1. System Overview
A single-phase control island built on the Siemens LOGO! 230RC logic module can deliver 8 × 230 V AC digital inputs, 4 × relay outputs, and two expansion slots of analog I/O without any external relay interposing. For an application that requires 10 AC digital inputs, 3 PT100 RTD inputs, and 4 relay outputs, the field-proven stack topology is:
LOGO! 230RC (base, slot 0) -> DM8 230R (slot 1) -> AM2 PT100 (slot 2) -> AM2 PT100 (slot 3)
This stack delivers the required I/O with one slot of headroom on the analog side and four unused relay outputs on the DM8 for future expansion. The 230RC base module alone already provides all four 10 A relay outputs needed, so the DM8 outputs can be reserved as spare or for auxiliary functions (alarms, lamps, auxiliary contactors).
2. Module Stack Architecture and I/O Map
| Slot | Module | Power Supply | Digital Inputs | RTD Inputs | Relay Outputs |
|---|---|---|---|---|---|
| 0 (base) | LOGO! 230RC | 115/230 V AC | 8 × 230 V AC | — | 4 × 10 A (resistive) |
| 1 | DM8 230R | 115/230 V AC (internally bus-fed) | 8 × 230 V AC | — | 4 × 5 A (resistive) |
| 2 | AM2 PT100 | 24 V DC or via base | — | 2 × PT100 | — |
| 3 | AM2 PT100 | 24 V DC or via base | — | 2 × PT100 | — |
Addressing in LOGO! Soft Comfort follows the slot position. Inputs I1..I8 belong to the 230RC, I9..I16 belong to the DM8, and AI1..AI2 plus AI3..AI4 belong to the two AM2 PT100 modules (channel count is module-relative in LOGO!). Outputs Q1..Q4 belong to the base, Q5..Q8 belong to the DM8.
2.1 Channel Assignment Example
| Function | Channel | Module | Phase |
|---|---|---|---|
| Start pushbutton | I1 | 230RC (group A) | L1 |
| Stop pushbutton | I2 | 230RC (group A) | L1 |
| High-pressure switch | I3 | 230RC (group A) | L1 |
| Flow switch | I4 | 230RC (group A) | L1 |
| Level switch | I5 | 230RC (group B) | L1 (or L2) |
| Thermal cut-out | I6 | 230RC (group B) | L1 (or L2) |
| Spare | I7 | 230RC (group B) | L1 |
| Spare | I8 | 230RC (group B) | L1 |
| Aux. contactor 1 | Q1 | 230RC | any (potential-free) |
| Aux. contactor 2 | Q2 | 230RC | any (potential-free) |
| Solenoid valve 1 | Q3 | 230RC | any (potential-free) |
| Solenoid valve 2 | Q4 | 230RC | any (potential-free) |
| Bearing temp sensor | AI1 | AM2 slot 2 | — |
| Winding temp sensor | AI2 | AM2 slot 2 | — |
| Ambient temp sensor | AI3 | AM2 slot 3 | — |
The DM8 outputs Q5..Q8 and the unused RTD channel AI4 remain available for later scope creep.
3. AC Input Phase Isolation: The Critical Constraint
This is the single most overlooked rule in 230 V AC LOGO! wiring. The 230RC base module splits its eight digital inputs into two electrically isolated groups of four:
- Group A: I1, I2, I3, I4 (terminals share one internal common)
- Group B: I5, I6, I7, I8 (terminals share a separate internal common)
The two groups are separated on the terminal block by a physical gap — a missing terminal screw — that visually marks the isolation boundary. The reason is galvanic isolation: if you wire inputs from different phases (e.g., L1 and L2) into the same group, the internal commons are shorted together and the inputs cross-couple through the supply.
3.1 Rules by Module Family
| Module | Input Groups | Cross-Phase Allowed? | Notes |
|---|---|---|---|
| LOGO! 230RC (base) | 2 groups of 4 | Yes — one phase per group | Physical terminal gap separates groups |
| DM8 230R | 1 group of 8 | No — all inputs same phase | Single internal common |
| DM16 230R | 2 groups of 8 | Yes — one phase per group | Use when different phases are required |
| AM2 PT100 | n/a (analog) | n/a | Sensor-side isolation only |
3.2 Practical Wiring Strategies
Strategy 1 — single-phase supply (typical). If all digital inputs are fed from L1, no group rules apply. All four groups on the 230RC plus the DM8 can use L1 directly. This is the simplest layout and matches the application where the pushbuttons, switches, and sensors are all on the same lighting or control circuit.
Strategy 2 — mixed-phase supply (three-phase system). If signals come from different phases (e.g., motor contactor status feedback from L1 and L2), assign each input to the correct group. For example, I1..I4 on L1 and I5..I8 on L2. The DM8 cannot be mixed — if you need additional 230 V inputs on L2, use a DM16 (which has two groups) rather than a DM8.
Strategy 3 — reserve groups. If a single-phase UPS feeds the LOGO! power supply and the I/O distribution is single-phase, the isolation rules collapse into a single-phase sanity check: confirm the L wire feeding I1..I4 and I5..I8 is the same conductor all the way back to the breaker.
4. Digital Output Relay Ratings and Derating
The 230RC and DM8 230R use electromechanical relay outputs, not transistors. Two rating numbers must be respected: the published resistive rating and the much smaller inductive rating.
| Output Module | Resistive Rating | Inductive Rating | Typical Inductive Use |
|---|---|---|---|
| 230RC Q1..Q4 | 10 A | derated (see below) | Small contactor coils, solenoid valves |
| DM8 230R Q5..Q8 | 5 A each | derated (see below) | Auxiliary relays, indicator lamps |
| LOGO! Contact 230 (contactor) | 20 A | 4 kW (AC-3 class) | Direct motor switching up to 4 kW |
The 10 A and 5 A ratings on the LOGO! relays apply to resistive loads such as heating elements or incandescent lamps. For inductive loads (contactor coils, solenoid valves, motor windings), the inrush and stored energy reduce the permissible continuous current substantially — typically to AC-15 / DC-13 values published in the device manual.
4.1 Output Isolation
Relay contacts on the 230RC and DM8 are potential-free — each contact has its own pair of terminals and is electrically isolated from the LOGO! internal circuitry. This means different phases can be wired across different outputs on the same module. Q1 can switch L1, Q2 can switch L2, Q3 can switch L3, and so on, without cross-coupling. The phase-isolation rule that applies to inputs does not apply to outputs.
4.2 Practical Recommendation
For motor loads or large solenoid banks, drive a LOGO! Contact 230 contactor from a LOGO! relay output. The contactor coil draws < 50 mA at 230 V AC and is well within the LOGO! rating, while the contactor's main contacts handle the 4 kW load directly. This also adds galvanic isolation between the LOGO! and the field, reducing surge coupling back into the logic supply.
5. AM2 PT100 Analog Input Configuration
The AM2 PT100 expansion provides two 3-wire PT100 RTD inputs per module. The two modules together provide four channels — one more than the application requires. For a 3-sensor application, AI1, AI2, and AI3 are wired to PT100 probes; AI4 is left open.
5.1 Wiring
For each PT100 sensor, run three conductors to the AM2 terminals: two in one leg (to compensate for lead resistance) and one in the other. Cable length and gauge matter: long runs introduce lead-resistance error that is only partially compensated by the 3-wire scheme.
| Parameter | Typical Value | Notes |
|---|---|---|
| Sensor type | PT100 (100 Ω at 0 °C) | Class A or Class B per IEC 60751 |
| Wire count | 3-wire (typical) | 2-wire reduces accuracy |
| Measurement range | −50 °C to +200 °C (typical LOGO! AM2 RTD spec) | Verify in your device manual |
| Resolution | 0.25 °C typical | Sufficient for motor / bearing protection |
5.2 Programming the Analog Inputs
In LOGO! Soft Comfort, the analog input block exposes the value as a scaled integer (in tenths of °C, or in raw ohms). Use the Analog Threshold Trigger or Analog Comparator blocks to alarm on overtemperature. A common configuration is two thresholds: a warning at 80 °C and a trip at 95 °C for class B insulation motors.
6. Power Supply Topology with UPS
For process-critical applications where the LOGO! must ride through mains dips and brief outages, a small single-phase UPS feeds the LOGO! power supply terminals (L, N). The UPS should be sized for the LOGO! base plus expansion steady-state draw plus the relay coil current.
6.1 Power Budget
| Consumer | Typical Draw |
|---|---|
| LOGO! 230RC base | 15–40 mA @ 230 V AC (idle to loaded) |
| DM8 230R expansion | 20–30 mA @ 230 V AC |
| AM2 PT100 (each) | 20–30 mA @ 24 V DC (sensor excitation) |
| Total LOGO! draw | ~ 100–150 mA @ 230 V AC ≈ 23–35 VA |
| Plus external relay coils | ~ 50 mA @ 230 V AC per coil |
A 100 VA online UPS (e.g., a SITOP or generic 230 V AC line-interactive unit) provides roughly 10–15 minutes of ride-through at this load — sufficient for most process-grade applications.
6.2 Earthing and PE
Wire PE from the UPS output ground to the LOGO! PE terminal (where provided on the base module). The PE bond is required for EMC and surge immunity, even if no field device draws PE current. For the DM8, no separate PE terminal is required.
7. Field Wiring Topology
The diagram below shows a representative wiring topology with the 230RC base, DM8 expansion, two AM2 PT100 modules, and the LOGO! Contact 230 contactor as the motor-switching element.
8. Programming in LOGO! Soft Comfort
The LOGO! Soft Comfort programming environment is the standard tool for configuring the stack. It allows you to:
- Detect the connected stack automatically via the Tools -> Detect LOGO! menu.
- Assign symbolic names (e.g.,
I1 = START_PB) via the I/O name editor. - Configure AM2 analog inputs as PT100 mode and scale to engineering units (°C).
- Program logic using FBD or LAD — for typical motor control, use a start/stop seal-in latch with an analog comparator trip from the RTD input.
- Simulate the program before download.
- Download to the LOGO! via Ethernet (LOGO! 8) or via the LOGO! cable (older 0BA6).
8.1 Sample Ladder Snippet — Seal-in with RTD Trip
Network 1: Seal-in (start permissive)
|--[ I1 START_PB ]--+--[ I2 STOP_PB_NC ]--+--( )-- Q1 MOTOR_RUN
| | |
|--[ Q1 feedback ]--+ |
Network 2: Overtemperature trip
|--[ AI3 > 95 degC ]--+--[/ Q1 ]-- (forces Q1 off on overtemperature)
The analog comparator block AI3 thresholds the PT100 input against a fixed setpoint. If the bearing temperature exceeds 95 °C, the comparator output forces Q1 off regardless of the seal-in latch.
9. Commissioning Verification Checklist
Before energising the field wiring, walk the stack through this checklist:
- Verify stack address assignment — confirm that I1..I16 and Q1..Q8 map correctly per slot.
- Verify phase isolation — with a multimeter on ohms, confirm that L of group A (I1..I4) and L of group B (I5..I8) are the same phase if you intended a single-phase layout. If they should be different phases, confirm the wiring maps to the correct groups.
- Verify input commons — confirm that N terminals of all input groups are tied to the same N bus.
- Verify relay contact isolation — with the LOGO! unpowered, check that no two relay contact commons are bridged.
- Verify PT100 wiring — for each sensor, measure resistance at the AM2 terminals with the sensor disconnected. PT100 should read ~ 107–110 Ω at room temperature (20–25 °C) including lead resistance.
- Verify UPS voltage — confirm 230 V AC ± 10% on L and N at the LOGO! power terminals before power-up.
- Power up — observe the LOGO! display / LEDs for normal run state.
- Force each input — toggle each pushbutton or sensor and verify the corresponding I indicator on the LOGO! display changes.
- Force each output — through LOGO! Soft Comfort online mode, force each Q output and verify the contactor or load responds.
- RTD sanity check — compare LOGO! Soft Comfort's online AI value to a handheld RTD calibrator reading.
10. Troubleshooting Matrix
| Symptom | Likely Cause | Verification | Resolution |
|---|---|---|---|
| LOGO! does not power up | No L/N voltage; UPS in bypass | Measure 230 V AC at L/N terminals | Restore mains; check UPS output |
| Input I1..I4 always on; cross-coupled to I5..I8 | Two phases wired to the same group — internal short | Measure phase-to-phase voltage between group A and group B commons | Re-wire to ensure each group is on one phase |
| PT100 reads −50 °C (underrange) | Open sensor lead or wrong wiring | Measure resistance at AM2 terminals | Re-terminate or replace sensor |
| PT100 reads ~ 200 °C + saturates | Short between sensor leads | Measure lead-to-lead resistance (should be ~ 110 Ω) | Replace cable run |
| Relay output welds closed | Inductive load driven above rating | Check load current vs published inductive spec | Add snubber or interpose contactor |
| Expansion module not detected | Wrong slot, missing terminator, firmware mismatch | Tools -> Detect LOGO! | Re-seat module; check firmware |
| LOGO! loses program on power cycle | No battery / supercap depleted, or no program retention | Check battery LED; re-download program | Replace battery (if equipped); re-download |
| DM8 inputs do not respond | Inputs wired to wrong phase, or DM8 not addressed | Verify slot and phase | Re-seat DM8; verify wiring |
| Output Q1 chatters / overheats | DC inductive load without flyback diode | Check load type and voltage | Add flyback diode or use AC-rated load |
| AI reads high-frequency noise | RTD cable run parallel to VFD output | Inspect cable routing | Re-route, add shielding, separate by 300 mm |
11. Related Module Sizing Notes
For applications where the LOGO! base + DM8 + AM2 stack exceeds the available slots or the budget, the following alternatives are field-proven:
- LOGO! 24RC — DC-powered variant with DC inputs (24 V DC sourcing instead of 230 V AC). Useful if the field signals are 24 V DC.
- LOGO! 12/24RCE with LOGO! AM2 (0–10 V analog) instead of AM2 PT100 — for non-RTD analog inputs.
- LOGO! 8 with Ethernet — supports remote I/O via the LOGO! CMR (communication module) for cellular telemetry.
Reference the Siemens LOGO! System Manual on the Siemens Industry Online Support portal for the full module catalog, derating curves, and wiring diagrams applicable to your specific firmware version.
12. Safety and Standards Notes
The configuration described here is built around 230 V AC mains-voltage signals and must comply with local electrical installation rules. The following points are non-negotiable:
- Isolation: when working with the module unpowered, confirm zero energy with a voltage tester on every input terminal, not just at the breaker.
- Overcurrent protection: each digital input group should be fed through a fused or breaker-protected branch sized for the field device count.
- Surge protection: if the inputs are routed outdoors or near inductive switching, fit surge arrestors at the panel entry.
- Relay contact protection: for inductive loads, fit an RC snubber (for AC) or flyback diode (for DC) across the load, or use the LOGO! Contact 230 contactor as an interposing element.
- Standards to verify: IEC 61131-2 for PLC environmental requirements, IEC 60947 for contactors, and IEC 60751 for PT100 sensor accuracy classes. Compliance with any of these is application-specific and must be verified by the integrator.
Disclaimer: this article documents the field-proven stack topology and the engineering rules of thumb that govern it. Always cross-check against the device manual for your specific module revision and firmware version. Electrical ratings, especially derated values for inductive loads, are subject to change between firmware versions and should be confirmed in the latest Siemens LOGO! manuals page.
Can I wire inputs from L1, L2, and L3 phases to a single LOGO! 230RC?
Only across the two isolated groups: L1 to I1..I4 and L2 to I5..I8 (or vice versa). Mixing phases within the same group of four inputs will short phases through the internal common rail and damage the module. The DM8 230R has a single input group of 8, so it cannot accept mixed phases.
What is the difference between the 10 A rating on the 230RC and the 5 A rating on the DM8 230R outputs?
Both are resistive load ratings. The 230RC base module outputs are rated at 10 A resistive for general-purpose loads; the DM8 230R expansion outputs are rated at 5 A resistive per output. For inductive loads such as contactor coils or solenoid valves, both must be derated substantially — refer to the device manual for AC-15 / DC-13 inductive ratings.
Can the AM2 PT100 module measure only three sensors, or do all four channels need to be populated?
Three sensors are supported on a 4-channel stack (two AM2 modules). Leave the unused channel's terminals open. The LOGO! will report an underrange value (typically −50 °C) for the unused channel — mask this in the program so it does not trigger spurious alarms.
Do I need a separate 24 V DC supply for the AM2 PT100 modules?
It depends on the LOGO! generation and the AM2 variant. Some AM2 PT100 modules are powered from the internal LOGO! bus and require no external supply; others need a 24 V DC auxiliary. Confirm in the device manual for your specific module revision.
Why use the LOGO! Contact 230 instead of switching the load directly with the LOGO! relay?
The LOGO! Contact 230 is a 20 A / 4 kW AC-3 contactor designed for direct motor switching. It draws < 50 mA at the coil, which is well within the LOGO! 10 A relay rating, while its main contacts handle the heavy motor load. This isolates the LOGO! from motor inrush, surge, and back-EMF, extending relay life.