CP 5511 Windows 7 Compatibility: Migration to CP 5512, CP 5711, and USB Adapters
The Siemens CP 5511 (Article No. 6GK1551-1AA00) is a Type II PCMCIA communications processor historically used to connect SIMATIC programming devices (PGs) and PCs to MPI and PROFIBUS networks. Field reports and Siemens' own support documentation confirm that the CP 5511 is not functional on Windows 7. The root cause is not a Siemens driver bug — the underlying 16-bit PCMCIA Card Services subsystem was deprecated by Microsoft and removed from the Windows 7 kernel. This article documents the root cause, the official Siemens migration path to the CP 5512 (CardBus) and the CP 5711 (USB), and the practical constraints of the third-party USB-to-MPI/DP converter (6GK1571-0BA00-0AA0) used by technicians who need a compact, laptop-friendly replacement.
1. Affected Hardware and Software Stack
1.1 CP 5511 Identification
| Attribute | Value |
|---|---|
| Siemens Article Number | 6GK1551-1AA00 |
| Bus Interface | 16-bit PCMCIA Type II |
| Network Protocols | MPI, PROFIBUS DP, S7 routing |
| PROFIBUS Baud | 9.6 kbps to 12 Mbps |
| Power | 5 V supplied by PCMCIA socket |
| Driver Package | SIMATIC NET PC Software (legacy) |
| Last OS Support | Windows XP Professional, Windows 2000 |
| Windows 7 Support | None (16-bit PCMCIA removed) |
The CP 5511 ships with a 9-pin D-sub PROFIBUS connector and a 16-bit PCMCIA edge connector. The card communicates with the host via the legacy 16-bit PC Card standard. Windows 7 ships with a 32-bit CardBus / 16-bit PCMCIA host controller stack, but the 16-bit Card and Socket Services that the CP 5511 enumeration script depends on are not present. Siemens support entry 4241537 describes the requirement and the supported card-and-socket services revision required by the device.
1.2 Companion Software Versions
| Software | Last CP 5511-Compatible Version | Windows 7 Status |
|---|---|---|
| SIMATIC NET PC Software | Edition 2008 (V8.0) and earlier | CP 5511 driver dropped |
| STEP 7 V5.5 + SP4 | Set PG/PC Interface = CP 5511 | Not recognized on Win 7 |
| STEP 7 Professional (TIA Portal) V13+ | CP 5511 not selectable | Use CP 5711 / CP 5512 |
| WinCC flexible 2008 SP5 | CP 5511 selectable | Runtime fails to bind |
| ProSave / SIMOTION Scout | CP 5511 selectable through V4.x | Not supported on Win 7 |
2. Root Cause: 16-bit PCMCIA Was Removed From the Windows 7 Kernel
The CP 5511 is a 16-bit PC Card. Microsoft deprecated 16-bit PC Card support in Windows Vista and removed it in Windows 7. The host-side driver relies on the legacy card.exe Card and Socket Services component and the PCMCIA.SYS enumerator, neither of which is installed by the Windows 7 in-box driver set. When a user inserts the CP 5511:
- The Windows 7 PCMCIA / CardBus class driver sees the device but cannot match it to a 16-bit socket services provider.
- Device Manager shows the device under Other devices with a yellow exclamation or under PCMCIA adapters with Code 28 ("The drivers for this device are not installed") or Code 52 ("Windows cannot verify the digital signature").
- SIMATIC NET's Set PG/PC Interface utility cannot bind to the device; the CP 5511 entry is greyed out or absent from the interface list.
- STEP 7 "Accessible Nodes" or TIA Portal "Online > Accessible nodes" returns an empty node list even when the PLC is online and the bus terminator is correctly installed.
This is the same root cause that affects every other 16-bit PC Card (modems, older wireless cards, etc.) on Windows 7. A new driver from Siemens will not fix it because the upstream OS support no longer exists.
3. Official Migration Paths
Siemens offers two direct successors and a third-party compact option. Each has different use-case, mechanical, and electrical trade-offs.
3.1 CP 5512 — 32-bit CardBus (Direct Successor)
| Attribute | Value |
|---|---|
| Article Number | 6GK1551-2AA00 |
| Bus Interface | 32-bit CardBus (PCMCIA Type II) |
| OS Support | Windows XP, Windows 7 (32/64-bit), Windows 10 (with SIMATIC NET V14+) |
| Mechanical Form Factor | CardBus card, same envelope as CP 5511 |
| Network Protocols | MPI, PROFIBUS, S7 routing — identical to CP 5711 |
| PC Station Use | Supported with SIMATIC NET PC Software |
| Power | 3.3 V supplied by CardBus socket |
The CP 5512 is functionally identical to the CP 5711 but uses a 32-bit CardBus socket. It is the recommended drop-in replacement for users with a notebook that has a true PC Card (CardBus) slot, including many industrial Panasonic Toughbooks, Siemens Field PG M4/M5, and older Dell Precision / Lenovo ThinkPad T-series workstations. Note that an ExpressCard slot is not a CardBus slot and will not accept the CP 5512 without an ExpressCard-to-PC-Card adapter, which is not officially supported.
3.2 CP 5711 — USB (Universal Replacement)
| Attribute | Value |
|---|---|
| Article Number | 6GK1571-1AA00 |
| Bus Interface | USB 2.0 Full Speed |
| OS Support | Windows 7, 8, 10, 11 (32/64-bit) via SIMATIC NET V12+ |
| Mechanical Form Factor | External brick, integrated PROFIBUS D-sub |
| Network Protocols | MPI, PROFIBUS, S7 routing, PROFINET IO (limited) |
| PC Station Use | Fully supported |
| Power | Bus-powered or external 24 V DC |
The CP 5711 is the universal solution and is the only one that works on every modern laptop. It is also the only one that is fully certified for SIMATIC Net PC Stations (i.e., a PC acting as a DP master, IO controller, or S7 OPC server with the SIMATIC NET V14+ PC suite).
3.3 USB-to-MPI/DP Compact Adapter (6GK1571-0BA00-0AA0)
| Attribute | Value |
|---|---|
| Article Number | 6GK1571-0BA00-0AA0 |
| Bus Interface | USB 1.1/2.0 |
| OS Support | Windows XP, Vista, 7 (32-bit only; 64-bit requires unsigned-driver mode or KNOWN ISSUES workaround) |
| Mechanical Form Factor | Pocket-size, ~15 cm cable |
| Network Protocols | MPI, PROFIBUS DP (master/slave), PPI |
| PC Station Use | Not supported — programming only |
| Power | 24 V drawn from the PROFIBUS / MPI socket on the partner |
This compact USB adapter is the technician's everyday tool: it lives in a laptop bag, draws all required operating power from the bus connector, and is far more portable than the CP 5711 brick. The trade-off is that it cannot be used in a SIMATIC NET PC Station configuration, and it has electrical constraints on which sockets will power it. See section 5.
4. Decision Matrix: Which Adapter for Which Workflow?
| Workflow | CP 5512 | CP 5711 | 6GK1571-0BA00-0AA0 |
|---|---|---|---|
| STEP 7 V5.5 programming on Win 7 | ✓ | ✓ | ✓ |
| TIA Portal V13+ online commissioning | ✓ | ✓ | ✓ (limited baud) |
| WinCC flexible / TIA HMI download | ✓ | ✓ | ✓ |
| SIMATIC NET PC Station (DP master) | ✓ | ✓ | ✗ |
| S7 OPC server on the engineering PC | ✓ | ✓ | ✗ |
| Laptop with no CardBus slot | ✗ | ✓ | ✓ |
| Drive or ET200 PROFIBUS socket | ✓ | ✓ | ✗ (no 24 V present) |
| Field service (portability priority) | ○ | ✗ (bulky) | ✓ |
| Cost (relative) | Low | High | Lowest |
For most service engineers running STEP 7 on a modern laptop, the 6GK1571-0BA00-0AA0 is the right answer. For SIMATIC NET PC stations in a control room, the CP 5711 is mandatory. The CP 5512 is the best fit for legacy Field PG M-series notebooks still in service.
5. Powering the USB-to-MPI/DP Compact Adapter
The compact 6GK1571-0BA00-0AA0 adapter draws +24 V DC from pin 7 (+) and pin 2 (GND) of the partner's PROFIBUS connector. This voltage is normally supplied by the CPU or HMI panel's MPI/PROFIBUS interface. If the partner device does not source 24 V on the bus connector, the adapter will enumerate, LED-status will be ambiguous, and S7 frames will silently fail.
5.1 Sockets That WILL Power the Adapter
- S7-300 CPU MPI/DP port (X1) — supplies 24 V isolated from the backplane.
- S7-400 CPU MPI/DP port — supplies 24 V.
- ET 200S / ET 200pro IM DP master port — supplies 24 V on the bus connector when configured as a passive station.
- SIMATIC HMI MPI/PROFIBUS port (e.g., TP177B, MP277, Comfort panels) — supplies 24 V.
- SIMATIC Field PG MPI port — supplies 24 V.
5.2 Sockets That WILL NOT Power the Adapter
- Sinamics / Micromaster / Masterdrives PROFIBUS connector — drives do not source 24 V on the DP port. The adapter will not enumerate.
- ET 200eco / ET 200AL block I/O PROFIBUS connector — passive I/O with no local 24 V source on the bus pins.
- Passive DP repeater segment — no terminator power.
- Some third-party DP slave connectors without 24 V jumper.
5.3 LED Diagnostics on the 6GK1571-0BA00-0AA0
| LED | State | Meaning |
|---|---|---|
| Power (PWR) | Steady green | 24 V from bus + 5 V from USB present, internal MCU running |
| Power (PWR) | Off or flashing | Bus 24 V missing OR USB not enumerated |
| Activity (ACT) | Flickering green | Token passing / frame activity on PROFIBUS |
| Activity (ACT) | Steady on | Bus error: short, missing terminator, duplicate address |
| Activity (ACT) | Off | No bus traffic, or partner powered off |
6. Installation Procedures
6.1 CP 5512 Installation on Windows 7
- Install SIMATIC NET PC Software V12 SP2 or later (V14 SP1 recommended for full Windows 7 x64 signed-driver support).
- Insert CP 5512 into a free CardBus slot. The device is hot-pluggable but cold-boot insertion is more reliable on Win 7.
- Open Set PG/PC Interface (control panel applet). Select CP5512 (CardBus) > MPI / PROFIBUS.
- Assign node address (default 0) and highest station address (HSA = 15 for MPI, 31 / 63 for PROFIBUS).
- Properties > MPI / PROFIBUS bus parameters > transmission rate = 187.5 kbps (MPI default) or 1.5 Mbps (PROFIBUS standard).
- Apply. Restart S7DOS service:
net stop "S7DOS" && net start "S7DOS"from an elevated command prompt. - Verify with STEP 7 Accessible Nodes or Diagnostics > Bus Nodes.
6.2 CP 5711 Installation on Windows 7
- Install SIMATIC NET PC Software V12 or later.
- Connect CP 5711 to a USB 2.0 port. The CP 5711 appears as a USB composite device with two interfaces (PROFIBUS + auxiliary).
- Allow Windows to install the signed driver (part of the SIMATIC NET install). If prompted for a location, point to
%ProgramFiles%\Siemens\Automation\SIMATIC_NET\drivers\CP5711. - Open Set PG/PC Interface and select CP5711 > MPI / PROFIBUS.
- Configure bus parameters identically to CP 5512.
- For PC Station use, also open SIMATIC NET Configuration Console and bind the CP 5711 to the appropriate OPC / DP / IO application slot.
6.3 6GK1571-0BA00-0AA0 Installation on Windows 7
- Do not connect the adapter before installing the driver.
- Insert the driver CD or extract the driver package (downloadable from the Siemens support portal). The driver is shipped in
USB-to-MPI-DP\Driver\Win7\x86and\x64folders. - On Windows 7 x64, disable driver signature enforcement or use the test-mode boot option. The driver is unsigned:
bcdedit /set testsigning onfollowed by a reboot. - Connect the adapter to USB. Windows Device Manager prompts for the driver; point it to the appropriate x86 or x64 folder.
- Connect the D-sub connector to the CPU or HMI MPI/PROFIBUS port. Confirm the PWR LED illuminates.
- Open STEP 7 / TIA Portal and select PC Adapter (USB) / PC Adapter (MPI) / PC Adapter (PROFIBUS) in Set PG/PC Interface.
- Set the PG/PC address (default 0) and baud (1.5 Mbps for PROFIBUS, 187.5 kbps for MPI).
HsLoader-style drivers; in that environment, a virtualized Windows 7 instance (VirtualBox / VMware) with USB passthrough is the most reliable way to keep the 6GK1571-0BA00-0AA0 working.7. Verification Procedure
- From an elevated command prompt, run
pnputil /enum-devices /class Netand confirm the Siemens MPI/PROFIBUS interface is listed with status OK and no Code 28 / 52. - Start the S7DOS service:
net start S7DOS. Confirm the service enters the Running state. - Open STEP 7 Set PG/PC Interface > Diagnostics. The bus statistics must show Token rotation time < 50 ms and Frame errors = 0 over a 30-second sample.
- Run Accessible Nodes. The target CPU must appear with its configured MPI / PROFIBUS address and firmware version.
- Download a small test block to a RAM-only DB and verify online consistency.
8. Troubleshooting Matrix
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
| CP 5511 not detected on Windows 7 at all | 16-bit PCMCIA removed from kernel | Replace with CP 5512 / CP 5711 / 6GK1571-0BA00-0AA0. Do not waste time on a driver update. |
| CP 5512 not detected on Windows 7 x64 | Wrong driver set installed (e.g., V8.0 from the Win XP era) | Install SIMATIC NET V12 SP2 or later; older packages lack the x64 signed driver. |
| CP 5711 enumerates but no bus traffic | USB selective suspend disabled; cable defective | Disable USB selective suspend in Power Options; replace the USB cable. |
| 6GK1571-0BA00-0AA0 PWR LED off | 24 V missing on partner connector | Move adapter to a CPU or HMI port. Do not use on a drive DP port without external 24 V injection. |
| ACT LED steady on, no Accessible Nodes | Bus short or duplicate station address | Power down the segment; check D-sub pin 6 (VP) and pin 5 (DGND) for short; verify station addresses are unique. |
| Adapter detected but Accessible Nodes empty | Baud rate mismatch (e.g., 12 Mbps DP vs 1.5 Mbps adapter) | Set PG/PC baud = bus baud. For DP, 1.5 Mbps and 12 Mbps are both common; 12 Mbps adapters require CP 5711. |
| Step 7 hangs in "Establishing connection" | PG/PC address collides with CPU address | Set PG/PC address > CPU address. Default 0 often conflicts with the CPU's default MPI 2. |
| TIA Portal: "Online: No connection possible" | Online access security set to "No access" in project properties | Project tree > device > Properties > Protection > Connection mechanisms > Permit access with PUT/GET or Permit online access. |
| Driver install fails with Code 52 on Win 7 x64 | Unsigned driver, secure boot enabled | Boot in test-signing mode: bcdedit /set testsigning on, reboot. |
9. Long-Term Roadmap
The CP 5511, CP 5512, and 6GK1571-0BA00-0AA0 are all in the Siemens PMD (Product Maintenance & Discontinuation) lifecycle. For new installations, Siemens recommends the CP 5711 (USB) or a PC Station with a CP 1623 / CP 1626 PCI-Express card for control-room applications. For field service, the compact USB-to-MPI/DP converter remains the practical option, with the caveat that it must be paired with a CPU or HMI socket that sources 24 V.
Engineers maintaining Windows XP estates (which is still common in pulp & paper and water/wastewater sectors) can continue to use the CP 5511 indefinitely. As soon as the engineering PC migrates to Windows 7 or later, the CP 5511 must be retired.
10. Quick Field-Reference Summary
- CP 5511 on Win 7: Will not work. Replace.
- Compact laptop with no CardBus slot: Use the 6GK1571-0BA00-0AA0 USB adapter, but only on a CPU or HMI port.
- Drive or ET200 PROFIBUS socket with no 24 V on the bus: Use the CP 5711 with external 24 V supply, or a CP 1623 PCI-Express card in a desk-bound PC.
- SIMATIC NET PC Station (DP master, OPC): Use the CP 5711 or CP 1623. The 6GK1571-0BA00-0AA0 is programming-only.
- Existing Field PG M4 / M5 with CardBus slot: CP 5512 is the lowest-effort drop-in.
- Windows 10 1607+ with the compact USB adapter: Plan for a Windows 7 VM with USB passthrough.
FAQ
Is the CP 5511 supported on Windows 7?
No. The CP 5511 is a 16-bit PCMCIA card, and Windows 7 removed 16-bit Card and Socket Services from the kernel. No firmware or driver update can restore functionality. Migrate to the CP 5512 (CardBus), CP 5711 (USB), or the 6GK1571-0BA00-0AA0 compact USB adapter.
What is the direct replacement for the CP 5511?
The official successor is the CP 5512 (Article No. 6GK1551-2AA00), a 32-bit CardBus card with the same PROFIBUS/MPI capabilities as the CP 5711. For laptops without a CardBus slot, the CP 5711 (6GK1571-1AA00) is the universal USB replacement.
Can the 6GK1571-0BA00-0AA0 USB-to-MPI/DP adapter be used in a SIMATIC NET PC Station?
No. The 6GK1571-0BA00-0AA0 is a programming-only adapter. For a PC Station acting as a DP master or OPC server, you need a CP 5711, CP 1623, or CP 1626.
Why does the 6GK1571-0BA00-0AA0 not work on a Sinamics drive PROFIBUS port?
The compact adapter draws +24 V from the bus connector. Sinamics, Micromaster, and similar drives do not source 24 V on the DP port. Use the adapter on a CPU or HMI port, or inject 24 V externally into the bus cable.
Does the CP 5711 work in a SIMATIC NET PC Station on Windows 7 x64?
Yes. Install SIMATIC NET V12 SP2 or later (V14 SP1 is recommended), plug the CP 5711 in, select it in the SIMATIC NET Configuration Console, and bind it to the desired application slot. The driver is x64-signed from SIMATIC NET V12 onward.