Overview: Telegram vs. Digital I/O Control on SINAMICS G120C
The SINAMICS G120C is a compact, modular drive platform designed for wall-mount and motor-mounted installations in the 0.55 kW to 132 kW power range. When integrating the drive into an S7-1200 or S7-1500 control system over PROFINET, two fundamentally different command paths exist for commanding start, stop, coast, and speed setpoint:
- Digital I/O control: Start/stop and direction bits are wired through 24 V digital outputs on the PLC to discrete inputs on the Control Unit (CU). Speed setpoint may be analog (0–10 V) or fixed via parameter.
- PROFIdrive telegram control: Control word 1 (STW1) and a normalized speed setpoint (NSOLL) are packed into a single PROFIdrive telegram and transferred cyclically over PROFINET. The drive returns status word 1 (ZSW1) and actual speed (NIST).
Field experience on retrofit projects — particularly where legacy hard-wired systems are being migrated to PROFINET in incremental stages — strongly favors telegram-based command. The control bits are sampled by the drive on the same PROFINET cycle that delivers the setpoint, eliminating the scan-time, relay-pull-in, and field-wiring race conditions that plague multi-wire digital control. This reference documents how to configure a minimal free PROFIdrive telegram between an S7-1200 and a G120C using SINAMICS Starter, the correct STW1 / ZSW1 bit map, and the typical commissioning workflow that delivers reliable start, stop, coast, and emergency stop behavior.
Prerequisites: Hardware, Firmware, and Software Stack
Before commissioning, verify that the hardware, firmware, and software versions on site support the configuration described here.
Hardware
-
SINAMICS G120C with a PROFINET-capable Control Unit (CU230P-2 PN, CU240E-2 PN, or CU240S2 PN-F). Confirm the CU type by reading the rating plate or via parameter
r0001. - SIMATIC S7-1200 CPU with PROFINET interface (CPU 1211C, 1212C, 1214C, 1215C, 1217C, or 1214FC / 1215FC for fail-safe variants).
- PROFINET cable (Cat 5e minimum, shielded) and an industrial switch if multiple PROFINET nodes are present.
- PROFINET device name labels for the G120C; the device name must be unique on the subnet.
Firmware
| Component | Recommended Firmware | Notes |
|---|---|---|
| G120C CU240E-2 PN | V4.7 SP10 or later | Adds full PROFIsafe / Safety Integrated support via PROFIsafe over PROFINET (PN-F variants only). |
| G120C CU230P-2 PN | V4.7 SP10 or later | Pump/fan/HVAC profile. |
| S7-1200 CPU | Firmware V4.4 or later | Required for SinaSpeed FB compatibility in TIA Portal V15.1+. |
| SINAMICS Starter | V5.4 SP3 / HSP with V4.7 drive support | HSP0160 or later for G120 V4.7. |
| TIA Portal (if using StartDrive) | V15.1 with HSP0185 | Optional — Starter is preferred for free telegram configuration. |
Software Stack
- SINAMICS Starter (or StartDrive in TIA Portal V15.1+) with the appropriate Hardware Support Package (HSP) installed.
- SinaSpeed function block library (part of the SINAMICS blocks for TIA Portal / STEP 7). Library identifiers: "SINAMICS" or "SINAMICS_S7-1200".
- GSD file for the G120C installed in TIA Portal or STEP 7 (GSDML-Vx.x-Siemens-Sinamics-G120C-xxxxxxxx.xml).
PROFIdrive Telegram Architecture on the G120C
PROFIdrive telegrams on the G120C are defined by parameter p0922 (IF1 PROFIdrive PZD telegram selection). Standard telegrams (e.g., 1, 2, 3, 20, 352) are pre-defined; for a minimal custom layout a free telegram is configured via p0922 = 999 with the PZD setpoints and actual values selected explicitly under p2071 / p2079.
Recommended Minimal Free Telegram Layout
| Direction | PZD Word | Signal | SINAMICS Parameter | Meaning |
|---|---|---|---|---|
| PLC → Drive | PZD1 | STW1 | p2051[0] = (control word source) | Control word 1 — ON/OFF1, OFF2, OFF3, enable, ramp enable, setpoint enable, fault acknowledge |
| PLC → Drive | PZD2 | NSOLL | p2051[1] = (speed setpoint) | Normalized speed setpoint (4000 hex = 100 % of p2000) |
| Drive → PLC | PZD1 | ZSW1 | p2050[0] = (status word 1 source) | Status word 1 — ready, enabled, fault, coast active, etc. |
| Drive → PLC | PZD2 | NIST | p2050[1] = (actual speed) | Normalized actual speed (4000 hex = 100 % of p2000) |
Configuring a Free Telegram in SINAMICS Starter
- Open the project in Starter and go online to the G120C. Accept any firmware version warning if the G120C is older than the HSP.
-
Select the telegram: Navigate to Configuration → Communication → IF1 PROFIdrive PZD telegram selection and set
p0922 = 999(free telegram configuration). -
Configure PZD setpoints (PLC → Drive): Under Free telegram configuration → PZD setpoints (p2051):
- Set
p2051[0] = (STW1 source). By default Starter routes to the BICO sourcer2090.0, which is the receive word 0 from IF1. Leave at default unless you require BICO re-routing. - Set
p2051[1] = (NSOLL source). The default target is the main setpoint connector; verifyp1070[0] = 2050[1]so the received speed setpoint is fed to the ramp-function generator input.
- Set
-
Configure PZD actual values (Drive → PLC): Under Free telegram configuration → PZD actual values (p2050):
- Set
p2050[0] = 53(status word 1, ZSW1). - Set
p2050[1] = 21(smoothed actual speed, NIST).
- Set
-
Set the reference speed:
p2000defines the speed value that corresponds to 100 % setpoint (4000 hex). Setp2000to the motor nameplate rated speed in RPM (default 1500 RPM). -
Set the bus cycle: In the PLC, configure the PROFINET send clock (typically 1 ms for motion, 4 ms for non-motion applications). Verify the G120C's PROFINET cycle matches; mismatched cycles trigger
F08501"PROFINET communication fault" orA08502warning. - Copy RAM to ROM and perform a power cycle to load the new telegram configuration.
p0922 = 999, parameters p2071 and p2079 are auto-derived. Read r2050 and r2051 to confirm the mapping matches the values above before commissioning.
Control Word 1 (STW1) Bit Map and Sequencing Rules
Control Word 1 (STW1) is the primary command interface for PROFIdrive profile drives. The bit definitions for the G120C conform to the PROFIdrive profile V4.1 (AC1) and are summarized below.
| Bit | Designation | 0 | 1 | Notes |
|---|---|---|---|---|
| 0 | ON / OFF1 | OFF1 (ramp-down to standstill) | ON (drive energizes) | Edge-sensitive rising edge required to start after a stop. |
| 1 | OFF2 | Coast to stop (pulse inhibit, no ramp) | OFF2 inactive | Must be 1 to permit run. |
| 2 | OFF3 | Fast stop (ramp p1135) | OFF3 inactive | Must be 1 to permit run. |
| 3 | Enable/Inhibit operation | Inhibit (pulse inhibit) | Enable (pulses enabled) | Logical AND with OFF1/OFF2/OFF3. |
| 4 | Ramp-function generator enable | RFG output frozen | RFG enabled | Used for jog/quick-stop interaction. |
| 5 | Continue at ramp-function generator output | Freeze setpoint | Continue | Used with bit 4. |
| 6 | Setpoint enable | Setpoint = 0 | Setpoint enabled | Set to 1 to allow NSOLL to drive speed. |
| 7 | Fault acknowledge | No effect | Edge 0→1 acknowledges faults | Self-clearing edge; reset bit to 0 after acknowledgment. |
| 8 | Jog bit 0 | — | Jog via p1058 | Lower priority than ON/OFF1. |
| 9 | Jog bit 1 | — | Jog via p1059 | Lower priority than ON/OFF1. |
| 10 | Control by PLC | Drive ignores process data | Drive follows process data | Critical — must be 1 for telegram control. |
| 11 | Reserved | — | — | Maintain 0. |
| 12 | Reserved | — | — | Maintain 0. |
| 13 | Motor potentiometer raise | — | Raise | When MOP is configured as setpoint source. |
| 14 | Motor potentiometer lower | — | Lower | When MOP is configured as setpoint source. |
| 15 | Reserved | — | — | Maintain 0. |
Mandatory Run Sequence in STW1
For the drive to release the pulses and accelerate to setpoint, the following bits must be true simultaneously:
- Bit 0 (ON/OFF1) = 1
- Bit 1 (OFF2) = 1
- Bit 2 (OFF3) = 1
- Bit 3 (Enable operation) = 1
- Bit 6 (Setpoint enable) = 1
- Bit 10 (Control by PLC) = 1
The drive evaluates STW1 once per PROFINET cycle (typically every 1–4 ms) and applies the safety AND of all bits before energizing the IGBTs. Telegram delivery guarantees that all bits arrive simultaneously and on the same bus cycle.
Status Word 1 (ZSW1) Bit Map for Returned Diagnostics
ZSW1 returns the drive's response to the PLC on every PROFINET cycle. The PLC program should monitor ZSW1 to verify the drive is actually in the commanded state.
| Bit | Designation | 0 | 1 | Notes |
|---|---|---|---|---|
| 0 | Ready to switch on | Not ready | Ready (no fault, mains OK) | Pre-condition for ON. |
| 1 | Ready to operate | Not ready | Ready (DC bus charged, no inhibit) | Setpoint can be enabled. |
| 2 | Operation enabled | Pulses inhibited | Pulses enabled | Drive is actively controlling motor. |
| 3 | Fault present | No fault | Fault active | Read r0947/r0948. |
| 4 | Coast stop not activated | OFF2 active | OFF2 inactive | Mirrors STW1 bit 1. |
| 5 | Quick stop not activated | OFF3 active | OFF3 inactive | Mirrors STW1 bit 2. |
| 6 | Switching on inhibited | Not inhibited | Inhibited (ON command blocked) | Re-arm STW1 to clear. |
| 7 | Alarm present | No alarm | Alarm active | Read r2122/r2123. |
| 8 | Speed setpoint/actual deviation | Within tolerance | Outside tolerance window | Use p2161/p2163 thresholds. |
| 9 | Control request | Local control | PLC control requested | Confirms telegram is in control. |
| 10 | f ≥ p1080 (zero speed threshold) | Below zero speed | Above or equal zero speed | Use p1080 to set. |
| 11 | f ≥ p1082 (max speed threshold) | Below max | At or above max | Compare with p1082. |
| 12 | Motor overload | No warning | Thermal model warning | Cross-check I²t utilization r0034. |
| 13 | Motor direction | Reverse (negative) | Forward (positive) | Reflects actual direction. |
| 14 | Torque limit reached | Below limit | At or above limit | Useful for soft-start current limit. |
| 15 | Reserved | — | — | — |
Why Telegram Control Is More Reliable Than Digital Outputs
A common retrofit pattern when migrating from legacy hard-wired controls to PROFINET is to "leave the digital wiring in place for now" and only convert the speed setpoint to PROFINET. This preserves risk but introduces a class of failure modes that are not visible at design time:
Sources of Latency in Digital I/O Control
- PLC scan time: The PLC reads inputs, executes logic, and writes outputs at the end of the scan cycle. On an S7-1200 this can range from 1 ms (small program) to 10 ms (large program, organization blocks, and motion OB's).
- Digital output update: On transistor outputs, the propagation delay is ~50 µs. On relay outputs (S7-1200 Rly variants), mechanical pull-in adds 5–15 ms and bounce time can extend another 2–8 ms.
- Field wiring: Cable capacitance and noise filtering on the drive's 24 V inputs add another 0.5–3 ms of RC delay.
-
Drive input scan: The G120C scans digital inputs every 1 ms (parameter
p0799or as configured). Inputs can be debounced viap0797/p0798.
The cumulative latency from "PLC logic asserts bit" to "drive IGBTs energize" can therefore exceed 20 ms on relay-output S7-1200 systems. During that 20 ms window, the PLC has already started the next scan and may have changed other outputs. If the PLC issues a sequence of commands that the drive interprets out of order, the drive may end up in a state the PLC did not command.
Timing Failure Modes: The OFF1/OFF2 Race Condition
Consider the following PLC logic sequence on a legacy system using digital I/O control:
Initial drive state: OFF1 = 0 (stopped), OFF2 = 0 (coast active), OFF3 = 1.
PLC scan N: Logic decides to start the drive. Sets OFF1 = 1 and OFF2 = 1 on outputs O:0 and O:1.
End of scan N: Output image is written to physical outputs. With a relay output module, the O:0 relay pulls in before the O:1 relay due to mechanical tolerance — let's say O:0 (OFF1) closes 4 ms after the command, while O:1 (OFF2) closes 9 ms after the command. The drive's input scan runs at 1 ms intervals.
The drive's digital input scanner sees the following sequence:
- T=0 ms: OFF1 = 0, OFF2 = 0 (start of sequence — both still open)
- T=4 ms: OFF1 = 1, OFF2 = 0 — drive logic: OFF2 active → coast command, OFF1 ignored
- T=9 ms: OFF1 = 1, OFF2 = 1 — drive would now run, but the OFF2 trigger at T=4 ms has latched the coast inhibit; depending on parameterization, the drive may require a fresh OFF1 edge to restart.
Result: the drive fails to start. The PLC continues to assert OFF1 and OFF2 = 1, but the drive refuses to release pulses because, from its perspective, OFF2 was asserted when the run command was issued.
Why Telegram Control Avoids This
PROFIdrive telegrams deliver all 16 control word bits as a single 16-bit word on the same PROFINET cycle. The drive receives STW1 atomically. Bit 0 (OFF1) and bit 1 (OFF2) cannot physically arrive on different cycles. The PROFIdrive state machine inside the G120C evaluates the full STW1 once per bus cycle, so a PLC that puts STW1 = 0x047F (OFF1=ON, OFF2=inactive, OFF3=inactive, enable=ON, setpoint enable=ON, PLC control=ON) always results in a coherent command. There is no race condition because there is no per-bit independent delivery.
Wiring the S7-1200 to G120C over PROFINET
Even when telegram control is used, certain terminals must still be wired for hardware interlock safety (e.g., STO via terminal, hardware coast). On the G120C, the Safe Torque Off (STO) function is implemented as a hardwired safety input when using Safety Integrated via terminal; it is implemented over PROFIsafe when using a PN-F Control Unit. Verify which variant is in use before commissioning.
Minimum Wiring for Telegram Control (no PROFIsafe)
| Drive Terminal | Signal | Connection | Notes |
|---|---|---|---|
| 1, 2 | 24 V supply | External 24 VDC | CU electronics power. |
| 31, 32 | Digital input 0 (DI0) | Hardwired emergency stop | Configure as STO via p1012 if no PROFIsafe. |
| 33, 34 | Digital input 1 (DI1) | Optional — local jog | Not required for telegram control. |
| PROFINET Port 1 | Ethernet | S7-1200 PROFINET port | PROFINET device name must match configuration. |
| PE | Protective earth | Ground bus | Required for EMC. |
Configuration of Digital Inputs in Telegram Mode
When the PLC is in control (STW1 bit 10 = 1), the drive ignores commands from DI0/DI1 for ON/OFF/coast. However, the digital inputs are still scanned and can be BICO-routed to other functions (e.g., DI0 mapped to STO via p1012 = 722.0, or DI1 mapped to a local jog command). Verify in the function plan under Configuration → Inputs/Outputs → Digital Inputs that DI0 and DI1 are not double-assigned to ON/OFF1/OFF2 commands if you want pure telegram control.
PLC Program Skeleton: SinaSpeed Function Block
Siemens provides the SinaSpeed function block (FB 285 / "SinaSpeed" in the SINAMICS library) as a turnkey interface for the G120C. The FB handles PROFIdrive state machine sequencing, fault acknowledgement, and setpoint ramp management, eliminating the need for the PLC to manually toggle individual STW1 bits.
SinaSpeed Block Interface (STEP 7 / TIA Portal)
| Input | Type | Description |
|---|---|---|
| EnableAxis | BOOL | Master enable for the axis (drives the safety AND logic). |
| SpeedSp | REAL | Speed setpoint in RPM (the FB converts to NSOLL internally using p2000). |
| RefSpeed | REAL | Reference speed matching p2000 (default 1500 RPM). |
| ConfigAxis | BOOL | One-shot configuration handshake. |
| Acknowledge | BOOL | Positive edge acknowledges drive faults (sets STW1 bit 7). |
| HwStop | BOOL | Hardware stop — drives STW1 bit 1 (OFF2) and bit 2 (OFF3) to 0 simultaneously. |
| Output | Type | Description |
|---|---|---|
| AxisReady | BOOL | ZSW1 bit 0 — drive ready to switch on. |
| AxisError | BOOL | ZSW1 bit 3 — fault present. |
| AxisWarn | BOOL | ZSW1 bit 7 — alarm present. |
| ActSpeed | REAL | Actual speed in RPM (NIST scaled by p2000). |
| ActPosition | REAL | Optional — for telegram 3 / 103 with position feedback. |
| ErrorWord | WORD | Fault code from r2131 / r2133. |
Example Call in Structured Text (SCL)
// G120C_Instance.scl — SinaSpeed wrapper
IF "dbG120C".ConfigRequest THEN
"dbG120C".ConfigAxis := TRUE; // one-shot to FB
END_IF;
"SinaSpeed_DB"(
EnableAxis := "dbG120C".RunReq AND NOT "dbG120C".HwStop,
SpeedSp := "dbG120C".SpeedRPM,
RefSpeed := 1500.0,
ConfigAxis := "dbG120C".ConfigAxis,
Acknowledge := "dbG120C".AckPulse,
HwStop := "dbG120C".HwStop OR "EStopPushbutton",
AxisReady => "dbG120C".Ready,
AxisError => "dbG120C".Faulted,
ActSpeed => "dbG120C".ActualRPM
);
// Pulse acknowledge on rising edge
"dbG120C".AckPulse := "dbG120C".AckCmd AND NOT "dbG120C".AckPrev;
"dbG120C".AckPrev := "dbG120C".AckCmd;
Commissioning Procedure and Verification
-
Pre-power checks: Verify mains voltage, motor nameplate data vs.
p0301–p0349, and that STO hardware circuit (terminals 31/32) is wired to the safety relay. -
Motor identification: Run
p1900 = 2(motor data identification, rotating) orp1900 = 1(non-rotating). This calibrates the field-weakening range and the I²t model. -
Save parameters: Copy RAM to ROM (
p0971 = 1) before loading the telegram configuration; this prevents parameter loss on power cycle. - Configure PROFINET device name: Use the PRONETA or TIA Portal topology editor to assign the device name (e.g., "G120C-001"). The PROFINET device name must match the PLC project exactly.
-
Set the IP address: Either via DHCP server (PRONETA / TIA Topology) or statically via parameter
p8921(PN NameOfStation IP) andp8922(subnet mask). -
Verify PROFINET communication: In Starter, monitor
r2050[0],r2050[1],r2090.0, andr2090.1live. You should see ZSW1 and NIST updating on every PROFINET cycle. -
Test telegram control from the Starter control panel: Set
p854.0 = 0to disable local control, then issue STW1 =0x047Fwith NSOLL =0x1000(10 % of p2000). Verify the motor accelerates to 150 RPM. - Test the safety AND: Toggle STW1 bit 1 (OFF2) to 0 with the motor running. The drive should coast immediately and pulse-inhibit. Restore STW1 bit 1 to 1 and re-issue STW1 bit 0 (OFF1) rising edge to restart.
-
Hand-off to PLC: With the drive verified, set
p854.0 = 1(control from PLC) and load the SinaSpeed instance. Run the PLC program in monitor and observe the AxisReady / AxisError outputs and ActSpeed. - Failure-mode test: While running, force STW1 bit 1 to 0 from the PLC for 200 ms, then restore. The drive should coast, stop, and re-start on the next OFF1 edge. This is the test that proves telegram control is working correctly.
Troubleshooting Matrix
| Symptom | Probable Cause | Drive Diagnostic Parameter | Corrective Action |
|---|---|---|---|
| Drive does not respond to STW1. | STW1 bit 10 = 0 (control not handed to PLC). | r2090.0 bit 10 | Set STW1 bit 10 = 1 in PLC; verify p854.0 = 1. |
| Drive accelerates then immediately stops. | STW1 bit 6 (setpoint enable) is 0 after start. | r2090.0 bit 6 | Set bit 6 = 1 in PLC; verify SinaSpeed output is correct. |
| Motor runs but ZSW1 bit 2 (operation enabled) is 0. | OFF2 or OFF3 active (STW1 bits 1/2 = 0). | r2090.0 bits 1,2 | Verify hardware stop wiring; check p0797 debounce. |
| Fault F08501 "PROFINET communication fault". | PROFINET watchdog timeout (p2040) exceeded. | r2050[0] ZSW1.3 | Increase p2040 to match PLC watchdog; verify send clock. |
| Fault F07900 "Motor blocked". | Motor cannot accelerate to setpoint within p2177. | r0947 = 7900 | Extend p2177, check mechanical load, verify p2000 matches motor. |
| Fault F30001 "Overcurrent". | Acceleration ramp too short; I²t exceedance. | r0947 = 30001 | Lengthen p1120 (ramp-up); verify p0305 motor current. |
| Speed setpoint ignored (motor at 0 RPM with NSOLL > 0). | Main setpoint source misconfigured. | r1070, r1071 | Verify p1070[0] = 2050[1] (setpoint from PZD2). |
| Actual speed (NIST) shows wrong scaling. | p2000 mismatch between PLC and drive. | r2000 | Match p2000 to RefSpeed input in SinaSpeed (default 1500 RPM). |
| Intermittent no-start fault under PLC control. | Digital I/O control still partially enabled; STW1 bit 10 toggling. | r852 | Verify all command sources point to PROFIdrive; remove redundant BICO routing. |
| Drive requires OFF1 edge re-issue after every stop. | OFF1 latch behavior; PLC keeps OFF1 = 1 continuously. | Monitor r2090.0 bit 0 | Drop OFF1 to 0 before re-start, then re-assert (rising edge). |
Field-Proven Notes from Legacy Retrofits
- Keep the existing hardware stop: Do not remove the hardwired STO or coast terminals when migrating to telegram control. STW1 bit 1 (OFF2) is a software command, not a safety function. Hardware STO is required for SIL 2/3 applications regardless of telegram path.
- Phase-in the speed setpoint first: On most retrofits, the first PROFINET element to migrate is the speed setpoint (NSOLL). Speed control is non-safety, and a wrong ramp or scaling is recoverable. Save the control word migration for the second phase when the field team is comfortable with the new telegram.
-
Document the BICO wiring: Many legacy G120C installations have non-default BICO routing (e.g., DI0 → ON/OFF1, DI1 → OFF2). When migrating to telegram control, reset these BICO connections to defaults via
p0010 = 30,p0970 = 1(factory reset), then reapply only the parameters you intend to change. - Use the Starter trace: Record STW1, ZSW1, NSOLL, NIST, and r0063 (smoothed actual speed) simultaneously for 5 seconds during start, run, stop, and fault scenarios. The trace file is invaluable when validating the safety AND logic against PLC scan behavior.
What telegram number should I select for a minimal G120C PROFINET speed control application?
Use p0922 = 999 for a free telegram. Configure p2051[0] = STW1, p2051[1] = NSOLL, p2050[0] = ZSW1, and p2050[1] = NIST. Alternatively, select standard telegram 1 (p0922 = 1) for the same 4-word layout using predefined mapping.
Why does my drive not start even though STW1 shows OFF1 = 1?
Check STW1 bits 1 (OFF2), 2 (OFF3), 3 (enable operation), 6 (setpoint enable), and 10 (control by PLC) — all must be 1 simultaneously. If any are 0, the drive inhibits pulse release. Also verify p854.0 = 1 so the drive accepts control from the PROFINET interface.
How do I migrate from digital I/O control to PROFINET telegram control on an existing installation?
Phase 1: Install PROFINET, configure the telegram and SinaSpeed in the PLC, but leave the digital wiring in place. Phase 2: Switch p854.0 to PLC control, run the PLC, and monitor STW1/ZSW1. Phase 3: Once verified, physically remove the digital control wiring and update the schematic. This minimizes production risk on 24/7 systems.
What is the typical PROFINET cycle time for non-motion G120C speed control?
For most conveyor, pump, fan, and mixer applications, a 2–4 ms send clock is sufficient. Below 1 ms, you risk excessive bus load on multi-node networks. Above 4 ms, the dynamic response of the speed loop may degrade on high-inertia loads. Match p2040 (PROFINET watchdog) to three times the send clock to avoid spurious F08501 faults.
Can I use telegram control with Safety Integrated via PROFIsafe?
Yes. On G120C PN-F Control Units (CU240S2 PN-F), configure a PROFIsafe slot in addition to the PROFIdrive telegram. The PROFIsafe channel carries STO, SS1, SS2, SLS, and other safety functions atomically, with a separate watchdog and CRC. STW1 in the PROFIdrive channel remains the process-data control word. See Siemens Entry ID 56749384 for the terminal-based safety variant and the parallel PN-F entry for PROFIsafe configuration.