Problem Description

When using a Siemens CP 5711 USB adapter (order number 6GK1571-1AA00) to download or upload a STEP 7 project to an S7-300 CPU 315-2DP over the integrated PROFIBUS-DP interface (X2 / MPI/DP), the connection attempt rotates indefinitely in the STEP 7 "Establish Online Connection" dialog and never reports an online partner. The same CP 5711 connects to the same CPU without error when the project is set to the MPI/DP port's MPI mode, isolating the fault to the PROFIBUS path rather than the hardware or driver.

The root cause is almost always one of the following:

  1. PROFIBUS is not activated in the offline project (no DP master system configured on the CPU's DP interface) — the most common cause.
  2. The CP 5711 is configured to operate as the only bus master and the real DP master is also online.
  3. The PROFIBUS bus parameters (baud rate, bus profile, highest station address) in STEP 7 disagree with the online network.
  4. Termination or cable polarity is wrong, leaving the CP 5711 outside the segment.
  5. USB driver, COM port assignment, or PG/PC interface selection is wrong.
The CP 5711 must be installed in Windows as a USB device and be selected as the active access point in Set PG/PC Interface. The LED pattern on the CP 5711 housing is the fastest way to distinguish a hardware/USB fault from a PROFIBUS protocol fault.

CP 5711 Hardware and Firmware Reference

Reference data for the CP 5711 Operating Instructions (Siemens):

Parameter Value
Order number (MLFB) 6GK1571-1AA00
Interface to host USB 2.0 full speed (12 Mbps)
Interface to field PROFIBUS DP / MPI / PPI, 9-pin D-sub female
PROFIBUS baud rates 9.6 kbps, 19.2 kbps, 45.45 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, 12 Mbps
Bus profile DP, standard, universal (DP/FMS)
Galvanic isolation 500 V (USB) / 500 V (PROFIBUS)
Power Bus-powered from USB (typ. 250 mA)
Required STEP 7 version STEP 7 V5.5 + SP2 or higher; TIA Portal V13+ with HSP for the CP 5711
Driver Siemens USB-to-PROFIBUS driver ("CP 5711"), creates a virtual COM port
A red LED that flashes cyclically (e.g. 1× / 3× / 5×) at power-up indicates a USB error — the CP 5711 has not enumerated. This is unrelated to PROFIBUS and must be cleared (driver, USB hub current, cable) before any PROFIBUS diagnosis is meaningful.

Prerequisites for a Healthy CP 5711 PROFIBUS Link

  • CP 5711 driver installed; a new COM port is visible in Windows Device Manager under "Ports (COM & LPT)" — note the number (commonly COM8..COM20).
  • PG/PC interface set to CP5711 (USB) -> PROFIBUS in Set PG/PC Interface.
  • STEP 7 V5.5 SP2 or TIA Portal V13+ with CP 5711 HSP installed.
  • PROFIBUS cable from CP 5711 D-sub to the S7-300 9-pin D-sub (X2). A standard PROFIBUS connector with PG socket (6ES7972-0BB12-0XA0 or the older 6ES7972-0BA12-0XA0) on the CPU side and a 9-pin male-to-male cable to the CP 5711 is required. Straight-through 1:1 wiring — pin 3 = B (red), pin 8 = A (green), shield on shell.
  • Termination active only at the two physical ends of the PROFIBUS segment. The CP 5711 must therefore be a bus terminator (i.e. at one end) or installed as a drop line to a bus where the two ends are already terminated — not in the middle of a terminated segment.
  • 24 V to the S7-300 PS 307, CPU in RUN or STOP (STOP is sufficient for download).

Diagnostic Procedure: CP 5711 → S7-315-2DP (PROFIBUS)

Work the steps in order. Each step is a gate — do not proceed to the next until the current one passes.

Step 1 — Verify CP 5711 enumeration on USB

  1. Open Windows Device Manager → Ports (COM & LPT). The entry "CP5711 (USB)" or similar must appear with a COM number.
  2. If the entry shows a yellow exclamation mark, re-install the driver from the STEP 7 DVD (folder CP5711\Driver) or the latest Siemens CP 5711 documentation package.
  3. Unplug the CP 5711, plug it into a different USB port (avoid unpowered hubs), and observe the LED: solid green = ready, off = no USB power, red = driver / firmware fault.

Step 2 — Configure the PG/PC interface correctly

  1. Start → SIMATIC → STEP 7 → Set PG/PC Interface (or Control Panel → PG/PC Interface).
  2. Access point of the application: S7ONLINE (STEP 7) (or CP5711.PROFIBUS.1 if you created a dedicated access point).
  3. Interface parameterization: CP5711 (USB) – PROFIBUS. Click Properties and confirm:
    • Station address: 0 (PG) or 1 — the CP 5711 is a master and must have a unique address on the segment.
    • Profile: DP.
    • Transmission speed: Auto (or fixed at 1.5 Mbps to start — auto-detect requires a clean, terminated segment).
  4. Click Diagnostics in the CP 5711 Properties dialog. The window offers two tests: Test (driver / USB / CP internal) and Read (live PROFIBUS bus scan). Run Test first — it must report OK. If it fails, do not run Read; fix the driver / cable / port first.
  5. Run Read. A list of all reachable PROFIBUS nodes is shown with their baud rate and station address. The S7-315-2DP (default address 2, default baud 1.5 Mbps) must appear. If it does not, the fault is at the bus level, not the project level — skip to Step 6.

Step 3 — Confirm PROFIBUS is active in the offline project

This is the single most common cause of an "it rotates forever" PROFIBUS connection with a CPU 315-2DP.

  1. In SIMATIC Manager, open the S7 project → Hardware (HW Config).
  2. Double-click the CPU 315-2DP → tab DP (or PROFIBUS interface). Confirm:
  • Interface is set to PROFIBUS, not MPI.
  • A DP master system is configured and at least the CPU itself is a DP master on it.
  • An address exists in the master system (the CPU's own DP address, default 2).

If the interface shows MPI, change it to PROFIBUS, give it a station address (e.g. 2), and save / compile the project. Re-download to the CPU (use the working MPI port for this one download, since PROFIBUS still cannot connect).

The CPU 315-2DP has two physical interfaces on the front: X1 = MPI/DP, X2 = MPI/DP (the second one on the -2DP/PN variants). The PROFIBUS network must be wired to the X2 port (labelled DP) and the interface in HW Config must be type DP-Master or DP-Slave — not MPI. Many project templates leave the CPU's DP interface as MPI by default.

Step 4 — Re-attempt "Establish Online Connection" over PROFIBUS

  1. In SIMATIC Manager, select the S7 station → PLC → Establish Online Connection.
  2. In the dialog choose PG/PC interface: CP5711 (USB) – PROFIBUS, target station address = CPU's DP address (default 2), target slot = 2 (for the CPU rack slot 2).
  3. Click OK. The "rotating wheel" should clear within 5–10 s and the online view should open.

If it still rotates, the offline project's DP master system parameters (HSA, baud rate, Tslot, watchdog) do not match the live bus. The PG/PC interface's Read test in Step 2 only reports active devices; it does not flag parameter mismatches. Move to Step 5.

Step 5 — Match bus parameters between PG and CPU

  1. Open the DP master system → Properties → PROFIBUS in HW Config. Note the baud rate, the highest station address (HSA, default 126), and the bus profile.
  2. Open the CP 5711 PG/PC properties (Step 2) and force the same baud rate and HSA. Auto detection is fragile on segments with mixed devices or reflection problems — pin both sides to a fixed 1.5 Mbps for diagnosis.
  3. Save, exit, retry the online connection.

Step 6 — Physical layer checks (cable, termination, addresses)

  1. CP 5711 segment position: confirm it is a terminator or on a drop line. End termination must be ON only at the two ends of the segment (resistor in the PROFIBUS connector visible between pins 3 and 8). Disable termination on every intermediate node.
  2. Cable polarity: A (green) → pin 8, B (red) → pin 3. The CP 5711 end is a standard 9-pin male; the S7-300 end is the PROFIBUS connector with PG socket. Reverse polarity yields activity on the bus (PG/PC Read still shows devices) but no master handshake — easy to mistake for a project fault.
  3. Station address uniqueness: every device on the segment must have a unique address. The CPU default is 2, the CP 5711 PG address is set in Step 2. If two devices share 2, the CP 5711 Read test still passes but Establish Online Connection rotates forever.
  4. Disconnect all other DP slaves and try a CPU-only segment. If the connection works, a downstream slave is duplicating an address or holding the bus.

Step 7 — "PG/PC is the only master on the bus" option

In some STEP 7 / TIA Portal builds, the CP 5711 PG/PC parameter dialog has a checkbox PG/PC is the only master on the bus. If the S7-315-2DP's DP master system has another PROFIBUS master (e.g. an HMI, a PLC-CPU acting as master, or a CP 343-1 CP on the same bus), and this checkbox is enabled, the CP 5711 will refuse to take the token and the online connection dialog rotates indefinitely.

Workaround: deselect PG/PC is the only master on the bus, especially when the CPU is itself the only DP master. If there really is a second master on the same segment, the bus topology must be split or the CP 5711 used only as a passive diagnostic observer (read-only).

Verification

Successful commissioning is demonstrated by the following three checks:

  1. CP 5711 LED: solid green during the active PROFIBUS session, returning to solid green when disconnected.
  2. SIMATIC Manager → PLC → Establish Online Connection: connects within 5 s, online view shows the CPU as reachable, online/offline comparison becomes available.
  3. PG/PC interface Diagnostics → Read: S7-300 CPU 315-2DP is visible with its configured DP station address and the bus baud rate is reported correctly.

Quick-Reference Troubleshooting Matrix

Symptom Likely cause Fix
CP 5711 LED off USB not powered / driver not loaded Reinstall driver, change USB port, replace cable
CP 5711 LED solid red Hardware fault or FW error Re-flash firmware per CP 5711 manual; replace if persistent
LED green, STEP 7 rotates forever Project has no DP master on CPU's DP interface HW Config → set CPU DP interface to PROFIBUS, build DP master system, re-download
Diagnostics → Read shows no CPU Physical layer: cable, termination, polarity, address Check A/B wiring, termination at both ends, address 2 free, baud rate pinned
Diagnostics → Read shows CPU, but no online connection Bus parameter mismatch or duplicate master Match baud rate/HSA in CP 5711 properties to HW Config; uncheck "PG/PC is only master"
MPI works, PROFIBUS does not CPU interface type = MPI in HW Config Change interface to PROFIBUS in HW Config and recompile
Connection succeeds only after CPU memory reset Corrupted project on CPU with wrong DP master ID MRES, then download a clean project over MPI, then switch to PROFIBUS

Field-Notes and Caveats

  • A connection that partially works — i.e. the CP 5711 Read test shows devices but Establish Online Connection hangs — is almost always a bus parameter mismatch, not a hardware fault. Pin both ends to a fixed baud rate (1.5 Mbps is the most robust on short PG/PC segments).
  • The CP 5711 draws its power from the USB port. On underpowered hubs or long USB cables, enumeration succeeds but the PROFIBUS transceiver can lose sync, producing intermittent online connections. Use a direct port or a powered hub.
  • The PROFIBUS connector on the S7-300 side must have its DP termination ON if the CPU is the end of the segment. The internal S7-300 bus terminator inside the CPU does not exist; termination lives in the connector.
  • If the project has not had the CPU's DP interface enabled, downloading over MPI with PROFIBUS still unconfigured is the only way to recover — you cannot use the failing PROFIBUS path to deliver the fix.
  • STEP 7 V5.5 SP2 and later recognise the CP 5711 natively. Earlier service packs may list it as "unknown" in the PG/PC interface; install SP2 or later before troubleshooting further.
  • TIA Portal users must install the CP 5711 Hardware Support Package (HSP) and select PC Interface → CP5711 PROFIBUS in the project tree. The HSP is bundled with TIA Portal updates or available from the Siemens support portal.
Always cross-check the CPU's DP interface address with the address set in the connected PROFIBUS connector. The CPU 315-2DP does not store its PROFIBUS address in the connector — the address is configured in HW Config and stored in the CPU's system data. After a memory reset, the CPU reverts to the last downloaded address (or default 2 if never configured).

FAQ

Why can my CP 5711 connect to the S7-315-2DP over MPI but not over PROFIBUS?

The most common reason is that the offline project has the CPU's second interface configured as MPI, not PROFIBUS. Open HW Config, change the CPU's DP interface type to PROFIBUS, build a DP master system, recompile, and re-download (you can use the working MPI path to deliver this fix).

What does a red flashing LED on the CP 5711 mean?

It indicates a USB-side error: the driver is not loaded, the USB port cannot deliver enough current, or the CP 5711 firmware has failed. Reinstall the CP 5711 driver, move to a powered USB port, or re-flash the firmware per the Siemens CP 5711 manual. Once the LED returns to solid green, retry the PROFIBUS connection.

How do I check the baud rate and address of devices on the bus from my PC?

In Set PG/PC Interface → CP5711 (USB) – PROFIBUS → Properties &rrightarrow Diagnostics, run the Read test. It scans the bus and lists every active PROFIBUS node with its station address and the detected baud rate (9.6 kbps up to 12 Mbps). If the CPU does not appear, the fault is physical (cable, termination, polarity, or power).

Does the S7-315-2DP support the CP 5711 directly, or do I need an MPI/DP converter?

No converter is required. The CP 5711 is a native USB-to-PROFIBUS/MPI/PPI adapter (MLFB 6GK1571-1AA00). The CPU 315-2DP exposes a 9-pin PROFIBUS-DP interface on its front panel; connect the CP 5711 directly to it using a PROFIBUS connector with PG socket and a 9-pin male-to-male PROFIBUS cable.

What is the default PROFIBUS address of a CPU 315-2DP?

Factory default is 2. The address is stored in the CPU's system data and is set in HW Config under the DP interface properties. The same value must be unique on the segment — if another device (HMI, slave, second PG) also uses address 2, the CP 5711 will see traffic but cannot establish a unique connection to the CPU.