Overview: SINAMICS S210 Safety Integrated Functions over PROFIsafe
The SINAMICS S210 servo drive (6SL3210-5HB series) integrates Safety Integrated Extended Functions including STO (Safe Torque Off), SS1 (Safe Stop 1), SOS (Safe Operating Stop), SLS (Safely-Limited Speed), SDI (Safe Direction), SSM (Safe Speed Monitor) and SLA (Safely-Limited Acceleration). Two paths exist to trigger these functions:
- Fail-safe digital inputs on the F-TM ServoDrive ST module inside the ET 200SP station (terminals STO+ / STO-).
- PROFIsafe over PROFINET from a SIMATIC F-CPU acting as PROFIsafe host.
When the STO function is wired via PROFIsafe, the safety control word (S_STW) travels inside a PROFIsafe telegram between the F-CPU and the drive. Selecting (activating) or deselecting (releasing) STO is therefore a matter of writing the correct bit pattern into the corresponding safety data block, not toggling a 24 V terminal. The Telegrams supported on the S210 with Safety Integrated are 30, 31, and the vendor-specific telegrams 900, 901, 902, 903. Telegram 30 is the standard two-word safety telegram; telegram 31 extends the payload for SLS with multiple limits; telegram 900 carries a compact one-word safety image for S210. The Telegram selection must match the configured Safety Integrated mode on the drive (Basic or Extended).
If the F-program is written directly against raw PROFIsafe payload bytes, the integrator must understand the bit assignment, byte order, and PROFIsafe CRC handling. To avoid that, Siemens publishes a library of ready-made F-blocks that wrap each telegram: SINAMICS S210 Safety Integrated Functions library (entry 109485794). The library contains one FB per telegram (e.g., SINA_SAFE_TLG30, SINA_SAFE_TLG31, SINA_SAFE_TLG900) that exposes a structured interface where the engineer selects or deselects STO with a Boolean input.
Prerequisites
- Hardware: SINAMICS S210 (6SL3210-5HB...), ET 200SP baseUnit, F-TM ServoDrive ST module (article number 6FE1202-... for the safety terminal module referenced in the F-DI documentation), PROFINET cable, and a SIMATIC F-CPU (e.g., CPU 1510SP F-1 PN / 1512SP F-1 PN / 1515SP PC F).
- Software: TIA Portal V17 or newer (V18/V19 recommended for the latest S210 HSP). STEP 7 Safety Advanced option package must be installed for F-programming.
- Library: SINAMICS S210 Safety Integrated Functions block library, installed into TIA Portal master data library.
- S210 firmware: V5.2 or newer (V5.2 SP3 recommended) for full Extended Functions coverage.
- GSD / HSP: SINAMICS S210 GSDML installed, or the matching Hardware Support Package imported in TIA Portal.
- Engineering rights: The Safety password for the S210 and the F-CPU must be known. Both the drive safety configuration and the F-program are password-protected; the password must be entered before each commissioning cycle.
Step 1: Configure the S210 and PROFIsafe Channel in the Device View
- Open the TIA Portal project and add the SINAMICS S210 from the hardware catalog. Use the latest GSD or HSP so that all safety telegrams (30, 31, 900) appear in the Telegram configuration drop-down.
- Right-click the S210 and open Properties → Safety Integrated. Select Extended Functions if you intend to use SS1, SLS, SS2, SDI, SLA, or SOS in addition to STO. Keep Basic Functions if only STO and SS1 are required.
- In the Telegram configuration, set Telegram 30 (Standard) for a typical STO-only or STO+SS1 setup. Use Telegram 31 if multiple SLS limit values must be transmitted. Use Telegram 900 for the S210 compact safety image.
- Assign a unique PROFIsafe address to the F-DI module (or the integrated PROFINET safety slot on the S210) in the range 1..1023. The address must match the F-DI DIP switch on the physical module, or be set by the PROFINET assignment tool (DCP) if Address assignment via PROFINET is enabled.
- Compile the hardware configuration. TIA Portal automatically generates the safety I/O tags (S_STW1, S_ZSW1, etc.) in the PLC tag table.
Assigning the PROFIsafe Address via TIA Portal (per official Siemens PDF)
The reference application Controlling SINAMICS S210 Safety Integrated Functions using TO Axis (PDF, 109760341) documents the procedure:
- Switch to Device view in the project tree under Device configuration.
- Right-click the F-DI module of the F-TM ServoDrive ST station.
- Select Assign PROFIsafe address from the context menu.
- Confirm the proposed F-address matches the rotary switches on the physical module, or set it via DCP if the slot is configured for network-assigned F-addresses.
Step 2: Install and Instantiate the Safety Block Library
The library referenced in the application manual is entry 109485794. After download, open the master data library in TIA Portal and drag the FB matching the chosen telegram into the F-program folder:
| Telegram | FB name (typical) | Inputs relevant to STO | Notes |
|---|---|---|---|
| 30 | SINA_SAFE_TLG30 |
iSelectSTO, iSelectSS1, iAcknowledge
|
Two S_STW words, two S_ZSW words |
| 31 | SINA_SAFE_TLG31 |
iSelectSTO, iSelectSS1, iSLS_Limit_Bit0..1
|
Extended payload for SLS limits |
| 900 | SINA_SAFE_TLG900 |
iSelectSTO, iSelectSS1
|
Compact S210 telegram |
The block takes care of bit-stuffing the control word, calculating the PROFIsafe CRC, and routing the payload through the F-CPU's safety stack to the drive. The integrator only interacts with Boolean inputs.
Step 3: STO Select / Deselect Bit Mapping in Telegram 30
If the F-program is written at the raw PROFIsafe level rather than using the library FB, the following bit positions apply for S_STW1 in Telegram 30:
| Bit | Function | Select (0 / 1) | Description |
|---|---|---|---|
| 0 | STO | 0 = STO active, 1 = STO deselected | Safe Torque Off request |
| 1 | SS1 | 0 = SS1 active, 1 = SS1 deselected | Safe Stop 1 request |
| 2 | SS2 | 0 = SS2 active, 1 = SS2 deselected | Safe Stop 2 (Tlg 31/900) |
| 3 | SOS | 0 = SOS active, 1 = SOS deselected | Safe Operating Stop |
| 4..5 | SLS | Bit pattern for SLS level | 00 = level 1, 11 = deselected |
| 6 | SDI+ | 0 = SDI+ active | Safe Direction positive |
| 7 | SDI- | 0 = SDI- active | Safe Direction negative |
| 8..11 | Vendor specific | n/a | S210-specific control bits |
| 12 | SSM | 1 = SSM active feedback | Safe Speed Monitor enable |
| 13..15 | Vendor specific | n/a | S210-specific status |
Bit semantics are low-active: writing 0 to bit 0 selects STO, writing 1 to bit 0 deselects STO. The default deselected state (drive ready to enable) is therefore S_STW1 = 16#0000_0000_0000_0000 if no other safety function is requested. The simplest ladder logic to deselect STO from the F-program is:
// F-program (FBD or STL)
// Always deselect STO when the safety door is closed and emergency stop is released
// Library FB: SINA_SAFE_TLG30 (DB instance: iDB_SafetyTlg30)
iDB_SafetyTlg30.iSelectSTO := FALSE; // 0 → STO active
iDB_SafetyTlg30.iSelectSS1 := TRUE; // 1 → SS1 deselected
iDB_SafetyTlg30.iAcknowledge := bAckFault;
iDB_SafetyTlg30(oSelectSTO => qSelectSTO, // diagnostic only
oSelectSS1 => qSelectSS1);
Use the FB instance for Telegram 30 unless SLS with multiple limit levels is required; in that case switch to Telegram 31 or the S210-specific Telegram 900.
Step 4: Compile the F-Program and Download
- Right-click the F-CPU → Compile > Safety Program. TIA Portal performs a safety check on every F-block (F-validity check, signature, runtime group assignment).
- Enter the Safety password for the F-CPU when prompted.
- Download the F-program to the F-CPU. The runtime group that contains the S210 safety FB must be assigned to a cyclic OB (typically OB 35 with 100 ms cycle).
- Download the standard PLC program (HMI tags, axis configuration, technology objects) separately. The safety download is independent and requires the Safety password.
Step 5: Resolve the Acceptance Test Required Fault
The Acceptance Test Required fault appears on the S210 when Safety Integrated Extended Functions have been configured but the mandatory safety acceptance test has not yet been completed and signed off. The fault is latched and blocks the safety handshake between the F-CPU and the drive, which means STO will stay selected and the axis will not move. It is the most common first-time-commissioning block on S210 projects.
Procedure to Clear the Fault and Complete the Acceptance Test
- Open Startdrive > Commissioning > Safety Integrated > Acceptance test on the S210.
- Select PROFIsafe as the safety channel for the test (the test would be slightly different for F-DI based wiring).
- Run the wizard: it steps through STO select/deselect, SS1 stop time, SLS limit verification, and SDI direction check. Each step must be physically verified (motor coasts to standstill for STO, decelerates on SS1, holds at limit for SLS).
- From the F-CPU, force STO active (write 0 to S_STW1 bit 0) and verify that the drive pulses are removed within the configured safe stop time (typically < 5 ms for STO).
- Deselect STO (write 1 to S_STW1 bit 0) from the F-program; verify the drive releases the pulses and the safety status word bit 0 returns to 1 (STO inactive).
- Sign off the acceptance test report. Startdrive generates a PDF that documents each step, the test results, the S210 serial number, the F-CPU serial number, and the Safety signature CRC.
- Save the report and archive it with the machine dossier. TIA Portal also stores the acceptance test status in the drive project; after successful completion, the Acceptance Test Required fault clears on the next power-up or after the safety acknowledgment bit is set.
Step 6: Verification and Commissioning Checklist
| Check | Expected Result | Method |
|---|---|---|
| S210 receives valid PROFIsafe telegram | S_ZSW1 bit 0 = 1 (STO deselected), no F-host communication error | |
| STO select via PROFIsafe | Pulses removed within ≤ 5 ms; drive reports STO active | Force bit 0 = 0 in F-program, observe drive status |
| STO deselect via PROFIsafe | Pulse enable restored, motion possible | Force bit 0 = 1, jog axis |
| PROFIsafe CRC valid | No F-life counter mismatch, no CRC error | F-CPU diagnostics buffer |
| Acceptance Test Required cleared | Fault absent after power cycle | Startdrive fault buffer |
| Safety signature stable | F-CPU safety signature unchanged after edit | TIA Portal > Safety > PrintF signature |
| TO Axis follows enable | Axis moves under PLC motion control after STO deselect | MC_Power + MC_MoveAbsolute |
Troubleshooting Matrix
| Symptom | Probable Cause | Resolution |
|---|---|---|
| Drive stays in STO, axis does not move | S_STW1 bit 0 = 0 in F-program | Set iSelectSTO input on the safety FB to FALSE (i.e., write 1 to S_STW1 bit 0 = deselect) |
| Acceptance Test Required fault active | Safety acceptance report not completed | Run Startdrive Acceptance test wizard, sign report, save to project |
| PROFIsafe communication error (red SF LED on F-DI) | Mismatch between configured F-address and DIP switch on F-DI | Right-click F-DI in Device view → Assign PROFIsafe address, or adjust DIP switch to match |
| Drive reports F01611 / F30611 | PROFIsafe parameterization error after drive download | Recompile Startdrive project, perform POWER ON of the drive |
| S_ZSW1 bit 0 does not toggle | Wrong telegram selected in drive configuration vs. PLC | Verify Telegram 30/31/900 matches in both TIA Portal hardware config and Startdrive Telegram configuration |
| Safety signature CRC mismatch | Online/offline drift after F-program change | Recompile Safety Program, re-download, re-print signature |
| F-CPU goes STOP after safety download | F-runtime group OB not assigned or OB 35 missing | Assign safety FB to a runtime group with OB 35 (or OB 30/OB 38 depending on cycle time) |
| SS1 never deselects after stop | SS1 hold time not configured in drive | Set p9652 (SS1 delay time) and p9653 (SS1 transition time) on S210, recompile safety configuration |
| SLA / SLS setpoint exceeds safe limit | Motion setpoint not limited by F-application | Add SLS limit monitoring in F-program with SINA_SAFE_TLG31 / TLG900 inputs |
Safety and Regulatory Notes
- The PROFIsafe protocol version configured on the F-CPU must be V2.4 or higher when communicating with a current S210 firmware. Mismatched PROFIsafe versions are rejected by the F-host at startup.
- STO via PROFIsafe must not be the only safety measure if the application requires a category higher than SIL 2 / PL d. Refer to the S210 Safety Integrated Functions manual for the achievable safety level per safety function.
- Always use the Safety password to lock the drive configuration after commissioning. Without a password, anyone with TIA Portal access can modify the safety configuration, which will trigger the Acceptance Test Required fault on the next startup.
- The Safety signature of the F-program must be archived alongside the acceptance test report. Any later change to the F-program invalidates the acceptance test and requires a new test run.
FAQ
Which PROFIsafe telegram should I use for STO only on SINAMICS S210?
Use Telegram 30 (Standard) for STO and SS1 only, or Telegram 900 for a compact S210-specific safety image. Switch to Telegram 31 only when multiple SLS limit values must be transmitted.
How do I clear the Acceptance Test Required fault on the S210?
Open Startdrive > Commissioning > Safety Integrated > Acceptance test, select PROFIsafe as the channel, walk through STO/SS1/SLS/SDI steps, sign the generated PDF report, and save it to the project. The fault clears on the next power-up or after the safety acknowledgment bit is set.
What is the bit position of STO in S_STW1 on Telegram 30?
Bit 0, low-active: write 0 to select STO (drive pulses removed), write 1 to deselect STO (drive enable). The library FB SINA_SAFE_TLG30 exposes a Boolean input iSelectSTO so you do not have to manipulate the bit directly.
Can I use the F-TM ServoDrive ST digital inputs and PROFIsafe at the same time?
Yes. The F-TM STO+ / STO- terminals and the PROFIsafe channel are logically ORed by the drive: STO is active if either source requests it. Use PROFIsafe for centralized control from the F-CPU and use the F-DI terminals for hard-wired E-stop loops as a redundant channel.
Which Siemens F-CPUs support the S210 via PROFIsafe?
All SIMATIC F-CPUs with PROFINET interface and STEP 7 Safety Advanced (e.g., CPU 1510SP F-1 PN, CPU 1512SP F-1 PN, CPU 1515SP PC F, CPU 1516F, CPU 1518F) support the SINAMICS S210 through the standard PROFIsafe host stack. TIA Portal V17 or newer is required.
Where do I find the SINAMICS S210 safety block library?
The library "SINAMICS S210 Safety Integrated Functions" is published under Siemens support entry 109485794. It contains one FB per telegram (30, 31, 900) that simplifies STO/SS1/SLS selection without touching raw PROFIsafe bytes.
What does the Siemens reference application 109760341 cover?
The PDF 109760341 walks through the complete wiring of safety functions of an S210 to a TO Axis technology object, including the F-DI PROFIsafe address assignment, the safety block integration, and the commissioning procedure described in this article.