Overview
The Siemens MICROMASTER 440 (MM440) supports two independent Command Data Sets (CDS0 and CDS1) and three independent Drive Data Sets (DDS0–DDS2). A Command Data Set groups the parameters that define where the drive receives its run command and where it receives its speed setpoint. By writing one set of parameters for index [0] and another set for index [1], a single MM440 can be switched between two completely different control schemes using a single hardware selector input.
This reference covers the canonical industrial case:
- Remote mode (CDS0) – run command from a terminal push button, speed setpoint from a 0–10 V or 4–20 mA analog signal sourced by a PLC.
- Local mode (CDS1) – run command from the same terminal push button, speed setpoint generated internally by the Motor Potentiometer (MOP) function, ramping up/down from a configurable fixed starting frequency.
The Local/Remote hand-off is performed by a single selector switch wired to DIN4, which is internally routed via P0810 to the active-CDS bit. No PLC re-programming, no fieldbus toggle, and no BOP key sequence is required at the panel.
Prerequisites
- MM440 inverter, any frame size (A through F) with firmware ≥ 1.0. The CDS feature is available on all production MM440 units; the procedure here is valid for firmware versions 1.x, 2.x, and 3.x.
- Basic Operator Panel (BOP) or Advanced Operator Panel (AOP) connected to the front RS-232 port for parameter entry.
- Three-wire start/stop push-button station (Start – N.O., Stop – N.C.) wired to DIN1 and +24 V.
- Local/Remote selector switch (1-pole 2-position maintained) wired to DIN4 and +24 V.
- For local mode MOP raise/lower: two momentary N.O. push buttons wired to DIN2 and DIN3.
- For remote mode: PLC analog output module (0–10 V on terminals 3/4 or 4–20 mA on terminals 10/11).
- Motor nameplate data available for P0304–P0311 (rated voltage, current, power, cos φ, frequency, RPM).
System Architecture and Operating Modes
The MM440 evaluates the active CDS at every control cycle (1 ms). When P0810 is configured to a digital input, the logical state of that input becomes the active-CDS selector:
| State of DIN4 (CDS selector) | Active CDS | Command Source | Setpoint Source | Use Case |
|---|---|---|---|---|
| LOW (0 V) | CDS0 (index [0]) | Terminal strip | Analog input from PLC | Remote – controlled by automation |
| HIGH (+24 V) | CDS1 (index [1]) | Terminal strip | Motor potentiometer (MOP) | Local – operator control at panel |
The selector bit does not need to be re-latched, debounced in software, or confirmed to the PLC – the MM440 performs the switch atomically on the next scan. The active CDS is reported in parameter r0050 (bit 0 of the active command word) for diagnostic read-back via USS/PROFIBUS or via the BOP.
Command Data Set (CDS) Parameter Strategy
The two parameters that drive 90 % of a CDS implementation are P0700 (command source) and P1000 (setpoint source). Both are indexed:
| Parameter | Index | Value | Meaning |
|---|---|---|---|
P0700 |
[0] | 2 | CDS0: command source = terminal strip |
P0700 |
[1] | 2 | CDS1: command source = terminal strip |
P1000 |
[0] | 2 | CDS0: setpoint = analog input 1 (ADC1) |
P1000 |
[1] | 1 | CDS1: setpoint = motor potentiometer (MOP) |
Why command source = terminal in both CDS, not BOP for the local case? The original question required that the Start/Stop push button initiate motion in both cases. A BOP-key start would not match this requirement. By keeping P0700[1] = 2, the operator's panel-mounted push buttons remain the run authority in local mode; only the setpoint source changes. This is the recommended architecture and is the one documented in the MM440 Operating Instructions for the dual-standby / manual-override case.
Step-by-Step Configuration Procedure
All parameter writes are performed from the BOP. Navigate to each parameter, press P, use the up/down arrow to edit, press P again to confirm.
Step 1 – Motor and Drive Identification
Set the standard motor commissioning parameters before enabling any CDS switching. These are not CDS-dependent and apply to both data sets.
-
P0100 = 0– operation in Europe (50 Hz, kW) -
P0205 = 1– inverter application (constant torque, low overload) -
P0300 = 1– select induction motor -
P0304– rated motor voltage (V) -
P0305– rated motor current (A) -
P0307– rated motor power (kW) -
P0308– rated motor cos φ -
P0309– rated motor efficiency (%) -
P0310– rated motor frequency (Hz) -
P0311– rated motor speed (RPM) -
P0335 = 1– motor cooling = self-ventilated -
P0640 = 150– motor overload factor (%) -
P1080 = 0– global minimum frequency (Hz) -
P1082 = 50– global maximum frequency (Hz) -
P1120 = 10– ramp-up time (s) -
P1121 = 10– ramp-down time (s) -
P1135 = 5– OFF3 ramp-down time (s) -
P1300 = 0– V/f linear characteristic
Run quick commissioning by setting P0010 = 1 and then P3900 = 3 to calculate motor data automatically. After the drive returns to display mode, set P0010 = 0.
Step 2 – Configure the Command Source for Each CDS
-
P0700[0] = 2– CDS0 commands come from the terminal strip. -
P0700[1] = 2– CDS1 commands also come from the terminal strip (keeps the operator push button active in local mode).
P0700[1] = 1 (BOP) unless the local run command is also being moved to the BOP keypad. The BOP start key would then be required, which conflicts with a hard-wired Start push button.Step 3 – Configure the Setpoint Source for Each CDS
-
P1000[0] = 2– CDS0 reads the main setpoint from analog input 1 (terminals 3 and 4, 0–10 V default; 4–20 mA ifP0756is re-scaled). -
P1000[1] = 1– CDS1 reads the main setpoint from the internal MOP, whose value is bumped by DIN2 (raise) and DIN3 (lower).
Step 4 – Map the Digital Inputs for Each CDS
| Digital Input | Terminal Pin | CDS0 Function (P070x[0]) | CDS1 Function (P070x[1]) | Description |
|---|---|---|---|---|
| DIN1 | 5 | 1 (P0701[0] = 1) | 1 (P0701[1] = 1) | ON / OFF1 – Start push button in both modes |
| DIN2 | 6 | 0 (P0702[0] = 0) | 13 (P0702[1] = 13) | MOP raise (local only) |
| DIN3 | 7 | 0 (P0703[0] = 0) | 14 (P0703[1] = 14) | MOP lower (local only) |
| DIN4 | 8 | – (reserved) | – (reserved) | CDS selector (0 = CDS0, 1 = CDS1) |
| DIN5 | 16 | 3 (P0705[0] = 3) | 3 (P0705[1] = 3) | Fault acknowledge (ACK) |
Step 5 – Activate the CDS Selector on DIN4
-
P0810 = 4– the bit-0 CDS selector source is connected to digital input 4. - Verify with
r0050; bit 0 should follow the state of DIN4 in real time.
Step 6 – Configure the MOP Behavior in CDS1
-
P1031 = 1– store last MOP setpoint so the drive resumes at the previously commanded speed after a power cycle. -
P1032 = 1– inhibit negative MOP setpoints (motor cannot run in reverse via MOP raise/lower). -
P1040[1] = 40.0– CDS1 MOP starting setpoint. The drive will ramp to 40 Hz on the first ON command in local mode, then accept raise/lower presses. -
P1080[1] = 40.0– CDS1 minimum frequency. The MOP cannot command below 40 Hz in local mode; the motor will not stall at low speed. -
P1058[1] = 50.0– CDS1 jog frequency (optional, used if a separate jog input is also wired).
P1080 and the MOP setpoint P1040 are independent parameters. Setting P1080[1] = 40 while leaving P1040[1] = 5 would mean MOP can still command 5 Hz, but the drive will clamp to 40 Hz. Set P1040[1] to match P1080[1] so the operator experience is intuitive (start at 40 Hz, raise and lower around 40 Hz).Step 7 – Configure the Analog Input for CDS0
-
P0756[0] = 0– ADC1 type = 0–10 V unipolar (default). -
P0757[0] = 0– ADC1 scaling x1 = 0 V. -
P0758[0] = 0.0– ADC1 scaling y1 = 0 %. -
P0759[0] = 10.0– ADC1 scaling x2 = 10 V. -
P0760[0] = 100.0– ADC1 scaling y2 = 100 %. -
P0761[0] = 0– ADC1 dead-band width = 0 V (no dead-band for PLC-driven setpoint).
The default 0–10 V to 0–50 Hz mapping is usually correct; if the PLC outputs 4–20 mA, wire to terminals 10/11 (ADC2) instead and re-scale P0756[1] = 2, P0759[1] = 20 mA.
Step 8 – Set Access Level and Save
-
P0003 = 3– expert access level (required to see and edit P0100 and other expert-only parameters). -
P0971 = 1– save all parameters to EEPROM. The drive will copy RAM values to non-volatile memory; allow approximately 5 seconds for the operation to complete.
Terminal Wiring and I/O Assignment
The MM440 control terminals are located on the front, behind the front cover. Use the diagram below for a single-supply, sinking-input wiring scheme (24 V supplied from the MM440 internal +24 V on terminal 9):
Wiring notes:
- Use a single 24 V rail from pin 9 and run the Stop N.C. contact in series with all start devices. Pressing Stop must drop DIN1 regardless of the CDS selected.
- For DIN4 selector, route the same +24 V from pin 9 through the L/R switch directly to pin 8.
- ADC1 reference (pin 4) must be tied to pin 1 (DGND) for single-ended 0–10 V PLC output. If the PLC output is differential, leave pin 4 connected to the PLC negative terminal only.
MOP (Motor Potentiometer) Operation in CDS1
Once P1000[1] = 1, the setpoint displayed in r0021 is the MOP setpoint. It is calculated as:
f_setpoint = P1040[1] + MOP_increment × P1058 × dt
where MOP_increment is +1 when DIN2 is active, –1 when DIN3 is active, P1058 is the MOP ramp rate (Hz/s), and dt is the scan time. Typical tuning values:
| Parameter | Value | Effect |
|---|---|---|
P1058 |
5.0 Hz/s | Pressing raise for 2 s adds 10 Hz |
| P1059 | 5.0 Hz/s | Pressing lower for 2 s subtracts 10 Hz |
| P1060 | 10.0 s | Pressing raise for 10 s reaches max from 0 |
| P1061 | 10.0 s | Pressing lower for 10 s reaches min from max |
The MM440 uses P1058/P1059 on MM440 ≥ FW 1.1; on older firmware the values P1060/P1061 control the rate. The Operating Instructions confirm which parameters apply to the firmware version on your nameplate label.
P070x = 0 (disabled) AND a wire to either rail. Floating inputs can cause intermittent MOP pulses.Analog Setpoint from PLC in CDS0
When DIN4 is LOW, CDS0 is active and r0021 reads the scaled value of ADC1 in percent. The MM440 multiplies this percentage by P2000 (default 50 Hz reference) to obtain the setpoint in Hz:
f_setpoint [Hz] = r0021 [%] × P2000 [Hz] / 100
If the PLC outputs 0–10 V, the resulting speed range is 0–50 Hz. If a different range is required, scale either P0757–P0760 (analog scaling) or P2000 (reference). Verify the scaling live with r0021 while the drive is stopped (no ON command), which avoids any setpoint filtering artifacts.
Commissioning and Verification
- Power-on test: Energize the drive with the Start push button released and the L/R selector in Remote (LOW). BOP should show the drive in "Ready" (r0002 = 1) with output frequency 0 Hz.
-
Remote speed sweep: Press Start. Drive should accelerate to 0 Hz (PLC at 0 V). Command the PLC to 5 V.
r0021should read 50 %;r0024should read 25 Hz within ramp time P1120. -
Selector switch test: With the drive running at 25 Hz, flip the L/R switch to Local (HIGH). The MM440 should freeze the MOP setpoint at the value of
P1040[1](default 5 Hz, or whatever the MOP had stored), not the analog value. Output frequency should ramp to that MOP value using P1121. -
Local speed sweep: Press MOP Raise for 5 s.
r0024should increase by approximatelyP1058 × 5 = 25 Hzfrom the starting value (subject to P1082 clamp). -
Stop authority: Press Stop. Drive should ramp down per P1121. Toggle L/R switch back to Remote, then to Local again. Drive should remain stopped; the MOP setpoint persists per
P1031 = 1. - Fault injection test: Open the motor wiring at the drive output terminals and command a run. The drive should trip with F0001 (overcurrent). Acknowledge via DIN5; drive should return to ready.
Troubleshooting Matrix
| Symptom | Likely Cause | Diagnostic Step | Corrective Action |
|---|---|---|---|
| Drive ignores L/R switch | P0810 not set, or wired to wrong input | Toggle DIN4; read r0050 bit 0 |
Set P0810 = 4; verify DIN4 wiring to pin 8 |
| Local mode runs at 5 Hz instead of 40 Hz | P1040[1] default (5) not overwritten | Read P1040[1] on BOP |
Set P1040[1] = 40; P0971 = 1 to save |
| MOP raise/lower does nothing | P0702[1] / P0703[1] still 0 | Read P0702[1], P0703[1] | Set P0702[1] = 13, P0703[1] = 14 (CDS1 only) |
| Analog setpoint stuck at 0 Hz | ADC1 wiring reversed or P1000[0] wrong | Read r0021 with 5 V applied |
Verify pin 3 = +, pin 4 = –; check P1000[0] = 2
|
| Drive trips F0001 immediately on start | Motor data wrong or ramp too short | Read P0304–P0310; ramp times P1120/P1121 | Re-enter motor nameplate data; extend ramp to ≥ 5 s |
| MOP setpoint resets on power cycle | P1031 = 0 | Read P1031 | Set P1031 = 1 and save with P0971 = 1 |
| Output frequency oscillates in analog mode | ADC1 noise pickup or dead-band wrong | Measure ADC1 voltage with scope | Set P0761[0] = 0.5 V dead-band; shield the analog cable |
| Drive starts in local without Start button | Hardware wire short or P0700[1] = BOP | Read P0700[1] and check DIN1 voltage | Set P0700[1] = 2; verify Stop N.C. is in series |
| Direction reverses unexpectedly | P1032 = 0 allows negative MOP | Read P1032 | Set P1032 = 1 to inhibit reverse via MOP |
| CDS switch causes fault F0041 | Motor identification or parameter inconsistency between CDS | Read F0041 history in r0947
|
Run P1900 = 2 motor ID; ensure P0700[0] = P0700[1] for symmetry |
For any of the above, the canonical reference is the MM440 parameter list and fault code table in the Operating Instructions (Section "Faults and Alarms").
Field-Proven Caveats
- Parameter changes are written to RAM immediately but lost on power-down unless
P0971 = 1is executed. Always run a final save before closing the cabinet. - The CDS switch is bumpless only for the setpoint path. If the drive is at 50 Hz (analog) and you switch to local, the output ramps to the MOP value via the deceleration ramp; it does not jump. This is the expected and safe behavior.
- When both CDS use the same
P0700value (terminal), changing the active CDS mid-run does not interrupt the run command. This is why this architecture is preferred over a P0700 toggle. - Some PLC scan schedules expect a feedback bit that confirms the active CDS. Map
r0050bit 0 to a digital output usingP0731or expose it over USS to the PLC if the L/R status is needed by the automation.
FAQ
Can the same Start/Stop push button be used for both Local and Remote mode on the MM440?
Yes. Wire the Start N.O. to DIN1 and the Stop N.C. in series with +24 V. Set P0701[0] = 1 and P0701[1] = 1, so DIN1 acts as ON/OFF1 in both CDS0 and CDS1. The L/R selector on DIN4 then changes only the setpoint source, not the run authority.
What is the difference between Command Data Set (CDS) and Drive Data Set (DDS) on the MM440?
CDS groups command-source and setpoint-source parameters (P0700, P1000, P0701–P0706, etc.) and is selected at runtime by a single bit. DDS groups motor and ramp parameters (P0300–P0335, P1080, P1082, P1120, P1121, P1300) and is selected by drive logic or another digital input. The dual-Local/Remote use case requires CDS switching; DDS switching is for multi-motor applications.
Why does the MOP start at 5 Hz even though I set P1080[1] = 40?
P1080 is the minimum frequency clamp; P1040[1] is the MOP's stored setpoint. The MOP outputs P1040, not P1080. To start at 40 Hz in local mode, set P1040[1] = 40. The minimum frequency P1080[1] = 40 then prevents the MOP from dropping below 40 Hz when the operator presses Lower.
What fault code indicates a CDS parameter inconsistency?
Fault F0041 (motor data identification failure) can be triggered if the motor data differs between DDS sets when the CDS switch occurs. Drive faults are reported in r0947; F0001 indicates overcurrent, F0002 overvoltage, F0003 undervoltage, F0011 motor overload. Reference the fault table in the MM440 Operating Instructions.
Can I use a single MM440 to switch between PLC analog control and BOP keypad control instead of MOP?
Yes. Set P0700[1] = 1 and P1000[1] = 1 to put the BOP's green Start key in control of CDS1. The BOP will command a fixed 5 Hz; use the BOP arrow keys for fine adjustment. Note that this moves the local run authority off the panel push buttons, which may not match the operator's expectations on a retrofit.