1. Overview
The integration scenario covered by this reference consists of a Siemens SIMATIC S7-300 station equipped with a CP 341 point-to-point communication module, an ABB serial data converter (commonly an ABB CRS-50 bridging RS-232/422/485 onto an industrial fieldbus), and a downstream GE Fanuc PLC acting as the data source. The intended use case is reading analog process values from the GE Fanuc slave and transporting them into the S7-300 data area.
Among the four protocol options presented on the CP 341 — 3964(R), ASCII Driver, RK 512, and Printer — none of them is the correct choice for this topology. The only protocol that simultaneously allows the CP 341 to talk to a generic Modbus RTU device (the ABB converter configured as a transparent RS-485 bridge) and to a Modbus RTU slave (the GE Fanuc PLC) is Modbus RTU, which requires the Modbus master dongle and the MODB_341 loadable driver.
2. CP 341 Hardware Variants and Order Numbers
The CP 341 family comprises three electrically distinct variants. Selecting the correct variant is mandatory before ordering the matching Modbus dongle, because the dongle is keyed to the physical interface.
| Variant | Order Number (MLFB) | Physical Interface | Typical Use |
|---|---|---|---|
| CP 341 RS-232C | 6ES7 341-1AH01-0AE0 | RS-232C (V.24), 9-pin sub-D | Point-to-point, short distance, full-duplex |
| CP 341 RS-422/485 | 6ES7 341-1CH01-0AE0 | RS-422 (4-wire) or RS-485 (2-wire), 15-pin sub-D | Multidrop, half-duplex, Modbus RTU standard wiring |
| CP 341 TTY | 6ES7 341-1BH01-0AE0 | 20 mA current loop (TTY) | Legacy installations only |
For Modbus RTU communication against an ABB converter operating on a 2-wire RS-485 multidrop segment, the CP 341 RS-422/485 (6ES7 341-1CH01-0AE0) is the correct variant. The RS-232C variant cannot drive an RS-485 bus directly and would require an external converter, which is undesirable because the ABB converter itself is the protocol translator in this topology.
3. Protocol Selection — Why Modbus RTU
The four loadable drivers offered by the CP 341 firmware are mutually exclusive on the dongle. Each dongle enables exactly one protocol:
| CP 341 Dongle Driver | Frame Structure | Suitable for Modbus RTU? |
|---|---|---|
| 3964(R) — Siemens proprietary | STX/ETX + BCC, 3964R adds ACK/NAK | No — Siemens devices only |
| ASCII Driver | Plain ASCII with selectable start/stop characters | No — no CRC, no Modbus framing |
| RK 512 | Siemens RK 512 block-oriented protocol | No — Siemens-only handshake |
| Printer | One-way ASCII output to a serial printer | No — unidirectional, no slave addressing |
| Modbus RTU Master | Modbus RTU (8-N-1 or 8-E-1, CRC-16) | Yes — the only correct choice |
| Modbus RTU Slave | Modbus RTU (8-N-1 or 8-E-1, CRC-16) | Yes — if the CP 341 is the slave, not the master |
Modbus RTU is the only driver in the family that provides:
- CRC-16 integrity checking on every frame
- Standardized function codes (01, 02, 03, 04, 05, 06, 15, 16, etc.)
- Slave addressing 1–247 on a shared bus
- Half-duplex turn-around discipline suited to RS-485
- Register-level read/write semantics that map cleanly to analog I/O
Because the GE Fanuc slave exposes its analog values as Modbus holding/input registers, the master function codes 03 (read holding registers) and 04 (read input registers) are the only ones required for read-only acquisition.
4. Modbus Dongle Installation Procedure
The loadable driver on the CP 341 is enabled by a small EPROM dongle plugged into the back of the module. Each dongle is sold separately and is supplied with a diskette containing the parameter assignment tool and the function blocks. The Modbus RTU master dongle has MLFB 6ES7 870-1AA01-0YA0; the matching slave dongle is 6ES7 870-1AB01-0YA0.
- Power down the S7-300 rack. The CP must be removed from the rack to access the dongle socket.
- With the module removed, locate the dongle socket on the back of the CP 341, above the backplane bus connector. The socket is keyed to accept the dongle in one orientation only.
- Insert the dongle firmly into the socket. The dongle is keyed so that pin 1 aligns with the marked position; do not force it.
- Re-seat the CP 341 in the rack, then power the station back up.
- Open the CP 341 parameter assignment tool (in STEP 7 V5.x, it appears as a CP 341 slot in HW Config → Properties → Parameter Assignment).
- Verify that the Modbus driver is now selectable. If only the four base protocols are still listed, the dongle is not detected — remove and re-seat it.
5. CP 341 Configuration as Modbus RTU Master
After the dongle is detected, the CP is configured from the Parameter Assignment dialog in STEP 7 → HW Config. The following table summarises the parameters relevant to the S7-300 ↔ ABB CRS-50 ↔ GE Fanuc topology.
| Parameter | Recommended Value | Reason |
|---|---|---|
| Protocol | MODBUS Master | Initiating read requests from S7-300 |
| Baud rate | 9600 bit/s (fallback 19200) | Compatible with most ABB serial converters and GE Fanuc serial modules |
| Parity | Even (8-E-1) | Modbus RTU standard; matches ABB default on most drive products |
| Data bits | 8 | Required by Modbus RTU |
| Stop bits | 1 | With even parity → 1 stop bit |
| Character delay | ≤ 1.5 character times (≤ 1.75 ms @ 9600) | Defines the inter-frame silence used by Modbus RTU |
| Inter-character timeout | ≤ 1.5 character times (start of frame detection) | Distinguishes the inter-frame gap from intra-frame gaps |
| Response timeout | 500–2000 ms (start with 1000 ms) | Allows for ABB converter latency |
| Number of retries | 2–3 | Compensate for occasional RS-485 collisions |
| Interface mode | RS-485 (2-wire, half-duplex) | Jumper-set on the 15-pin connector |
| Termination | 150 Ω at both ends of the bus, switched in on the CP and on the last slave | Prevents reflections on the 2-wire segment |
Save and download the hardware configuration. The CP 341 will not enter Modbus data exchange until the user program issues a send/receive job via the P_SND_RK / P_RCV_RK function blocks.
6. ABB CRS-50 Converter Integration
The ABB CRS-50 is a serial-to-Modbus gateway that exposes the host fieldbus as a transparent RS-232/422/485 channel. For use in the present topology the CRS-50 must be configured as a Modbus RTU bridge rather than as an ASCII gateway — the two modes are mutually exclusive and the converter does not auto-detect.
| CRS-50 Setting | Required Value | Notes |
|---|---|---|
| Protocol | MODBUS RTU | Not ASCII — the GE Fanuc slave does not speak ASCII framing |
| Baud rate (host side, facing CP 341) | 9600 bit/s | Must match CP 341 setting exactly |
| Parity / Data / Stop | Even / 8 / 1 | Standard Modbus RTU |
| Termination on CRS-50 RS-485 port | ON only if CRS-50 is the physical end of the segment | Otherwise OFF, with termination at the two physical ends |
| Bridge / Pass-through | Pass-through (transparent) | The CRS-50 must not interpret frames — it must forward them byte-by-byte |
| Handshake signals (RS-232 side) | RTS/CTS unused, TX/RX only | The CP 341 RS-485 variant does not use these |
7. P_SND_RK and P_RCV_RK Function Block Programming
Data transfer between the S7-300 CPU and the CP 341 is performed exclusively through two library function blocks from the CP 341 Point-to-Point Communication package:
- FB 8 / FB 9 — P_SND_RK (Send) — hands a send job to the CP 341 and returns once the job has been accepted by the firmware
- FB 7 / FB 8 — P_RCV_RK (Receive) — fetches the next received frame from the CP 341 and writes it into a CPU data area
The block interface is identical for the Modbus driver; the FB numbers depend on the STEP 7 version and the library variant. In STEP 7 V5.5 with the Modbus master library installed, the standard assignments are FB 8 (P_SND_RK) and FB 7 (P_RCV_RK).
7.1 Send Job Structure (Modbus Master Read Request)
The send buffer for a Modbus master read job is built by the user program and is structured as a Modbus Application Data Unit (ADU) without the slave address and CRC — the CP 341 driver appends both automatically.
DATA_BLOCK "dbSend"
STRUCT
FunctionCode : BYTE := 16#03; // Read Holding Registers
StartingHi : BYTE := 16#00; // Start address high byte
StartingLo : BYTE := 16#00; // Start address low byte
QtyHi : BYTE := 16#00; // Quantity high byte
QtyLo : BYTE := 16#0A; // Quantity low byte = 10 registers
END_STRUCT;
END_DATA_BLOCK
For a request to slave address 1, register 0, quantity 10, the resulting wire frame (CP 341 appends the slave ID and CRC-16) is:
01 03 00 00 00 0A C5 CD
7.2 Receive Job Structure (Modbus Master Response)
The receive buffer is sized for the expected payload plus a 1-byte function-code echo and a 1-byte byte-count prefix:
DATA_BLOCK "dbRcv"
STRUCT
FunctionCode : BYTE; // Echoed by slave, must match request
ByteCount : BYTE; // 2 × number of registers
RegWord : ARRAY[1..20] OF WORD; // Up to 10 holding registers
END_STRUCT;
END_DATA_BLOCK
7.3 OB1 Call Skeleton
// Trigger every 200 ms — adjust to application update rate
CALL "P_SND_RK" , DB108
REQ := TRUE // rising edge starts a new job
R := FALSE
LADDR := 256 // logical I/O address of CP 341 slot
DB_NO := 200 // DB containing the send buffer
DBB_NO := 0 // start at byte 0 of DB 200
LEN := 5 // 5 bytes: FC + start(2) + qty(2)
R_CPU := FALSE
R_LIFE := FALSE
DONE := M 100.0 // job accepted by CP 341
ERROR := M 100.1 // job rejected, see STATUS
STATUS := MW 102
;
CALL "P_RCV_RK" , DB109
EN_R := TRUE // receive permanently enabled
R := FALSE
LADDR := 256
DB_NO := 201 // DB for the receive buffer
DBB_NO := 0
LEN := 21 // 1 + 1 + 2 × 10 = 21 bytes max
NDR := M 110.0 // new data received
ERROR := M 110.1
STATUS := MW 112
S_BUF := ANY-pointer (not used here)
;
REQ input on P_SND_RK is edge-sensitive. Holding it permanently TRUE after the first scan is acceptable for a cyclic request — the CP 341 re-arms itself after the previous job completes — but a one-shot pattern (set REQ, then reset when DONE = TRUE) is the recommended industrial practice.8. RS-485 Half-Duplex Wiring
Because Modbus RTU is a half-duplex, master-slave protocol on a 2-wire RS-485 bus, the wiring must follow the EIA-485 standard strictly. Pin assignments on the CP 341 RS-422/485 (6ES7 341-1CH01-0AE0) 15-pin sub-D connector when jumper-configured for 2-wire RS-485 are:
| Pin | Signal | RS-485 2-Wire Name |
|---|---|---|
| 11 | T(A) — non-inverting driver out / receiver in | Data + (D+) |
| 4 | T(B) — inverting driver out / receiver in | Data − (D−) |
| 6 | 5 V auxiliary supply (≤ 90 mA) | Bus power (optional) |
| 10, 15 | Common / shield reference | Functional earth, shield |
| All others | Unused in 2-wire mode | — |
Wiring rules:
- Maximum stub length from the main trunk to each device: ≤ 30 cm at 9600 bit/s
- Cable: twisted pair, characteristic impedance 100–120 Ω, capacitance ≤ 50 pF/m, e.g. Belden 3106A or equivalent
- Shield: bonded to functional earth at one point only (typically the cabinet ground), to avoid ground loops
- Termination: 150 Ω across A/B at both physical ends of the trunk. The CP 341 has a slide switch inside the connector housing to insert 150 Ω; enable it only if the CP is the physical end of the bus
- Total cable length: ≤ 1200 m at 9600 bit/s, but in noisy industrial environments the practical limit is 500–700 m
9. Master / Slave Role Decision Matrix
Before commissioning, the role of the S7-300 must be fixed. The decision is dictated by which device holds the initiative to read/write registers, not by the physical wiring:
| Role of S7-300 (CP 341) | Role of ABB CRS-50 | Role of GE Fanuc | Required CP 341 Driver | Initiative Source |
|---|---|---|---|---|
| Master | Transparent bridge | Modbus RTU slave | Modbus RTU Master dongle | S7-300 / CP 341 |
| Master | Modbus master on fieldbus side | Modbus slave behind gateway | Modbus RTU Master dongle | S7-300 → CRS-50 → GE Fanuc |
| Slave | Transparent bridge | Modbus RTU master (or another ABB device) | Modbus RTU Slave dongle | GE Fanuc (or other master) |
For the present use case — the S7-300 wants to read analog values from the GE Fanuc — the first row applies: the CP 341 is the Modbus RTU master, the CRS-50 is a transparent RS-485 bridge, and the GE Fanuc is the Modbus RTU slave. This is the only configuration in which the CP 341 initiates the read requests.
10. Verification and Commissioning
- Physical layer check: with the station powered and the CP 341 in run, measure the DC bias on the bus. A healthy RS-485 segment shows approximately 200 mV between A and B, and the 5 V / 0 V bias on the master side from the fail-safe resistors.
- Diagnostic buffer: open STEP 7 → PLC → Diagnostic Buffer. No "Modbus driver not loaded" or "dongle missing" entries must be present.
- Test frame with a Modbus poll utility: temporarily disconnect the CP 341 from the bus and connect a laptop running a Modbus master test tool (e.g., Modbus Poll, QModMaster) at the same baud / parity. Confirm that the GE Fanuc slave responds correctly to function codes 03 and 04.
-
First successful cyclic read: in the S7 user program, monitor
NDRonP_RCV_RKand theByteCountbyte in the receive DB. A non-zeroByteCountwith the expected function-code echo is the first sign of life. -
Timestamp check: log the time between two consecutive
NDRevents; it must equal the application cycle time and must not vary by more than one Modbus frame time (≈ 30 ms at 9600 bit/s for 10 registers). -
Long-run stress test: run for at least 4 h, capturing any
ERRORandSTATUSvalues. A healthy bus produces zero errors per hour at 9600 bit/s; occasional single errors (1 per 24 h) are acceptable.
11. Troubleshooting Matrix
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
| Modbus driver not selectable in HW Config | Dongle missing or unseated | Power down, remove CP 341, re-seat dongle, restart |
| STATUS = 0x0001 on P_SND_RK | Job still active from previous cycle | Reset REQ when DONE=TRUE; do not overlap jobs |
| STATUS = 0x8001 on P_RCV_RK | CRC error in received frame | Check parity, baud, termination; inspect for ground loops |
| STATUS = 0x8002 on P_RCV_RK | Slave address mismatch | Verify the GE Fanuc Modbus slave address matches the request |
| STATUS = 0x8003 on P_SND_RK | Response timeout — no slave reply | Confirm slave is powered, address correct, and RS-485 A/B not swapped |
| STATUS = 0x8004 on P_RCV_RK | Function-code mismatch | Slave replied with exception code 01 or 02 — check GE Fanuc register map |
| STATUS = 0x8005 on P_RCV_RK | Quantity of registers exceeds receive buffer | Increase the LEN parameter of the receive DB |
| Diagnostic buffer: "Parity error" recurring | Electrical noise on the bus | Re-check shield bonding, segregate from VFD power cables, lower baud to 4800 |
| Diagnostic buffer: "BREAK" on RS-485 | Open circuit on A or B line | Continuity-check the trunk; verify termination resistors |
| Intermittent successful reads (1 in 10) | Slave address collision or A/B polarity swap | Swap A and B on one side; verify only one device uses each slave ID |
STATUS value in the Modbus master manual supplied with the dongle for the exact definition in your STEP 7 version.12. Field-Commissioning Notes and Edge Cases
- Baud-rate drift on the GE Fanuc serial module: some older GE Fanuc serial modules (e.g., IC693CMM311) drift by up to 2 % at 9600 bit/s. The CP 341 tolerates ±2 %, but a combination of 2 % drift on both ends pushes the cumulative error to 4 %, producing occasional CRC failures. Use 4800 bit/s on long cable runs if the GE Fanuc module is at the limit of its specification.
- ABB converter not in pass-through mode: if the CRS-50 is left in its Modbus master role on the fieldbus side, it will inject its own requests onto the segment. The CP 341 master requests will then collide with the CRS-50 master requests. Force the CRS-50 into transparent / pass-through operation.
- CP 341 in S7-400 vs. S7-300: the CP 341 is mechanically compatible with both, but the slot numbering and logical I/O address differ. In S7-300, the LADDR is 256 in the example above. In S7-400, re-derive it from HW Config → Properties of the CP 441/443 (the S7-400 equivalent is the CP 441, not the CP 341; the CP 341 cannot be used in an S7-400 rack).
- Mixing master and slave dongles on the same CP: only one dongle fits in the socket. If the application later requires the same CP 341 to act as a slave to another device, the dongle must be physically swapped and the configuration re-loaded.
- Character delay tuning: the 1.5-character inter-frame silence is critical. If the GE Fanuc module is slow to turn the line around, increase the inter-character timeout to 3.5 character times, but only if the same CP is the only master — multiple masters require the strict 1.5 character timing per Modbus RTU.
13. Cross-References and Standards
- MODB_341: Modbus slave instruction for CP 341 (S7-300, S7-400) — Siemens TIA Portal documentation, parameter interface and error codes for the CP 341 Modbus loadable driver.
- EIA/TIA-485-A — Electrical characteristics of generators and receivers for use in balanced digital multipoint systems. Governs the physical layer of the RS-485 segment.
- Modbus Application Protocol V1.1b3 and Modbus over Serial Line V1.02 — Modbus Organization reference documents for function codes, exception codes, and the 1.5 / 3.5 character inter-frame timing.
Which CP 341 driver should I use to read Modbus RTU data from a GE Fanuc PLC through an ABB converter?
Use the Modbus RTU Master dongle (6ES7 870-1AA01-0YA0) on the CP 341 RS-422/485 variant (6ES7 341-1CH01-0AE0). Neither 3964(R), ASCII, RK 512, nor Printer can carry Modbus RTU frames. The driver is enabled by inserting the dongle into the socket on the back of the CP and selecting MODBUS Master in the HW Config parameter assignment.
What function blocks do I need in the S7-300 to send and receive Modbus RTU frames via the CP 341?
Use P_SND_RK to hand a send job to the CP and P_RCV_RK to fetch received frames. In STEP 7 V5.5 with the Modbus master library these are typically FB 8 (P_SND_RK) and FB 7 (P_RCV_RK). The send buffer contains the Modbus function code plus start address and quantity; the CP 341 automatically appends the slave address and CRC-16.
Is Modbus RTU on the CP 341 half-duplex or full-duplex?
Modbus RTU over a multidrop bus is always half-duplex 2-wire RS-485. The CP 341 RS-422/485 variant must be jumper-configured for 2-wire mode and the bus terminated with 150 Ω at both physical ends. Full-duplex 4-wire RS-422 is supported by the same hardware but is not the Modbus RTU standard and is rarely used in this application.
How do I know whether the ABB CRS-50 must be a master or a transparent bridge?
It depends on which side of the gateway holds the initiative. If the S7-300 is reading data from a downstream Modbus slave, the CRS-50 must be set to transparent pass-through mode and the CP 341 acts as the master. If, instead, the CRS-50 itself needs to poll the GE Fanuc and publish the data to a different fieldbus, it must be configured as a Modbus master on the fieldbus side and the S7-300 would then be a slave or use a different protocol to read from the CRS-50.
What is the difference between the CP 341 and the CP 340, and can the CP 340 carry Modbus RTU?
The CP 340 is the predecessor module and supports only 3964(R), ASCII, and Printer drivers. It has no Modbus RTU capability and no dongle socket. The CP 341 is the only S7-300 point-to-point module that supports the Modbus loadable driver. If the application specifies a CP 340, Modbus RTU is not possible on that hardware and a CP 341 must be used instead.