including DB1, power-cycle EM 277 |
| Cyclic exchange runs but data is "shifted" by one byte | Slot offsets in master do not match wizard's V-memory starting offsets | Align V-memory starting addresses in wizard with the slot start addresses used in STEP 7 |
| S7-300 receives all zeros despite EM 277 SF/BF both OFF | S7-200 user program is not writing the configured V-memory bytes | Confirm the wizard-configured subroutine (SBR_xxx) is being called from the main OB1; verify MOV/MOVB writes target the wizard's reserved V-range |
| Watchdog trips on S7-300 CPU (SF on CPU, not just DP) | DP cycle time exceeds OB1 watchdog or DP watchdog | Reduce baud-rate-limited slaves or increase DP watchdog time in HW Config |
PROFIBUS Wiring and Shielding Checklist
- Use only violet PROFIBUS cable (6XV1830-0EH10). The shield must be bonded to the D-sub backshell at every node.
- Maintain at least 20 cm separation from VFD motor cables and other 50/60 Hz power runs.
- Terminate the bus at exactly two nodes - the physical ends. With a point-to-point link (CPU 317-2DP ↔ EM 277), terminate at both ends.
- Do not exceed the segment length budget; if needed, use an RS 485 repeater (6GK1500-0EA02) to extend the segment.
- Avoid spur (stub) lines longer than 0.3 m at 12 Mbps. Use PROFIBUS connectors with horizontal cable entry rather than vertical to minimize stubs.
TIA Portal Context and Migration Notes
Newer TIA Portal versions (V13 through V20) accept the same EM 277 GSD file and present the same slot table, but the surrounding engineering environment differs. For comparison, the same S7-300 / EM 277 topology in TIA Portal V20 is configured through Devices & Networks; the master DP port is selected on the CPU's Properties > PROFIBUS interface subnode. Connection-resource allocation rules for non-DP S7 connections (used for S7-300 to S7-400/1500 communication) are described in S7 connection general settings (S7-300, S7-400, S7-1500) in TIA Portal V20. The S7-200 cannot terminate an S7 connection; it must always be a DP slave on PROFIBUS, not an S7 connection peer.
When migrating from STEP 7 V5.x to TIA Portal, preserve the EM 277 GSD in the new project catalog and re-import the slot table. Micro/WIN remains the only engineering tool for the S7-200 side regardless of the master's portal choice.
Functional Limits and Edge Cases
- Maximum slaves per DP master: The CPU 317-2DP supports up to 32 DP slaves per master system at 1.5 Mbps with default parameters. The EM 277 counts as one slave.
- Diagnostic interrupt: The EM 277 supports DP-V0 only; it does not emit DP-V1 alarms. Diagnostic data must be polled rather than pushed.
-
Consistency: PROFIBUS guarantees byte-level consistency but not multi-byte consistency unless the master uses the Total length read/write services (SFC14 / SFC15 in STEP 7). For data structures larger than 4 bytes, prefer SFC14/SFC15 with the
RECORDvariant of the slot to maintain consistency across the cycle. - Hot-swapping: The EM 277 cannot be inserted or removed under power. Removing it under power will fault the EM 277 and force a station failure on the master.
- Operating mode change behavior: On the CPU 226 STOP → RUN transition, the EM 277 re-enters parameterization. The master briefly shows BF flashing during the transition and resumes cyclic exchange automatically.
Field-Commissioning Caveats
- Always export the STEP 7 project after first successful commissioning and archive it with the Micro/WIN source. The two sides must move together; a configuration change on the master without a matching change in the wizard will surface only as a generic wizard error on the next slave download.
- If the CPU 226 is replaced in the field, the replacement must have the same Micro/WIN project downloaded before it is reconnected to PROFIBUS. An unconfigured CPU 226 + EM 277 stack accepts the parameterization from the master but fails to enter cyclic exchange.
- Record the EM 277 rotary address on the cabinet door label. Field service technicians frequently re-set the address during troubleshooting and forget to update the documentation, leaving the master pointing at the wrong node.
- For installations with long cable runs or high EMC exposure, prefer fiber-optic PROFIBUS via an OLM (Optical Link Module) rather than copper, especially when the S7-200 cabinet is mounted near a VFD or motor contactor panel.
- When the DP segment contains a mixture of 1.5 Mbps and 12 Mbps devices, force the master to the slowest device's baud rate or split the segment with a repeater. Auto-baud on the EM 277 only succeeds if the master's parameterization telegram declares a rate the slave supports.
FAQ
Why does the Micro/WIN PROFIBUS wizard reject my project with "Invalid parameter was specified in configuration information"?
The error means the wizard's generated configuration data block does not match either the master configuration or the byte-granularity rules of PROFIBUS. Reopen Tools > PROFIBUS Wizard, confirm the CPU family and node address, ensure the I/O profile matches the STEP 7 slot table exactly (for example 8 bytes in / 8 bytes out on both sides), and avoid any mapping that targets a single bit such as V100.0 or Q0.1. Transfer whole bytes and unpack bits in the user program.
Can the S7-200 CPU 226 act as a PROFIBUS master?
No. The CPU 226 has no PROFIBUS interface and cannot act as a DP master. It can only participate on PROFIBUS as a DP slave via the EM 277 module. The S7-300 CPU 317-2DP (or any DP-V0/V1 master) must own the bus and parameterize the EM 277.
What is the maximum amount of I/O the EM 277 can exchange with the S7-300?
The EM 277 supports up to 244 bytes of inputs and 244 bytes of outputs in aggregate, configured in fixed slot sizes of 8, 16, 32, or 64 bytes per slot. Most installations use 8 or 16 bytes per direction; larger profiles are reserved for high-throughput applications and require careful attention to consistency services on the master.
How do I read and write consistent blocks larger than 4 bytes from the S7-300?
Use SFC14 (DPRD_DAT) for consistent reads and SFC15 (DPWR_DAT) for consistent writes on the master. Call them with the peripheral address of the EM 277 slot and a length matching the slot size. Without SFC14/SFC15, PROFIBUS only guarantees byte-level consistency and a multi-byte value can be torn across a cycle boundary.
My EM 277 BF LED is flashing but the SF LED is off. What does that mean?
Flashing BF means the master sees the slave on the bus but the parameterization frame was rejected. The most common cause is a configuration mismatch between the STEP 7 slot table and the Micro/WIN wizard (different I/O sizes, different PROFIBUS address, or a GSD revision incompatible with the EM 277 firmware). Compare both sides byte for byte, re-import the correct GSD if necessary, and power-cycle the EM 277.