Configuring Yaskawa Motoman with Cognex In-Sight on PROFINET

Jason IP13 min read
RoboticsTutorial / How-toYaskawa
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

Vision-guided robotics (VGR) on a Yaskawa Motoman controller paired with a Cognex In-Sight vision system over PROFINET is one of the most common cell architectures in discrete-parts manufacturing. The robot approaches a workpiece, the In-Sight camera locates features, and the controller offsets the motion path in real time. The PLC—typically a Siemens S7-1500—orchestrates the cell: handshake, trigger, hand-off of vision results, and job dispatch.

This reference walks through the engineering steps for a PROFINET-based cell using a Motoman DX200/FS100/YRC1000 controller, a Cognex In-Sight 9000, 7000, or 2800 series camera, the MotoSight™ 2D software option, and an S7-1500 with TIA Portal. It covers network commissioning, In-Sight job configuration, the three-point user-frame (ORG/XX/XY) calibration, the camera-to-robot calibration grid, and the ladder/structured-text glue that binds them.

Engineering note: Cognex refers to the supported product family as In-Sight®, and the Yaskawa-branded vision option as MotoSight™ 2D. The Motoman communications protocol running on the camera's serial port is the legacy path; on PROFINET, the camera is a PN device and vision data is exchanged through cyclic I/O or record data.

System Architecture and Data Flow

The PROFINET cell uses a three-tier topology: the PLC is the IO controller, the In-Sight camera is a PN device, and the Motoman controller is reached either through its optional PROFINET Scanner/Slave board (typically the Motoman YAS2.80 PROFINET option on the DX200/FS100 or the standard PN slave on the YRC1000) or via EtherNet/IP. The In-Sight sensor publishes results as PN slot data; the PLC reads them, validates them, and signals the robot to move to the offset pose.

Role Device PROFINET Function Key GSD/GSDML
IO Controller Siemens S7-1500 (CPU 1515-2 PN, firmware ≥ V2.9) Master, AR establishment Integrated in TIA Portal
Vision Device Cognex In-Sight 9000 / 7000 / 2800 series PN Device, real-time results slot GSDML-Vx.x-Cognex-In-Sight_xxxx.xml
Robot Controller Motoman DX200 / FS100 / YRC1000 PN Slave (or EIP adapter) Yaskawa GSDML file per firmware
HMI TP/CP-series or HMI KTP1200 Optional PN node

Cognex publishes its PROFINET GSDML files on the In-Sight support site; import them in TIA Portal under Options → Manage General Station Description Files (GSD). The In-Sight 9000 series, including the In-Sight 3900 AI vision system released in 2024, uses the same PROFINET slot model as legacy In-Sight sensors and is backward-compatible with the MotoSight 2D job structure. See the In-Sight 3900 product announcement and the In-Sight Explorer Motoman Communications help for the protocol specifics.

Prerequisites and Bill of Materials

  1. Robot controller with the VGR option enabled: DX200, FS100, DX100, or YRC1000. The MotoSight 2D PC option (part-number family YAS-MTSIGHT-2D) is required on the controller or on the engineering PC.
  2. Cognex In-Sight camera with PROFINET support enabled in firmware. In-Sight 9000, 7000, 2800, 3800, and 3900 series all support PROFINET; enable the protocol in In-Sight Explorer → Sensor → Add Sensor → PROFINET.
  3. Siemens S7-1500 PLC with PN interface (any CPU 15xx-2 PN, 1516-3 PN/DP, or 1518-4 PN/DP). Firmware ≥ V2.9 is recommended for full GSDML-V2.3 support and to use record-data reading via RDREC.
  4. PROFINET switch: managed, DCP-capable (e.g., Siemens Scalance XC-200, XC-300, or Phoenix Contact FL SWITCH 2308 PN).
  5. MotoSight 2D Calibration Grid: 9×9 or 12×12 checkerboard with 10 mm or 20 mm squares, supplied by Yaskawa or a third-party machine-vision vendor.
  6. Three fiducial targets on the workpiece or fixture: high-contrast, non-symmetric (fiducials must not be collinear).
  7. Network configuration shared PROFINET name, IP subnet, and DCP discovery enabled.
Field warning: Never daisy-chain PROFINET devices through a passive switch. Use a star topology from the managed switch. PROFINET IRT requires cut-through switching; standard store-and-forward switches can violate the 1 ms update budget.

PROFINET Network Commissioning

Assigning Device Names and IP Addresses

PROFINET requires a unique device name per node. Assign names using the Siemens PRONETA tool or TIA Portal's Online → Accessible Nodes. Recommended IP scheme for a 3-node cell:

Device PROFINET Name IP Address Subnet
S7-1500 CPU plc-cell01 192.168.1.10 255.255.255.0
In-Sight 9000 #1 vision-cam01 192.168.1.20 255.255.255.0
Motoman YRC1000 robot-arm01 192.168.1.30 255.255.255.0

Update time for the In-Sight PN slot should be set to 1 ms (RT class 1) for low-latency hand-off. With the In-Sight 9000 series and a YRC1000 PROFINET option, you can drop to 500 µs with IRT, but only if the switch supports it. The Cognex Vision-Guided Robotics application note lists the supported update rates per sensor family.

GSDML Slot Mapping on the In-Sight Camera

The In-Sight PROFINET image has a fixed slot map. Typical default for the 9000 series:

  • Slot 0: DAP (Device Access Point)
  • Slot 1: 32-byte results block (vision results, pass/fail, offsets)
  • Slot 2: 64-byte extended results (coordinates, scores, strings)
  • Slot 3: 8-byte control word (trigger, job select)

The PLC reads slots 1 and 2 as input modules; slot 3 is an output module the PLC writes to trigger the camera and select a job number. The In-Sight Motoman Communications help documents the legacy serial protocol; the PROFINET slot map mirrors the same data structure so existing MotoSight 2D jobs can be reused.

Cognex In-Sight Job Setup

Open In-Sight Explorer (firmware ≥ 5.7 recommended for 9000/3900 series), connect to the camera, and create a new .job file. The job contains the vision tools, the calibration, and the result-string format. Below is a minimal job layout for a pick-and-place cell.

  1. Acquire Image: set exposure, gain, and lighting so the fiducials read >120 on the 0-255 grayscale. Use AutoExposure during commissioning, then lock values for production.
  2. Pattern Find (PatMax®): train a single fiducial as a reference pattern. PatMax is tolerant of 360° rotation, scale, and lighting changes.
  3. Blob / Edge Tools for each of the two remaining fiducials, or three PatMax instances for full rotational invariance.
  4. Calibration: link the three fiducial coordinates to the robot's three taught points.
  5. Output Format: emit a result string that the PLC parses, e.g. X=123.45,Y=-67.89,R=12.34,SCORE=87,STATUS=OK.
Calibration data is stored in the .job file. Backing up the job to the controller's jobs folder or to a TIA Portal project HMI card is part of the cell's recipe. The In-Sight 9000/3900 series has an SD card slot for job cloning; populate the slot when running identical lines.

MotoSight 2D Configuration on the Motoman Controller

MotoSight 2D is the Yaskawa-branded vision option that integrates In-Sight cameras with the Motoman controller. The product page on motoman.com MotoSight 2D lists the supported controllers and the calibration wizard. Activate the option on the controller pendant, define the camera IP, and map the camera's data slot to MotoSight internal variables.

Camera-to-Robot Calibration Grid

The grid calibration teaches the In-Sight camera the relationship between pixel coordinates and robot Cartesian coordinates. Yaskawa's recommended procedure:

  1. Place the calibration grid in the camera's field of view, ensuring the grid is flat and parallel to the work surface. Use a 9×9 grid with 10 mm squares for typical 200 mm field-of-view applications.
  2. In MotoSight 2D, select Calibrate → Grid Calibration. The software moves the robot to nine positions (3×3 matrix), and at each position it records the grid intersection pixel coordinate from In-Sight and the corresponding robot Cartesian coordinate from the controller.
  3. MotoSight computes a 3×3 homography matrix that maps pixel (u, v) to robot (X, Y, Rz). The matrix is saved with the job.
  4. Validate the calibration by commanding the robot to three test points picked from In-Sight. A residual under 0.5 mm in X/Y and 0.5° in Rz is acceptable for most pick-and-place cells; high-precision cells demand under 0.2 mm / 0.2°.

Three-Point User Frame (ORG / XX / XY)

The user frame is the origin and orientation the robot uses for taught points. With three fiducials you can build a deterministic, repeatable frame regardless of fixture drift. Procedure on the Motoman pendant:

  1. Move the robot so the TCP is centered on fiducial #1. Record the position as the ORG (origin) of frame UF[1] or higher.
  2. Move the TCP to fiducial #2, which lies on the desired XX axis. MotoSight or the standard Motoman frame wizard records this as XX.
  3. Move the TCP to fiducial #3, which lies in the desired XY plane. Record this as XY. The controller calculates the orthonormal frame using the right-hand rule.
Geometric warning: the three fiducials must not be collinear. Place fiducial #2 and #3 at least 50 mm apart on perpendicular axes; a near-collinear triplet amplifies numerical noise in the cross-product that defines Z. Use a triangle with sides at least 4:3:1 for a stable frame.

Siemens S7-1500 PLC Integration

The PLC acts as the cell orchestrator. The minimal data exchange is: PLC writes a job-select byte and trigger to the camera; the camera returns a results block containing the offset pose and a status word; the PLC validates and forwards offsets to the robot.

TIA Portal Data Blocks

DB Symbol Type Description
iCamIn PRG.IN.CAM_RESULTS Struct of 16 bytes Parsed from PN slot 1
qCamOut PRG.OUT.CAM_CTRL Byte Bit 0 = Trigger, Bits 1-7 = Job#
iRobPose PRG.IN.ROBOT_POSE Real[6] X, Y, Z, Rx, Ry, Rz from robot PN slot
qRobCmd PRG.OUT.ROBOT_CMD DWord Job select, move command
stat PRG.STAT.CELL_STATE Int 0=Idle, 10=Trigger, 20=WaitRes, 30=Move, 40=Done, 99=Error

Structured-Text State Machine

The cell is best modeled as a deterministic state machine. A minimal ST implementation in TIA Portal V17+:

// Cell state machine - VGR pick sequence
CASE #stat OF
    0:  // Idle
        IF #bStart THEN
            #qCamOut.%X0 := TRUE;          // Trigger pulse
            #stat := 20;
        END_IF;

    20: // Wait for results
        IF #iCamIn.DONE AND #iCamIn.STATUS = 16#01 THEN
            #stat := 30;
        ELSIF #iCamIn.STATUS = 16#FF THEN
            #stat := 99;                   // Vision fault
        END_IF;

    30: // Compose offset pose
        #qRobCmd[0] := #iCamIn.X_OFFSET;    // mm
        #qRobCmd[1] := #iCamIn.Y_OFFSET;
        #qRobCmd[2] := #iCamIn.RZ_OFFSET;   // deg
        #qRobCmd[3] := 1;                   // job # = Pick
        #stat := 40;

    40: // Wait robot done
        IF #iRobPose[3] = 1 THEN
            #qCamOut.%X0 := FALSE;
            #stat := 0;
        END_IF;

    99: // Fault
        ;                                  // Latch and alarm
END_CASE;

Hand-off to the Robot Controller

The PLC writes the offset to the robot either through PN process data (e.g., 8 bytes of FLOAT containing X, Y, Rz) or through a job-select register on the Motoman controller. The Motoman PROFINET Slave manual describes the slot map; on YRC1000 the standard PN slot exposes 32 bytes of input and 32 bytes of output. A common pattern:

  • PLC → Robot Output Byte 0: CmdCode (0=Idle, 1=PickOffset, 2=PlaceBase)
  • PLC → Robot Output Bytes 1-4: X offset (REAL)
  • PLC → Robot Output Bytes 5-8: Y offset (REAL)
  • PLC → Robot Output Bytes 9-12: Rz offset (REAL)
  • Robot → PLC Input Byte 0: Status (0=Busy, 1=Done, 2=Fault)

Robot Job (Inform Job / MotoCom32) for Vision Offsets

On the Motoman controller, the offset hand-off is consumed in an Inform job (or Inform LIST job on YRC1000). The job reads the PN input bytes, builds a Cartesian offset variable, and applies it through the SETE and SFTON instructions.

// Inform job on YRC1000 - read PN offset and shift
GETE B001 1 B000    // Get current pose
ADD B000[0] B010[0] B020[0]   // X_base + X_offset
ADD B000[1] B010[1] B020[1]   // Y_base + Y_offset
SFTON B020 P001             // Activate shift on user frame 1
MOVL V001= 50.0             // Move to offset pose at 50 mm/s

The shift-on (SFTON) instruction is reset at the end of the pick sequence with SFTOF. The exact instruction set depends on the controller generation—see the YRC1000 INFORM III manual for the GETS/PUTS register conventions and the DX200 PROFINET manual for the equivalent B0xx variable ranges.

Verification and Commissioning Checks

  1. PROFINET diagnostics: open TIA Portal Online → Diagnostics and confirm no AR (Application Relationship) errors. Watch for cyclic IO timeouts greater than 2× the configured update time.
  2. Camera health: in In-Sight Explorer, run the job in Live mode at 10 fps and verify Pass rate > 99% over 100 triggers.
  3. Grid calibration residual: MotoSight's calibration report must show residual < 0.5 mm in X/Y and 0.5° in Rz. If the residual is high, recheck grid flatness and lighting.
  4. User-frame drift test: re-teach all three fiducials three times. The standard deviation of the resulting frame origin must be < 0.3 mm.
  5. End-to-end pick test: run 50 picks with parts placed at random orientations. Check the actual robot position vs. the In-Sight-detected position; deviation should be < 1.0 mm in X/Y.
  6. PLC hand-shake timing: with a logic analyzer or TIA trace, confirm the camera's results arrive within 1 cycle (1 ms) of the trigger.
Safety: before running the cell, validate the e-stop circuit on the Motoman controller and the safety relay chain on the S7-1500 F-CPU (if used). Vision offset is non-deterministic in absolute terms; do not use it for force-limited or collaborative trajectories without additional guarding.

Troubleshooting Matrix

Symptom Probable Cause Remedy
AR (Application Relationship) fails at startup PROFINET name mismatch, DCP blocked by switch Re-assign device name, enable DCP, disable IGMP snooping on switch port
Cyclic IO with 3-4 ms latency, not 1 ms Update time set too high or store-and-forward switch Set update time = 1 ms, replace with cut-through PROFINET switch
In-Sight Pass rate drops to 70% under shop-floor lights Autoexposure not locked, IR contamination Lock exposure, add band-pass filter, add shrouding
Residual after grid calibration > 2 mm Grid not flat, TCP length wrong Verify TCP with dial indicator, place grid on flat reference, repeat calibration
Robot position drifts 5-10 mm during shift day User frame not re-mastered; fixture unclamped Re-teach UF[1] at shift start, verify fixture clamp force
PLC never receives Done from robot PN slot map offset wrong, byte order swapped Use PRONETA to read live PN data, check Big-Endian vs Little-Endian
STATUS=0xFF persistent in PLC In-Sight job not loaded, or no image acquired Save & deploy job, check trigger wiring, inspect lens for contamination

Extended Engineering Considerations

Update Rate vs. Cycle Time

A 1 ms PN update time is the floor for hand-off latency, but a pick-and-place cell typically spends 200-500 ms in motion. The dominant cycle-time gain comes from running the In-Sight acquisition in parallel with the previous part's placement, not from shrinking the PN update time. The MotoSight 2D product page and the Cognex VGR application note discuss parallel-trigger strategies.

Job Selection from the PLC

To run multiple part types, map 8 job slots to PN output bits. The In-Sight firmware allows up to 255 jobs per sensor. Validate job change on the PLC side by waiting for JobAck in the input slot before triggering; otherwise stale results from the previous job can corrupt the offset.

Calibration Backup and Recipe Handling

Treat the In-Sight .job file, the MotoSight calibration matrix, and the S7-1500 recipe DB as a single versioning unit. TIA Portal's Project History can store DB versions; use the SD card slot on the In-Sight 9000/3900 to clone jobs to spare cameras. After a controller firmware update on the Motoman, re-validate the user frame and grid calibration—YRC1000 firmware updates can reset calibration data.

FAQ

What firmware does In-Sight need for PROFINET with a Motoman YRC1000?

In-Sight firmware 5.7 or later is recommended on the 9000 and 3900 series, with the PROFINET protocol enabled in In-Sight Explorer. The Motoman YRC1000 must run firmware YAS2.81 or later with the PROFINET Slave option installed and a MotoSight 2D license active on the controller.

How many fiducials are required for a stable user frame?

Three non-collinear fiducials are sufficient: the ORG point, the XX point on the X axis, and the XY point defining the plane. Place them at least 50 mm apart with a triangle ratio near 4:3:1 to minimize numerical noise in the cross-product used to derive Z.

What grid residual is acceptable for pick-and-place?

Under 0.5 mm in X/Y and 0.5° in Rz is typical for general pick-and-place. For high-precision cells (1 mm or tighter part placement), require under 0.2 mm / 0.2° and re-validate the calibration weekly or after any collision event.

Can the S7-1500 read the In-Sight results as record data instead of cyclic I/O?

Yes. Use RDREC (SFB52) or RDREC with the In-Sight record index. The In-Sight PROFINET manual describes the available record indices for status, results strings, and image statistics. Cyclic I/O is preferred for low latency; record data is preferred for diagnostic pulls.

Why does the In-Sight Pass rate degrade in production but not at commissioning?

Most often it is lighting change (overhead factory lights, IR from heaters) or vibration moving the fixture. Lock the camera exposure, add a band-pass filter or shrouding, and verify the fixture is rigidly clamped. Re-running the calibration grid after mechanical changes is faster than re-tuning the tools.