1. Overview
The SIMATIC OP7 (order number 6AV3607-1JC20-0AX1) is a compact text-display operator panel from the Siemens SIMATIC HMI family, released in the late 1990s alongside the OP3, OP5, OP15 and OP17 series. Designed as a low-cost status/alarm/parameter terminal for SIMATIC S5, S7-200 and S7-300 lines, the OP7 fits cabinets where a graphical HMI is unnecessary but operator entry plus diagnostics are required. Configuration is performed with Siemens ProTool (the reference build is ProTool V6.0 with Service Pack 2), which compiles a binary project image transferred to the panel over an RS-232 TTY (20 mA current loop) or MPI link.
This reference covers the canonical install path for the OP7 on a modern Windows engineering workstation: where to obtain ProTool, the PC-to-panel cable, the parameter set that drives a successful transfer, and the field verification steps that confirm a working commission. A troubleshooting matrix and a migration pathway to WinCC flexible / TIA Portal are appended for legacy installations.
| Field | Specification |
|---|---|
| Order number (MLFB) | 6AV3607-1JC20-0AX1 |
| Commercial designation | SIMATIC OP7 |
| Display | LCD monochrome, 4 lines × 20 characters |
| Backlight | EL or LED, suffix dependent |
| Function keys | 8 system keys (F1–F8), 4 with soft-key labels |
| Status LEDs | 2 (fault + message present) |
| Power supply | 24 V DC ±20 %, ~250 mA |
| Power consumption | ≈ 6 W |
| Front cut-out | 138 mm × 68 mm (bezel 148 × 76 mm) |
| Real-time clock | Yes (CR2032 battery backup) |
| Flash memory | 256 KB non-volatile, 64 KB retain |
| Compiled-project ceiling | ≈ 192 KB (field-recommended, max 256 KB) |
| Tags | ≤ 1024 (ProTool) / ≤ 128 (ProTool Lite) |
| Alarms | 128 discrete + 32 analog |
| Recipes | 1 recipe, ≤ 16 entries |
| Project password | 4-digit numeric, enabled in compiler options |
2. Hardware Identification and Variant Ambiguity
Siemens released the OP7 under several order suffixes; the two relevant to the OP family are -0AX0 and -0AX1. They differ in on-board interfaces and are easy to confuse once a panel has been removed from service.
| Capability | -0AX0 | -0AX1 |
|---|---|---|
| TTY (20 mA) to PLC | Mandatory | Yes (compatibility) |
| MPI to S7-300/400 | No | Yes |
| PPI to S7-200 | Via TTY-PPI bridge | Native on board |
| PC download protocol | TTY only | TTY or MPI (PROFIBUS) |
| Compiled project ceiling | 192 KB | 256 KB |
| Battery | CR2032 | CR2032 |
| Approximate release year | 1995 | 1998 |
2.1 Suffix identification procedure
- Isolate and open the rear cover of the OP7 (24 V isolated first).
- Locate the CE/UL plate; the suffix appears after the dash on the second line (e.g.,
6AV3607-1JC20-0AX1). - Cross-check against Table 2; commit the resulting interface set before proceeding to cabling.
3. Configuration Software — ProTool Versions
ProTool is the legacy configuration toolkit for the SIMATIC OP/TP/MP panel series before WinCC flexible took over. The OP7 family is supported from ProTool V5.2 SP2 through V6.2 SP3. The version most often quoted as a reference build is ProTool V6.0 SP2 (internal build 6.0.0.4).
| Version | Service pack | OS support | Status for OP7 |
|---|---|---|---|
| ProTool V5.2 | SP2 | Windows 95/98/NT 4.0 | Legacy, common in S5-95U/F installations |
| ProTool V6.0 | SP2 | Windows NT 4.0/2000/XP | Reference build |
| ProTool V6.0 | SP3 | Windows XP/Server 2003 | Compatible, runs on Win7 with elevation |
| ProTool V6.2 | SP2/SP3 | Windows XP/Server 2003 | Final ProTool release |
| ProTool Lite | — | Embedded | Free, ≤ 128 tags, single project |
| WinCC flexible 2005+ | SP1+ | Windows XP/7 | Migration target |
ProTool is archived at the official Siemens Industry Online Support entry 6AV6581-3BX06-0DX0 (ProTool V6.0). Authentication requires a Siemens Industry Online Support account. Legacy installations are also present on the SIMATIC Documentation & Software DVD set (order code 6ES7 998-8XA01-8YE0). The reference manual for SIMATIC 500/505 tooling that references ProTool is published at Siemens entry ID 29034071.
ProTool installs the Device Catalogue, which lists every supported panel model. If the OP7 entry disappears, the catalog file OP.cat has been overwritten by a later ProTool version — reinstall the SP2 patch or restore OP.cat from the original media.
3.1 Project sizing for OP7
| Resource | Hard limit | Field-recommended ceiling |
|---|---|---|
| Screens | 20 | 12 |
| Tags (ProTool Lite) | 128 | 120 |
| Tags (ProTool full) | 1024 | 512 |
| Discrete alarms | 128 | 96 |
| Analog alarms | 32 | 24 |
| Recipes | 1 with 16 entries | 1 with 12 entries |
| Soft-keys | 4 paired with F1–F8 | 4 |
| User language faces | 1 | 1 |
| Area pointers | 3 (status, control, date/time) | 3 |
| Compiled project size | 256 KB | ≤ 192 KB |
4. PC ↔ OP7 Cabling and Converter Wiring
The OP7 was engineered before USB was standard on industrial PCs; the panel exposes a TTY (20 mA current loop) interface. Connecting a modern engineering workstation requires an RS-232 ↔ TTY converter, since a passive null-modem cable cannot drive a current-loop receiver.
| Cable / adapter | Siemens order code | Function |
|---|---|---|
| PC-TTY converter | 6ES7 901-3CB30-0XA0 | RS-232 ↔ 20 mA current-loop converter; standard issue for OP7 to PC transfers |
| PC-TTY prefabricated cable | 6XV1 440-2KH32 | Pre-wired RS-232 ↔ TTY cable with integrated converter |
| MPI cable (for -0AX1) | 6XV1 830-0EH10 | PROFIBUS FC standard cable for MPI download |
| USB ↔ RS-232 adapter | third-party (FTDI FT232) | Required if engineering PC has no DB9 serial port |
| USB ↔ MPI adapter | 6GK1 571-1AA00 | Direct MPI download on -0AX1 panels |
4.1 Internal wiring of the PC-TTY converter
The 6ES7 901-3CB30-0XA0 converter performs the level transition in a single box. The relevant wiring scheme is summarised below.
| PC DB9 pin | RS-232 signal | OP7 round (TTY) | Function |
|---|---|---|---|
| 2 | RXD | 3 (TA) | Data received OP7 → PC |
| 3 | TXD | 4 (TB) | Data transmitted PC → OP7 |
| 4 | DTR | 1 (T+) | +20 mA current source |
| 6 | DSR | 1 (T+) | +20 mA loop acknowledgment |
| 5 | SG | 2 (reference) | Signal ground |
| 7 | RTS | — | Handshake used by ProTool |
| 8 | CTS | — | Handshake used by ProTool |
The current loop sources 20 mA from pin 1 (T+) returning on pin 2 (T−). Reverse connection results in the panel reporting No PG/PC indefinitely. The round connector is keyed to prevent mirror insertion; an older alternative used a 4-pin Siemens TTY cable, order code 6XV1 440-1KH12.
5. Installing ProTool on a Modern Windows PC
- Back up the system prior to installing a 16-bit INF-companion ProTool driver if the installer prompts.
- Disable UAC or run the installer as Administrator (right-click → Run as administrator).
- Mount the SIMATIC Documentation & Software DVD (or the ProTool V6.0 ISO) and execute
Setup.exe. - Select ProTool Configuration and the matching Service Pack; tick Install Op-Catalog OPC.
- Insert the USB CodeMeter dongle when prompted (or plug the legacy parallel dongle into LPT1).
- Reboot. Confirm the ProTool menu group appears under Start → SIMATIC → ProTool.
- Open ProTool and select File → New. The OP7 entry should be present in the device list.
6. Building the OP7 Project
- New project: Open ProTool, File → New. In the device-selection dialog select OP7 under SIMATIC HMI → Text Devices.
- Project path: Use no spaces and ≤ 8 characters in the filename to avoid issues when cross-importing to STEP 5 / STEP 7 archives.
-
PLC selection: Pick the connected controller protocol and configure the COM port + baud rate:
- AS511 over TTY: 9600 bit/s, Even parity, 8 data, 1 stop.
- PPI to S7-200: 9600 bit/s, OP7 network address 1.
- MPI to S7-300/400 (0AX1): 187.5 kbit/s, OP7 address 1.
-
Area pointers: ProTool will request three area pointers. The defaults are:
- Status byte:
MW 0 - Control byte:
MW 2 - Date/time:
DB10 word(or set to none if unused)
- Status byte:
- Tags: Use the Tag Editor to point at a SIMATIC S7-300 data block (e.g., DB100). S5-95U/F projects reference flag byte, data word, or DB/DX parameters.
- Screens: Create up to 12 screens. Each screen defines which tags to display, alarm acknowledgement, and the soft-key actions.
- Alarms: Define discrete alarms (bit-triggered) and analog alarms (limit-based) referencing the same tags.
- Recipes: Optional. Map the recipe to a 16-entry array, often stored in DB50.
-
Compile: Project → Compile. ProTool produces a
*.pnzfile ready for transfer.
6.1 Tag definition example
Tag Name : "M1_Speed"
PLC : SIMATIC S7-300
Data area : Data Block
DB number : 100
Byte.Offset : 0.0
Length : 2 bytes
Type : INT (signed)
Display : Numeric, 5 digits, " rpm"
Limit 0 : 0 (yellow)
Limit 1 : 1500 (red)
Sampling cycle : 1 s
Acquisition : Continuous
6.2 Alarm definition (motor overload)
Alarm number : 27
Class : Fault
Trigger tag : "M1_Temp"
Trigger logic : > 85 °C, sustained 3 s
Acknowledgement : Operator acknowledged
Display screen : Screen_2
6.3 Soft-key action (start command)
F-key : F1 (soft-key "Run")
Action : Set Bit
PLC area : Output (PAB)
Address : A 8.0
Bit behaviour : Set to 1 on key-press; reset on key-release
7. Project Transfer Procedure (TTY)
- Connect the PC-TTY converter to the OP7 round (TTY) port; observe the converter LEDs transitioning to Ready.
- Power on the OP7. The panel displays a startup message followed by the home screen or the boot menu. When a project is missing or corrupted, the boot menu offers Transfer mode automatically.
- Press F2 + Insert (or, on -0AX1 suffixes, set the panel-side rotary switch to Download).
- In ProTool open File → Download → Settings. Configure the PC serial channel:
- PC interface:
COM1(or the COMx mapped to USB-RS232 if used) - Baud rate:
9600 bit/s(TTY) or187500 bit/s(MPI) - Handshake:
RTS/CTS - Parity:
Even - Data bits:
8 - Stop bits:
1
- PC interface:
- Click OK. Then File → Download → Start to send the compiled
*.pnz. - The OP7 progress indicator climbs to 100 %. The OP7 reboots automatically into run mode with the newly loaded project.
8. MPI Network Setup (0AX1 Variant)
When the panel carries the -0AX1 hardware suffix and exposes a 9-pin sub-D MPI port, the OP7 can join an MPI bus at 187.5 kbit/s. The MPI route is preferred for plants with a single PC engineer working on multiple panels.
| Parameter | Required value |
|---|---|
| OP7 MPI address | 1 (default; set ≥ the PLC master address + 1) |
| MPI baud rate | 187.5 kbit/s (must match PLC MPI baud rate) |
| Highest station address (HSA) | 31 (≤ 31 if no repeater; up to 126 with repeaters) |
| Bus terminator | 220 Ω between DB9 pin 3 (RxD/TxD-P) and pin 8 (RxD/TxD-N) at each end of the segment |
| Cable | 6XV1 830-0EH10, ≤ 1.5 m drop to the panel |
| Total bus length | ≤ 50 m at 187.5 kbit/s; 1000 m with repeater (6GK1 500-0DA00) |
9. Operator Acceptance Test (Commissioning Checklist)
- After download the OP7 displays the home screen; verify each configured tag shows the correct value read from the PLC.
- Force a bit in the connected PLC using STEP 7 or a programmer; verify the OP7 redraws the affected screen within one update cycle (typically ≤ 1 s).
- Push the operator past a configured limit value (e.g., M1_Speed > 1500 rpm); confirm the analog alarm fires and is recorded in the message list.
- Press each soft-key in turn; confirm the configured bit toggle, screen change, or recipe load.
- Cycle panel power; the project, clock, and recipe data must survive. If any data resets to zero, replace the CR2032 battery (panel-side compartment).
- Run for 30 minutes without operator interaction; the OP7 should not enter a fault state nor require a watchdog reset.
- Capture the project file
*.pnzto the maintenance folder and label the project archive per the plant's engineering convention.
9.1 Battery replacement
- Remove 24 V from the OP7.
- Loosen the rear battery compartment cover.
- Replace the CR2032 cell observing polarity (+/−).
- Re-apply 24 V and re-set the real-time clock via the OP7 Setup menu.
10. Troubleshooting Matrix
| Observed symptom | Most likely root cause | Remediation |
|---|---|---|
| "No PG/PC" indefinitely | TTY converter missing or TTY current-loop polarity reversed | Verify 6ES7 901-3CB30-0XA0 status LEDs; check T+ / T− pair; cycle OP7 power |
| Transfer aborts at ~25 % | Baud-rate / parity mismatch | Force 9600 bit/s, 8-E-1, RTS/CTS; disable FIFO on the PC COM port in Device Manager |
| Transfer aborts at ~75 % | Compiled project > 192 KB | Trim alarm or screen count; reduce recipes |
| OP7 displays "PLC not responding" | Wrong COM port or PLC powered off | Open STEP 7, run PLC → Set PG/PC Interface; verify PLC supply is 24 V |
| Alarm list empty despite alarm conditions | Status/control pointer mismatch | Confirm ProTool pointers match DB in PLC (e.g., MW 0 / MW 2) |
| Garbage characters on screen | MPI baud mismatch / unterminated bus | Set bus to 187.5 kbit/s; fit 220 Ω terminator at both ends |
| F-keys ignored | Configured as event with no action | Open F-key properties → assign Set Bit to a valid DB or PAB |
| OP7 reboots after every download | Compiled size > flash capacity | Target ≤ 192 KB compiled output; remove unused tags |
| Clock resets on power cycle | Dead CR2032 battery | Replace battery; reset clock via OP7 Setup menu |
| "Library missing K00F00000" | ProTool runtime not patched | Apply ProTool V6.0 SP2 patch from Siemens DVD |
| Boot menu reappears after successful download | Verification error / incomplete image | Repeat the transfer; if persistent, re-check area pointer configuration |
11. Migration to OP73 / WinCC flexible
The OP7 family has been replaced on Siemens price lists by the OP73 (same text-display form factor) and the KTP400 Comfort for graphical applications. Plants that already own an OP7 and wish to preserve the engineering investment can migrate an existing project using WinCC flexible.
- Install WinCC flexible 2005 SP1 or later.
- Open the WinCC flexible project wizard; select Migrate.
- Choose the original
*.pnzas the source file. - Select the target device OP73 mono; the wizard preserves tags, alarms, and screens within OP73 capacity.
- Re-check the area pointers — WinCC flexible defaults to DB pointers rather than MW.
- Compile and transfer to OP73.
12. Frequently Asked Questions
Which software is required to configure the Siemens SIMATIC OP7 6AV3607-1JC20-0AX1?
ProTool V6.0 (preferably with Service Pack 2) is the canonical configuration software. The package entry is archived at Siemens Industry Online Support — 6AV6581-3BX06-0DX0. If ProTool is unavailable, the WinCC flexible migration wizard can open a back-up of the original *.pnz project.
What cable is needed between the engineering PC and the OP7?
Use the Siemens PC-TTY converter with order code 6ES7 901-3CB30-0XA0 to interface the PC's RS-232 (or USB-RS232 adapter) to the OP7's TTY port. The integrated-cable variant referenced as 6XV1 440-2KH32 supplies the same role but should be confirmed to contain a TTY/RS-232 converter inside its housing. For -0AX1 panels a PROFIBUS cable (6XV1 830-0EH10) can be used on the MPI port.
Which PLCs can be connected to the OP7?
SIMATIC S5 (AS511 over TTY), SIMATIC S7-200 (PPI or TTY), and SIMATIC S7-300/400 (MPI on -0AX1, or TTY bridge) are natively supported. For non-Siemens PLCs, ProTool V6.2 includes Modbus RTU but the OP7 end still requires an external Modbus-to-TTY converter.
Can ProTool V6.0 run on Windows 10 or 11?
Yes, in practice. Set ProTool.exe to Windows XP SP3 compatibility mode, run as Administrator, install the CodeMeter runtime for the USB license dongle, and disable the Microsoft FIPS 2000 hashing policy. ProTool V6.2 SP3 is more stable on Windows 7.
What is the maximum number of tags an OP7 project can hold?
ProTool Lite limits the project to 128 tags; the full ProTool supports 1024 tags. Recommended field ceilings are ≤ 120 and ≤ 512 tags respectively to leave headroom for alarm / recipe growth.
How is the OP7 internal battery replaced?
Remove power to the panel, loosen the rear battery compartment cover, and replace the CR2032 cell observing polarity (+/−). Re-apply power and re-set the real-time clock via the OP7 Setup menu. A discharged battery makes the clock reset and may cause recipe data loss.
What is the SIMATIC 500/505 reference that ProTool can also be used for?
Siemens kept a single configuration tool chain bridging SIMATIC S5 (505 family) and the OP panel series. The reference manual at Siemens Industry Online Support entry ID 29034071 documents ProTool's role in SIMATIC 500/505 commissioning.
Why does my OP7 still display "Transfer mode" after a successful download?
The boot menu reappears when the most recent transfer flagged a verification error, or when an incomplete image is held in flash. Repeat the transfer; if the boot menu persists, verify the area pointers and ensure the COM port is mapped to the same physical DB9 or USB-serial adapter.