Overview
Exterior lighting projects using a Siemens LOGO! 230RC logic module require attention to three engineering layers that are often overlooked in residential-style installations: input voltage selection, relay output derating, and expansion module addressing. The LOGO! 230RC (a 230 VAC powered base unit with relay outputs) is well suited to mains-driven lighting circuits because it shares the same L/N supply as the lighting load, eliminating the need for an extra 24 VDC power supply. The trade-off is that the on-board relay contacts are not designed to switch the full branch-circuit current of a multi-fixture lighting run; they must drive a contactor or impulse relay, which in turn handles the lighting load.
This reference covers the engineering decisions for a typical three-stage exterior lighting system:
- Scheduled on/off control via the LOGO! weekly/yearly timer blocks.
- Presence-triggered bright-up using a 230 VAC PIR or radar sensor on a digital input.
- Continuous dimming or stepped dimming using a 1–10 V analog output or DALI/KNX gateway.
It also documents expansion with the LOGO! DM8 230R, LOGO! DM16 230R, and the mixed-voltage LOGO! DM8 24R modules, and provides the maximum system architecture permitted by firmware 8.x and 0BA8 base modules.
Prerequisites
- LOGO! 230RC base module (LOGO! 8 family, MLFB 6ED1052-1MD08-0BA1 or 0BA8 standard 6ED1052-1FB00-0BA8). Verify on the device label.
- LOGO! Soft Comfort V8.x or higher for offline program development. The current release is available from the Siemens Industry Online Support portal.
- A 230 VAC mains distribution that includes a dedicated MCB (typically 10 A Type C or Type B) for the LOGO! supply and a separate MCB for the lighting load.
- Sensor data sheet specifying output type (volt-free contact, 230 V switched, or low-voltage DC).
- Contactor or impulse relay with coil voltage matched to the LOGO! relay rating and contact rating ≥ load current.
Selecting the Right LOGO! Base Module
For 230 VAC lighting environments the practical base module choices are:
| MLFB (example) | Supply | Inputs | Outputs | Notes |
|---|---|---|---|---|
| 6ED1052-1FB00-0BA8 (LOGO! 230RCo) | 115/230 VAC | 8 DI | 4 relay (10 A) | No display, no Ethernet |
| 6ED1052-1MD08-0BA1 (LOGO! 8.3 230RCE) | 115/230 VAC | 8 DI | 4 relay (10 A) | Built-in Ethernet, display |
| 6ED1052-1HB00-0BA2 (LOGO! 8 230RCE) | 115/230 VAC | 8 DI | 4 relay (10 A) | Built-in Ethernet, no display |
All 230 V base modules expose the same input circuit topology: each digital input (I1–I8) detects 115/230 VAC between the input terminal and N. Sensor switching must therefore present an AC voltage between the input and N, not a volt-free contact, unless the base unit is a 24 V variant.
Power Supply and Earth Connection Considerations
The LOGO! 230RC accepts 115 VAC and 230 VAC on terminals L1 and N. The PE conductor from the supply must be terminated in the upstream distribution board, but it is not terminated at the LOGO! module. The plastic housing carries no user-accessible earth bonding point; the device relies on reinforced insulation to satisfy Class II requirements. The same applies to every DM8/DM16 230R expansion: the earth from the lighting circuit must continue through the contactor and the lighting load, bypassing the LOGO! entirely.
Wiring the Digital Inputs for the Motion Sensor
For a 230 VAC PIR sensor (typical model families: Steinel IS 1, ESYLUX RC, Theben theLeda), connect the switched output (commonly a brown or black conductor) to a LOGO! digital input (I1–I8) and the neutral (blue) to the LOGO! N terminal. The sensor's L supply is taken from the same MCB that feeds the LOGO! L1.
| Sensor conductor | Function | LOGO! terminal |
|---|---|---|
| Brown (L in) | Live feed to sensor | Distribution L (same MCB as LOGO! L1) |
| Blue (N) | Neutral | LOGO! N |
| Black/Brown (switched L out) | Motion pulse | LOGO! I1–I8 (programmed as DI) |
If the sensor uses a volt-free (relay) output, confirm whether the contact is rated for 230 VAC switching. Some 24 V sensors cannot be wired directly to a 230 V input because the LOGO! input threshold is around 79 VAC (for 230 V inputs) and a 24 V closed contact will never be recognised. In that case, add an interposing 24 VDC relay or use a 24 V base module on the affected input.
Relay Output Limitations and Contactor Sizing
Each LOGO! relay output is rated as follows (manufacturer data, base module 230RCE/230RCo):
- Resistive load: 10 A at 230 VAC
- Incandescent / halogen: 1,000 W
- Fluorescent with electronic ballast: 10 × 58 W
- LED driver switching (inrush-limited): typically 6 A continuous
- Mechanical endurance: 10 million cycles
- Electrical endurance at full load: 100,000 cycles (derate for inductive or capacitive loads)
Although a single LED fixture may fit within the 10 A rating, the contact endurance of a relay that is cycled multiple times per evening by a motion sensor is severely reduced. Use a contactor sized for the load:
| Load | Typical current | Recommended contactor | Contactor coil |
|---|---|---|---|
| 10 × 7 W LED floods | ~0.4 A | Schneider LC1D09 (9 A AC-3) | 230 VAC |
| 30 × 7 W LED floods (one circuit) | ~1.0 A | Schneider LC1D09 or LC1D12 | 230 VAC |
| HID 70 W metal halide × 4 | ~1.5 A + inrush | Schneider LC1D25 with capacitive de-rating | 230 VAC |
Three-phase apparent power (for multi-circuit or 3-phase contactor coils):
kVA = sqrt(3) × V_LL × I_line / 1000
Single-phase apparent power (typical lighting contactor coil):
kVA = V × I / 1000
Wire the LOGO! output (Q1–Q4) to the contactor coil terminal A1, link A2 to N, and route the lighting MCB through the contactor's main contacts (L → contactor in → contactor out → lighting load L, with N and PE handled separately).
Wiring Topology (Inline SVG)
Step-by-Step Wiring Procedure
- Isolate the supply. Lock out / tag out the upstream MCB. Verify zero voltage with a CAT III 600 V meter.
- Mount the LOGO! and contactor on a DIN rail inside a suitable IP54 (outdoor) or IP20 (indoor) enclosure. Maintain ≥ 10 mm clearance above and below for ventilation.
- Terminate the supply. L → LOGO! L1, N → LOGO! N. Do not connect PE to the LOGO!.
- Terminate the sensor. Sensor L → MCB load side; Sensor N → LOGO! N; Sensor switched L out → LOGO! I1.
- Terminate the contactor coil. LOGO! Q1 → Contactor A1; Contactor A2 → N.
- Terminate the lighting MCB through the contactor. Lighting MCB load → Contactor L (in); Contactor T1 (out) → Lighting L; Lighting N → N bus; Lighting PE → PE bus.
- Re-energise the MCB and verify the LOGO! powers up. Display shows 'LOGO!' and the time. Use the cursor keys to navigate to the inputs menu and confirm I1 toggles when the PIR triggers.
Expansion Module Configuration
LOGO! 8.x base modules support a backplane bus that carries digital I/O and analog I/O between the base and up to 8 expansion modules, plus up to 2 communication modules (CMK2000, CMR2020, etc.). The total address space is bounded by firmware, not by a hardware connector count.
| Resource | Maximum on a single LOGO! 8 station |
|---|---|
| Digital inputs | 24 |
| Digital outputs | 20 (16 on the bus + 4 in the base) |
| Analog inputs | 8 |
| Analog outputs | 2 |
| Expansion modules | 8 |
| Communication modules | 2 (CMR/CMK) |
Modules are daisy-chained to the right of the base; the bus connector on the left of the expansion module mates with the bus connector on the right of the previous module. There is no separate cable to buy — the bus is integrated in the module housings. No termination resistor is required.
Module Compatibility Table
| Module | Supply | DI | DO | AI | Use with 230RC? |
|---|---|---|---|---|---|
| DM8 230R (6ED1055-1FB00-0BA2) | 115/230 VAC | 4 | 4 relay | 0 | Yes, same supply, no extra PSU |
| DM16 230R (6ED1055-1NB10-0BA2) | 115/230 VAC | 8 | 8 relay | 0 | Yes, same supply |
| DM8 24R (6ED1055-1CB00-0BA2) | 24 VDC | 4 | 4 relay | 0 | Yes, requires separate 24 VDC PSU on its L+/M terminals |
| DM8 24 (6ED1055-1CB10-0BA2) | 24 VDC | 4 | 4 transistor (0.3 A) | 0 | Yes, requires 24 VDC PSU |
| AM2 (6ED1055-1MA00-0BA2) | 115/230 VAC or 24 VDC | 0 | 0 | 2 | Yes |
| AM2 RTD | 24 VDC | 0 | 0 | 2 (PT100/PT1000) | Yes, with 24 VDC PSU |
Mixing voltage classes is permitted by the firmware; only the expansion module's own supply needs to be present and correctly referenced. A 230 V base and a 24 V DM8 can coexist as long as the 24 VDM8 has its own 24 VDC power supply — the bus carries only logic-level signals, not power. This allows irrigation valves (typically 24 VAC) and alarm sensors (typically 12/24 VDC) to be added later without disturbing the lighting wiring.
Maximum System Configuration
For the exterior lighting + irrigation + alarm project described in the original question, a representative maximum build is:
- 1 × LOGO! 230RCE base (8 DI / 4 DO)
- 1 × DM8 230R (4 DI / 4 DO) for additional lighting zones
- 1 × DM16 230R (8 DI / 8 DO) for grouped lighting and override pushbuttons
- 1 × DM8 24R (4 DI / 4 DO) for irrigation valve actuators on 24 VAC
- 1 × AM2 (2 AI) for a 4–20 mA light-level sensor for dusk/dawn switching
This uses 24 DI (limit), 20 DO (limit), 2 AI (limit), and 5 expansion modules (limit 8). The system will accept the configuration but LOGO! Soft Comfort will issue a warning if any resource is exceeded at compile time.
Programming the Lighting Logic (LOGO! Soft Comfort)
A minimal lighting program consists of three blocks:
- Weekly timer (B001): enables scheduled operation between sunset and a fixed time, e.g. 18:00 to 23:00 Mon–Sun. Output of B001 drives an OR gate to Q1 (contactor = base brightness).
- Edge-triggered one-shot on the PIR (B002): a positive edge from I1 starts an off-delay (B003) of, e.g., 120 s. Output of B003 drives Q2 (boost to 100 % via a second contactor or a 1–10 V signal).
- Yearly timer / astronomical clock (optional, B004): disables the entire system between fixed dates (e.g. December holiday period).
Example block list in LOGO! Soft Comfort ladder notation (FBD is functionally identical):
B001 Weekly Timer Cam1 = 18:00, Cam2 = 23:00, Mon..Sun -> Q1 (dim)
B002 Edge detector Input = I1 (PIR), edge rising -> trigger B003
B003 Off-delay Ta = 120 s -> Q2 (boost)
B004 Yearly timer Off = 23 Dec..02 Jan -> disable B001
B005 OR B001 OR B002 (or manual override I2) -> Q1
Verification and Commissioning
- Apply power. Confirm LOGO! powers up and shows no '?' (unknown module) marker on the display.
- Force Q1 from the menu: the contactor must pull in audibly; the lighting must illuminate. Listen for contactor chatter indicating under-voltage.
- Trigger the PIR by walking through the detection zone. Confirm I1 indicator on the LOGO! display toggles for the duration of the PIR pulse.
- Monitor Q2 (boost) for the configured 120 s after the PIR trailing edge.
- Check the weekly timer by setting the on-time to one minute in the future and verifying the lighting comes on without the PIR.
- Measure the contactor coil voltage under hold: should be ≥ 195 VAC at 230 VAC nominal. Below this, the contactor will buzz and contacts will pit.
- Record all parameters in the LOGO! project comment and export the LSC file for archival.
Troubleshooting Matrix
| Symptom | Likely root cause | Diagnostic step | Fix |
|---|---|---|---|
| LOGO! display blank, no power | MCB tripped, L/N reversed, L missing | Measure L1 to N at the LOGO! terminals | Restore supply; check MCB; swap L and N if 115 V configured |
| Sensor never registers on I1 | Sensor is volt-free contact rated 24 V, LOGO! input is 230 V | Measure voltage on I1 to N when sensor is active | Use 24 V sensor with DM8 24R, or replace sensor with 230 V output type |
| Contactor chatters when Q1 is on | Coil voltage too low (long cable run, undersized wire) | Measure A1–A2 voltage on contactor | Upsize cable or use intermediate relay close to contactor |
| Output relay welds closed | Inrush current from capacitive LED driver exceeding rating | Inspect relay, measure load inrush with scope | Add NTC inrush limiter or use a contactor on all LED loads |
| LOGO! Soft Comfort shows 'unknown module' for DM8 24R | 24 V supply to DM8 is missing or reversed | Measure L+ / M on DM8 24R | Wire external 24 VDC PSU, observe polarity |
| PIR triggers but Q2 does not energise | Off-delay parameter Ta = 0, or B003 is disabled in the program | Open LSC, inspect B003 parameter | Set Ta to 120 s, ensure block is connected |
| Weekly timer fires at wrong time | LOGO! real-time clock not set, or DST not handled | Check menu: Set..Clock | Set time; enable automatic DST in base configuration |
| PE warning from inspector | Inspector expects PE terminal on LOGO! | Show Class II marking on the device | None required; document the device's double-insulation rating |
Field-Notes Summary
For an exterior lighting project that starts with one zone and is later expanded to irrigation and alarms, plan the LOGO! build for the largest expected I/O count from day one. Buy a 230RCE rather than a 230RCo (the Ethernet model is field-upgradable and supports remote access via the LOGO! Access Tool). Always derate the on-board relay by routing the load through a contactor — the cost of a 25 A four-pole contactor is small compared with the labour of replacing a welded relay output. Use the integrated bus for expansion: there is no separate ribbon cable to specify or lose. If you need a 24 V sensor on a 230 V base, add a DM8 24R rather than re-architecting the whole station. Finally, document the earth topology in the as-built drawings so the inspector can see that the PE is correctly bonded at the panel and the load, not at the LOGO!.
How many DM8 230R modules can I add to one LOGO! 230RC base?
A single LOGO! 8 station accepts up to 8 expansion modules and a maximum of 24 digital inputs, 20 digital outputs, 8 analog inputs, and 2 analog outputs. In practice you can attach up to three DM16 230R modules (24 DI / 24 DO) but the firmware will cap the usable count, so a 230RCE + 2 × DM16 230R is the typical maximum in 230 V lighting builds.
Does the LOGO! 230RC need a protective earth (PE) connection?
No. The LOGO! 230RC is a Class II double-insulated device and intentionally provides no PE terminal. The earth conductor from the supply and the lighting load must be terminated at the upstream distribution board and at the load fixture respectively, bypassing the LOGO!.
Can the LOGO! relay output switch the lighting load directly?
Technically yes up to 10 A resistive, but it is poor practice for any load that cycles often (PIR-driven) or that has high inrush (LED drivers, HID, capacitive ballasts). Use a contactor or impulse relay with a 230 VAC coil driven by the LOGO! output; the contactor carries the load current.
Can a DM8 24R be used on a LOGO! 230RC base?
Yes. The DM8 24R requires its own 24 VDC power supply on its L+ and M terminals, but the backplane bus between the modules carries only logic signals. This is the standard way to add 24 V sensors, irrigation valves, or alarm contacts to a 230 V lighting station.
Where can I find a sample LOGO! program for timed lighting with motion override?
The Siemens application examples portal hosts a number of reference projects, including exterior lighting and presence-based dimming. Use the LOGO! Soft Comfort V8.x online help (F1) to browse the 'Application Examples' set, then adapt the weekly timer + edge detector + off-delay pattern to your zones.