Overview
Siemens Sm@rtServer (formerly branded as Sm@rtService in WinCC Flexible 2008) is the integrated web server in WinCC Runtime Advanced, Comfort Panels, and the TIA Portal HMI family. It exposes the running HMI project over TCP/IP so a remote PC browser, custom HTML page, or OPC client can read and write PLC tags without installing the full TIA Portal on the remote machine. Typical use cases include remote tank-level monitoring, pump-station telemetry, and supervisory dashboards where a thin client only needs tag values and acknowledge-only screens.
The most common failure when first deploying Sm@rtServer is no connection between the engineering station, the HMI/PC runtime, and the PLC on a shared switch. The browser shows "Cannot connect to server," the runtime logs 0x80040D14 or "Web server not started," or a script call such as GetVar("FillLevel_Water") returns an empty string. These faults are almost always the result of a missing web-server activation, a closed HTTP port, an empty user list, or a tag-name vs. absolute-address mismatch in the HTML script.
This reference consolidates the WinCC Flexible Options Getting Started and the modern WinCC Runtime Advanced / Comfort Panel web server documentation into one commissioning procedure. It targets the following hardware combinations:
- PC running WinCC Runtime Advanced (RT) on Windows 10/11, Ethernet-attached to S7-1200 or S7-1500.
- Comfort Panel TP700 / TP900 / TP1200 attached via PROFINET to an S7-1200/1500.
- Legacy PC station running WinCC Flexible 2008 SP5 with the Sm@rtService option.
Architecture and Topology
The reference topology mirrors the source setup: a single Ethernet switch fans out three nodes — the engineering/service PC, the runtime PC (or the HMI panel), and the S7 PLC. There is no router between them, so all three devices must share the same IP subnet.
[ Service PC ] [ Runtime PC / Panel ] [ S7-1200/1500 ] IP 192.168.0.10 <----> IP 192.168.0.20 (Sm@rtServer) <--> IP 192.168.0.30 Browser (port 80) SWITCH WinCC RT / Comfort PROFINET / S7
Required components and addressing ranges:
| Node | Function | Default IP | Open Ports |
|---|---|---|---|
| Service PC | Remote browser, script client | 192.168.0.10 / 24 | Outbound 80, 443, 102 (S7 optional) |
| Runtime PC / Comfort Panel | Hosts Sm@rtServer, web pages | 192.168.0.20 / 24 | Inbound 80 (HTTP), 443 (HTTPS), 102 (S7) if enabled |
| S7-1200 / S7-1500 PLC | Tag data source | 192.168.0.30 / 24 | Inbound 102 (ISO-on-TCP / S7 communication) |
| Ethernet Switch | Layer-2 fan-out, no routing | n/a | n/a |
Sm@rtService (WinCC Flexible 2008) vs. Sm@rtServer (TIA Portal / RT Advanced)
The source project uses the older WinCC Flexible 2008 product. The option key installed in the image was "Sm@rtService for WinCC flexible". In current TIA Portal releases the same capability is called Sm@rtServer and ships as the "WinCC Sm@rtServer" option in WinCC Runtime Advanced, or is built-in on every Comfort Panel from firmware V11 onward. The conceptual model is identical:
- The runtime hosts an HTTP server (port 80 by default, configurable up to 65535).
- Authorized users browse to
http://<runtime-ip>/and see standard service pages (start page, diagnostics, recipe views, alarm views). - User-authored HTML pages in the project can call
GetVar("TagName")/SetVar("TagName", value)to read/write HMI tags. The runtime then forwards the request to the connected PLC via the configured HMI connection.
If the project is being migrated from WinCC Flexible 2008 to TIA Portal V16/V17/V18/V19/V20, recompile the project on the new runtime. The legacy "Options" installer (Sm@rtService) is no longer licensed; the modern equivalent is the "WinCC Runtime Advanced" license with the Sm@rtServer add-on (article number 6AV2107-0CR00-0BB0 for V16/V17 single license) or a Comfort Panel image (built-in).
Prerequisites
- Runtime license: WinCC Runtime Advanced with the Sm@rtServer option, or a Comfort Panel image. Verify in TIA Portal: Project tree → Runtime settings → Licenses. Without the option, the web server is present in the image but refuses remote connections and returns HTTP 402.
- Web server activation in the runtime settings: Runtime settings → Services → Web server → Enable web server on this device. This checkbox is off by default; the missing check is the single most common cause of "cannot establish a connection."
-
HMI connection between the runtime and the PLC must be online (green status in the runtime diagnostics). Without an active connection,
GetVar()still returns the last cached value or empty, but writes are silently dropped. - User list with at least one user assigned the HMI Web Administrator or Web User role. The default image ships with zero users; remote logins fail with HTTP 401 until a user is created.
- Firewall rule on the runtime PC permitting inbound TCP 80 (and 443 if HTTPS is enabled). The Windows firewall blocks inbound HTTP by default on Windows 10/11.
- Network reachability: ping the runtime IP from the service PC; if the ping fails, the switch port is wrong or the subnet mask is mismatched. If the ping succeeds but the browser fails, the firewall or web server activation is the cause.
Step-by-Step Configuration
Step 1 — Assign Static IPs
Configure static IP addresses on all three nodes. Avoid DHCP for HMI/PLC nodes so the browser bookmark does not break across reboots.
- PC: Control Panel → Network → Ethernet → Properties → IPv4 → Use the following IP address:
192.168.0.10 / 255.255.255.0. - Runtime PC: Same path, IP
192.168.0.20 / 24. - S7-1200/1500: In TIA Portal, Device properties → PROFINET interface → Ethernet addresses → IP address. Program into the PLC and download. Alternatively set online via the CPU display (S7-1500) or the TIA "Online → Accessible nodes" assignment.
Step 2 — Activate the Web Server
In TIA Portal (or WinCC Flexible for legacy projects):
- Open the HMI device configuration.
- Navigate to Runtime settings → Services → Web server.
- Enable "Web server on this device".
- Select HTTP port (default 80) and HTTPS port (default 443) if encryption is required.
- For HTTPS, generate or import an X.509 certificate. Self-signed certificates trigger a browser warning; the warning can be accepted for commissioning.
Reference the standard service pages of the web server, as documented in the TIA Portal V20 manual: Service pages of the web server (Panels, Comfort Panels, RT Advanced).
Step 3 — Configure User Administration
Per the official "Remote Panels / RT Advanced" commissioning guide, the steps are:
- In the runtime settings, click User Administration.
- Create a user (e.g.
SoapUser) with a strong password. - Assign the role HMI Web Administrator for full read/write, or HMI Web User for read-only of selected tags.
- Apply. The user list is part of the runtime image and must be downloaded to the runtime.
For "Close with runtime" behavior (closing the Sm@rtServer window also stops the runtime), configure the same user for the local runtime session. Source: Remote Access to WinCC Runtime Advanced (PDF, Siemens Support, 109476153).
Step 4 — Define HMI Tags and Connections
Create the tags that will be exposed to the web. The HMI tag can be symbolic (e.g. FillLevel_Water) or an absolute PLC address (e.g. DB1.DBD20). Symbolic names are strongly recommended for web scripting because they remain stable across PLC address changes.
| HMI Tag | PLC Address | Data Type | Access Direction |
|---|---|---|---|
| FillLevel_Water | %DB1.DBD20 | Real | Read-only |
| Pump1_Cmd | %DB1.DBX30.0 | Bool | Read/Write |
| Alarm_Active | %DB1.DBX40.0 | Bool | Read-only |
Make sure the HMI connection (e.g. HMI_Connection_1) is bound to the PLC at 192.168.0.30 with rack/slot 0/1 (S7-1500 default) or 0/0 (S7-1200 default). The connection mode must be "Active" on the HMI side; the PLC is passive.
Step 5 — Author Custom HTML Pages
Custom HTML pages are placed in the project under HMI → HTML pages and downloaded with the runtime. The runtime substitutes tag placeholders in the served HTML. A minimal page that displays a tag and a write-back button:
<html>
<head><title>Tank Level</title></head>
<body>
<h1>Tank Level Monitor</h1>
<p>Current level: <b><!--@FillLevel_Water--></b> m</p>
<form method="post" action="set.html">
Setpoint: <input name="Pump1_Cmd" type="checkbox" value="1"> Pump ON
<input type="submit" value="Apply">
</form>
</body>
</html>
For dynamic refresh without page reload, use the runtime's VBScript-like functions inside the HTML page (the runtime interprets the <script> blocks at serve time). Per the WinCC flexible Getting Started Options manual, the correct call is:
<script>
var v = GetVar("FillLevel_Water");
document.write("Level = " + v + " m");
</script>
GetVar() accepts only the HMI tag symbolic name. Passing an absolute address such as DB1.DBD20 will not resolve; the runtime returns an empty string and logs a "Tag not found" warning. If your project only has absolute addresses, create a wrapper HMI tag with a symbolic name that points to the same PLC address.Step 6 — Compile and Download
Compile the HMI project, then download the runtime image to the panel or PC runtime. The Sm@rtServer starts automatically when the runtime starts. If recipes are imported via Sm@rtService HTML pages, the runtime must be restarted for the new recipes to become active — this is a documented behavior, not a bug. See: Service pages of the web server.
Verification Procedure
- From the service PC, open a browser and navigate to
http://192.168.0.20/. The expected response is the Sm@rtServer start page (Comfort Panels display a Siemens logo, the project name, and the firmware version). If the page loads, Layer 3 connectivity and the web server are healthy. - Click Diagnostics on the start page. Confirm the HMI connection to the PLC shows Connected in green.
- Open the project HTML page (e.g.
http://192.168.0.20/index.html). Verify theFillLevel_Waterplaceholder is replaced with a real numeric value, not the literal text<!--@FillLevel_Water-->. - Submit the write form (Pump ON). Confirm on the PLC side via TIA "Monitor & Modify" that the bit at
DB1.DBX30.0transitions to 1 within one cycle (typical scan 50–200 ms). - Force a controlled PLC stop or disconnect. The HTML page should show "--- (no connection)" or the last cached value, and the diagnostics page should show the connection in red. This confirms the runtime is correctly handling loss of the PLC link rather than freezing the browser.
- Reboot the runtime and confirm the start page loads within 30–60 s. Comfort Panels are typically up in 20 s; PC runtimes with antivirus can take 60–90 s.
Network, Firewall, and Port Reference
| Service | Protocol / Port | Direction | Required For |
|---|---|---|---|
| Sm@rtServer HTTP | TCP 80 (configurable) | Inbound to runtime | Standard service pages, custom HTML |
| Sm@rtServer HTTPS | TCP 443 | Inbound to runtime | Encrypted pages, certificate-based auth |
| S7 Communication | TCP 102 (ISO-on-TCP) | Runtime ↔ PLC | Tag read/write via HMI connection |
| PROFINET | UDP 34964, 34963 | Runtime ↔ PLC | Discovery, diagnostics (LLDP, DCP) |
| DNS | UDP 53 | Optional | Hostname resolution (skip if using IPs) |
On the runtime PC, allow inbound traffic with Windows Firewall with Advanced Security:
netsh advfirewall firewall add rule name="Sm@rtServer HTTP" dir=in action=allow protocol=TCP localport=80
netsh advfirewall firewall add rule name="Sm@rtServer HTTPS" dir=in action=allow protocol=TCP localport=443
netsh advfirewall firewall add rule name="S7 Comm" dir=in action=allow protocol=TCP localport=102
For Comfort Panels, the firewall is part of the panel image and the relevant ports are open by default. If a corporate switch has port-based ACLs, request that 80/443/102 be unrestricted between the service-PC and the panel VLAN.
Troubleshooting Matrix
| Symptom | Likely Cause | Diagnostic | Remediation |
|---|---|---|---|
| Browser: "Site cannot be reached" | Wrong IP, firewall, cable |
ping 192.168.0.20 from service PC |
Fix IP, swap cable, add firewall rule |
| Browser: HTTP 401 Unauthorized | No users defined | Try anonymous, check user list in project | Create user, assign HMI Web role |
| Browser: HTTP 402 Payment Required | Sm@rtServer option not licensed | TIA → Runtime → Licenses | Install license, re-transfer license key |
| Browser: HTTP 404 on index.html | HTML page not in image | Check project → HTML pages tree | Re-download project with HTML pages |
| Page loads but tag value is empty | Symbolic name missing / HMI tag offline | Diagnostics page → HMI connection | Add HMI tag with symbol, fix connection |
| GetVar("DB1.DBD20") returns "" | Absolute address not allowed | Inspect runtime log for "Tag not found" | Replace with symbolic HMI tag name |
| Recipes imported via web do not appear | Runtime not restarted | n/a | Restart WinCC Runtime; per Siemens V20 manual |
| Slow page load > 5 s on LAN | Antivirus scanning HTML / proxy | Disable AV, retest; check WinDefend logs | Add runtime folder to AV exclusion |
| Service PC sees runtime, runtime cannot reach PLC | Wrong PLC IP / rack-slot / subnet | TIA Online → Accessible nodes | Correct HMI connection properties, ping PLC |
| HTTPS works, HTTP fails | Mixed-content policy, browser upgrade | Test in private/incognito window | Disable HTTPS-only mode in browser, or use HTTPS |
Scripting Reference: GetVar / SetVar and Alternatives
The runtime-side script engine inside the served HTML is intentionally limited compared to browser JavaScript. The documented built-ins are:
| Function | Syntax | Returns | Notes |
|---|---|---|---|
| GetVar | GetVar("TagName") |
String | Symbolic name only; absolute addresses rejected |
| SetVar | SetVar("TagName", value) |
Boolean (true = success) | Writes through HMI connection; subject to user rights |
| GetVarEx | GetVarEx("TagName") |
Variant (numeric preserved) | Recommended for floating-point tags |
| GetTagInfo | GetTagInfo("TagName") |
String (quality code) | Use to detect bad/stale values |
Example — periodic refresh of a level value without page reload (using META refresh; AJAX is not supported by the runtime's script engine):
<html>
<head>
<meta http-equiv="refresh" content="5">
</head>
<body>
<h2>Level: <script>document.write(GetVarEx("FillLevel_Water"));</script> m</h2>
<p>Status: <script>document.write(GetTagInfo("FillLevel_Water"));</script></p>
</body>
</html>
For high-frequency updates (> 2 Hz) or large tag counts, use the OPC UA server of the runtime (TIA Portal → Runtime → Services → OPC UA Server) rather than custom HTML. The OPC UA server can also expose the same tags to SCADA, historians, and Python clients without HTML round-trips.
Migration Notes: WinCC Flexible 2008 → TIA Portal
If the source project is being upgraded because the Sm@rtService option is end-of-life:
- Open the project in TIA Portal (use “Migrate project” wizard if it is a WinCC Flexible 2008 SP5 archive).
- Re-enter the option license (article 6AV2107-0CR00-0BB0 for V16, 6AV2107-0CR05-0BB0 for V17).
- Recompile and re-download the runtime. The compiled Sm@rtService HTML from the legacy project will be converted, but VBScript blocks must be reviewed — some legacy VBS functions have no equivalent in the modern runtime.
- Re-test all
GetVar()calls. TIA Portal V20 enforces symbolic tag names; any direct addressDB1.DBD20must be wrapped in an HMI tag with a name such asDB1_DBD20(underscore, no dot) to remain valid.
Safety and Operational Caveats
Pump1_Cmd over the web is not a substitute for hard-wired safety interlocks.For tank-level control specifically, the recommended design is:
- Level sensing and pump on/off in PLC ladder / SCL; PLC owns the safety envelope.
- HMI displays the level and accepts setpoint changes; HMI writes the setpoint to the PLC, the PLC applies its own safety limits.
- Sm@rtServer exposes the level for remote viewing; remote control is restricted to a separate "Remote-Authorized" user with an explicit confirm step.
FAQ
Why does the browser show "Cannot connect to server" even though the runtime is running?
The most common cause is the Web server checkbox being disabled in the runtime settings. Open TIA Portal, navigate to Runtime settings → Services → Web server, enable it, and re-download the project. Also verify Windows Firewall allows inbound TCP 80 (HTTP) and TCP 102 (S7) on the runtime PC.
Can I use GetVar("DB1.DBD20") in my HTML page?
No. GetVar() and SetVar() require the symbolic HMI tag name. Absolute addresses like DB1.DBD20 are rejected and the function returns an empty string. Create a symbolic HMI tag (for example FillLevel_Water) that points to %DB1.DBD20, then call GetVar("FillLevel_Water").
Imported recipes via Sm@rtService HTML are not visible in the runtime — what now?
This is documented behavior: after importing recipes through the Sm@rtServer web pages, the runtime must be restarted for the new recipes to take effect. Stop and start the WinCC Runtime (or reboot the Comfort Panel). Reference the TIA Portal V20 service-pages manual entry on recipe handling.
Which port does Sm@rtServer use, and can I change it?
Default is TCP 80 for HTTP and TCP 443 for HTTPS. The port is configurable in Runtime settings → Services → Web server → Port. When changing the port, update any bookmarks and re-configure any corporate proxy that whitelists the runtime IP.
Is the Sm@rtService option from WinCC Flexible 2008 still available?
The legacy Sm@rtService option key has been replaced by the Sm@rtServer component built into WinCC Runtime Advanced and every Comfort Panel (TP700 / TP900 / TP1200 / TP1500 / TP1900 / TP2200). The modern equivalent runtime license is article 6AV2107-0CR00-0BB0 (TIA V16/V17) or its successor for the active TIA Portal version.