CP343-1 to Honeywell DCS: S7 Communication Data Limits and TCP Coexistence
When a Siemens S7-300 CPU is connected to a Honeywell Experion DCS server (or any third-party HMI/SCADA) that uses a CP 1613 with S7 Communication, two distinct communication paths become available on the CP 343-1: the S7 connection (handled by the CPU operating system) and the TCP / SEND-RECEIVE interface (driven from the user program through FC5 AG_SEND and FC6 AG_RECV). Engineers frequently ask whether the FC5/FC6 blocks are required, what the maximum payload is on each path, and how to handle a configuration that appears to mix both protocols on a single CP. This reference consolidates the rules, sizing limits, and configuration steps for the part number 6GK7 343-1CX10-0XE0 (CP 343-1 Lean) and CPU 315-2DP against a Honeywell DCS station running S7 Communication through a CP 1613.
1. Hardware Identification and Roles
The hardware referenced in this article forms a deterministic three-node path. Each device has a single, well-defined role in the topology.
| Component | Order Number / Type | Role | Key Capability |
|---|---|---|---|
| CPU | CPU 315-2 DP (6ES7 315-2AG10-0AB0 family) | S7-300 central processor; runs the S7-300 program and the integrated S7 Communication OS service | Handles S7 connections natively; exposes BSEND/BRECV (SFB 12/13) and PUT/GET via the operating system when an S7 connection is configured |
| Communications Processor | CP 343-1 Lean, 6GK7 343-1CX10-0XE0 | Industrial Ethernet CP for S7-300 / SINUMERIK 840D sl; provides PROFINET, TCP, UDP, ISO-on-TCP, and S7 Communication transport | One S7 connection plus the SEND/RECEIVE (FC5/FC6) interface; 8 KB transport buffer |
| SIMATIC PC Station | CP 1613 (6GK1 161-3AA00) in the DCS server | PCI card providing the PC station with a S7-400-compatible Ethernet interface for the SIMATIC NCM PC manager | Acts as the S7 Communication partner; is configured as a S7-300 / S7-400 station type in STEP 7 / NCM PC |
| SCADA / DCS | Honeywell Experion Server (or any third-party HMI supporting the Siemens S7 protocol) | S7 client on top of CP 1613 driver (e.g. Experion's S7-TCP channel) | Polls configured DBs from the PLC through the OS-managed S7 connection |
The CP 343-1 Lean is documented in the Siemens manual CP 343-1 Lean (6GK7343-1CX10-0XE0) Operating Instructions. The CPU 315-2 DP is documented at CPU 31xC and CPU 31x - Technical Data and the S7 Communication functions (PUT/GET, USEND/URCV, BSEND/BRCV) are described in the S7-300/400 System and Standard Functions Reference Manual.
2. The Two Communication Paths on CP 343-1
Engineers regularly conflate "Industrial Ethernet" with a single protocol. In reality, the CP 343-1 Lean supports two functionally independent, simultaneously active paths to the same remote partner:
2.1 Path A – S7 Connection (OS-managed)
An S7 connection is established by the operating system of the CPU 315-2DP and transported by the CP 343-1 Lean across Industrial Ethernet. The connection is configured once in STEP 7 / NCM PC using a typed connection (e.g. S7 connection) bound to a CP 343-1 interface, and the CP keeps it alive without any block calls in OB 1. The S7 Communication partner (Honeywell DCS / Experion with CP 1613) reads or writes data blocks using the standard Siemens S7 protocol, mapped onto TCP/IP + ISO-on-TCP (port 102) at the transport layer.
For a CPU 315-2DP, the only S7 Communication function blocks that operate on the S7 connection are:
- SFB 12 BSEND / SFB 13 BRCV – segmented bidirectional transfer
- SFB 14 GET / SFB 15 PUT – read / write remote data (server function on the CPU)
- SFC 7 / SFC 8 – communication status and link-up
For an S7-300 station, the partner-initiated GET (read) does not require PUT/GET to be called in OB 1; the CPU operating system responds to a read request automatically if the configured S7 connection is established and the partner has the right authorization. This is the path used by a DCS that polls tags from the PLC.
2.2 Path B – SEND/RECEIVE (FC5 AG_SEND / FC6 AG_RECV)
The SEND/RECEIVE interface is a generic, byte-stream transport. It is configured as either a TCP, UDP, or ISO-on-TCP connection in the CP properties. The user program calls:
- FC5 AG_SEND – copy N bytes from an ANY-pointer to the CP's send buffer, transmit on a configured connection
- FC6 AG_RECV – block on receive and copy up to N bytes from the CP's receive buffer to an ANY-pointer
This is the path used when the partner is a non-Siemens application that only speaks raw TCP (or ISO-on-TCP / UDP). The function blocks are part of the "SIMATIC NET CP 343-1 Lean SEND/RECEIVE" library and must be instantiated per connection in OB 1.
3. Data-Length Limits – The Key Sizing Matrix
The maximum payload per request on Industrial Ethernet is fundamentally different between the two paths. Mis-sizing either path is the most common cause of incomplete or truncated data.
| Path / Mechanism | Maximum User Data per Call | Maximum User Data per TCP/IP Frame | Notes |
|---|---|---|---|
| FC5 AG_SEND over TCP (Path B) | 8192 bytes | Up to 1460 bytes per Ethernet frame (fragmented internally by the CP) | 8 KB limit is fixed in the CP 343-1 Lean; payload >8 KB requires multiple AG_SEND calls. Documented in section "SEND/RECEIVE Interface" of the CP 343-1 Lean manual. |
| FC5 AG_SEND over ISO-on-TCP | 8192 bytes | Up to 1460 bytes per frame (TSAP-based) | Same 8 KB limit as TCP; same AG_SEND/AG_RECV interface. |
| FC5 AG_SEND over UDP | 2048 bytes | Single datagram | No flow control; partner must be addressed by IP and UDP port. Use only on trusted networks. |
| S7 Communication PUT/GET (SFB 14/15) on Ethernet (S7-300 server, single request) | ~ 200 bytes per call | One S7 message | For an S7-300 acting as server, each PUT/GET request is limited to ~200 bytes because the CPU 31x firmware does not implement the segmented S7 function set. The Experion / DCS must break larger transfers into multiple requests or use BSEND/BRCV. |
| S7 Communication BSEND/BRCV (SFB 12/13) on Ethernet (S7-300, partner-initiated) | Up to 32768 bytes per call (16-bit length field) – but only 8192 bytes per CP buffer in CP 343-1 | Sequence of S7 messages | Segmented, ack-based, transparent up to the SFB length. BSEND is initiated by the PLC; partner side on a CP 1613 supports it. |
| Honeywell Experion S7-TCP channel with polling | ~ 200 bytes per poll by default; configurable up to the DCS driver maximum | One S7 message | Default S7-300 client block size for polling is 200 bytes; the DCS issues additional reads in the background to cover larger DBs. |
The two numbers engineers must commit to memory for this part number are:
- FC5 AG_SEND over TCP = 8 192 bytes per call (Path B, byte stream)
- S7 PUT/GET against CPU 315-2DP = ~ 200 bytes per request (Path A, polled by partner)
Anything larger than 200 bytes that must come from the DCS to the PLC and back has to be assembled at the application layer in the PLC data block. The DCS driver typically does this transparently, splitting the desired range into 200-byte chunks. The PLC programmer's responsibility is only to provide a contiguous DB with sufficient length, starting at byte 0 of the area being polled.
4. Why FC5/FC6 Are Not Required for the S7 Connection
The original question on the panel was: "If I remove the FC5 AG_SEND block, can I still communicate with the Honeywell DCS server over Industrial Ethernet?" The answer is yes – with a single, important condition.
The S7 connection is established and maintained by the operating system of the CPU 315-2DP and forwarded by the CP 343-1 Lean. No user program involvement is needed for the connection to come up, to keep it alive, or to respond to a partner-initiated read (SFB 14 GET on the DCS side). The FC5/FC6 blocks are part of the SEND/RECEIVE interface – they belong to Path B, not to Path A.
Conversely, if the partner is a generic TCP server (a Python script, a custom OPC bridge, a SCADA driver that expects raw bytes), the FC5/FC6 blocks are mandatory – there is no other way to push user data from OB 1 onto the Industrial Ethernet interface of the CP.
5. Diagnosing a "TCP + S7" Coexistence on the Same CP
The original configuration reported in this article – "TCP connection at CP 343-1 end, S7 connection at Honeywell DCS server end" – is not in itself contradictory. It simply means that two separate connections have been configured in the S7-300 station: one typed TCP and one typed S7. As long as the partner endpoints are distinct (different IP, different TSAP, or different application port), the CP 343-1 Lean will establish both. The risk is on the partner side: a DCS that only knows the Siemens S7 protocol will not be able to consume data placed on the TCP connection by AG_SEND. In that case, the TCP connection will show as established at the CP (LED / online diagnostics), but the user data will be silently dropped at the partner.
5.1 Decision matrix
| What does the DCS actually consume? | Which connection is required? | FC5/FC6 in OB 1? | Active user program needed? |
|---|---|---|---|
| Siemens S7 protocol (read/write DBs) | S7 connection only | No – blocks may remain, will not harm | No – CPU OS handles the partner-initiated GET |
| Raw TCP byte stream (custom driver) | TCP connection | Yes – both AG_SEND and AG_RECV must be called | Yes – OB 1 must drive the data exchange |
| Both simultaneously (rare) | S7 connection + TCP connection | Yes – for the TCP leg only | Yes – for the TCP leg only |
| ISO-on-TCP (e.g. RFC 1006 to a Siemens S7-400 HMI) | ISO-on-TCP connection | Yes – same FC5/FC6 interface | Yes – same as TCP |
6. Configuring the CP 343-1 Lean for an S7 Partner
Use STEP 7 V5.5 (with the CP 343-1 Lean HSP or the standard hardware catalog). The configuration steps assume an S7-300 station with the CP 343-1 Lean inserted in slot 4 (or any free slot).
6.1 Prerequisites
- STEP 7 V5.5 SP4 or later installed.
- CP 343-1 Lean (6GK7 343-1CX10-0XE0) in the hardware catalog, with at least firmware V2.x (the device accepts V1.x but V2.x is recommended for stability with modern Experion drivers).
- CPU 315-2DP with firmware V2.x or later (so that the BSEND/BRCV functions behave per the S7-300 reference manual).
- Honeywell DCS server with CP 1613 installed and the S7-TCP channel licensed; the station type in NCM PC is set to S7-300 with Ethernet CP 343-1.
- IP plan in place. The CP 343-1 Lean default address is 0.0.0.0; assign a fixed address (e.g. 192.168.10.20) before commissioning.
- Firewall / managed switch: port 102/TCP (ISO-on-TCP / S7) and – if the TCP leg is used – the port chosen for AG_SEND/AG_RECV (default 2000 for CP 343-1) must be open between the PLC and the DCS server.
6.2 STEP-by-STEP configuration in STEP 7
- Open the S7-300 station in STEP 7. In HW Config insert the CP 343-1 Lean (6GK7 343-1CX10-0XE0) at the appropriate slot. Double-click the CP to open its properties.
- In the Properties – Ethernet Interface dialog, set the IP address, subnet mask, and (if used) router. Confirm with OK.
- Open NetPro (or Configure Network). Right-click the CP 343-1 Lean and choose Insert New Connection.
- In the Insert New Connection dialog, choose the partner as Unspecified / S7 connection (the partner is configured in NCM PC; the PLC side is what you are configuring here). Set the connection type to S7 connection.
- Set the local TSAP (e.g.
S7-300-PLC.01.01– this is the slot and connection number on the CP) and the partner TSAP (e.g.CP1613.01.01– matching the configuration on the CP 1613 side). - Activate Establish an active connection on the PLC side if the DCS server cannot open the connection from its side; otherwise leave it passive (CP 1613 typically opens the connection actively when the channel is enabled in Experion).
- Save and compile. Download the HW Config and the NetPro data to the CPU (PG target system: CPU 315-2DP).
6.3 DB preparation on the PLC side
The DCS will read a data block; the DB must exist in the CPU with the right length and must not be optimized (i.e. it must be a standard DB with "non-optimized" access – this is the default for S7-300, so no action is needed unless DBs have been converted).
Example configuration block (read-only DB exposed to the DCS):
DATA_BLOCK "DB_HMI_Data"
TITLE = DCS Interface Data Block
{ S7_Optimized_Access := 'FALSE' }
AUTHOR : ENGINEER
FAMILY : DCSIF
VERSION : 0.1
STRUCT
ProcessValue_01 : REAL; // e.g. temperature
ProcessValue_02 : REAL; // e.g. pressure
ProcessValue_03 : REAL; // e.g. flow
StatusWord_01 : WORD; // bit-packed status
AlarmWord_01 : WORD; // bit-packed alarms
Heartbeat : INT; // incremented each scan
Spare : ARRAY[0..49] OF BYTE;
END_STRUCT;
END_DATA_BLOCK
The DCS driver is configured to read the first N bytes of DB 100 (or whatever DB number is assigned) starting at byte 0. With a CPU 315-2DP, the partner issues up to ~200 bytes per GET request; the DCS driver accumulates the chunks transparently.
6.4 Optional – sending data actively from the PLC to the DCS (BSEND)
If the application requires the PLC to push data without polling, the partner must support BSEND (CP 1613 does). Add the following call in OB 1:
CALL "BSEND" , "DB_BSEND_INST" // SFB 12 instance DB
REQ := TRUE // triggered on rising edge
R := FALSE
ID := W#16#0001 // S7 connection ID (from NetPro)
R_ID := DW#16#0000_0001 // any 32-bit identifier
DONE := M10.0
ERROR := M10.1
STATUS := MW12
SD := P#DB100.DBX0.0 BYTE 200 // ANY pointer to the data
LEN := 200
Note the LEN of 200 bytes. Exceeding the per-call maximum on an S7-300 server (the partner may still accept it from an S7-400, but for an S7-300 server the recommended LEN is ≤ 200 to avoid the SFB returning STATUS W#16#8088 / 80A1).
7. Verification – Is the S7 Connection Actually Up?
After download and CPU restart, validate the link in the following order. Each step produces an unambiguous pass/fail.
-
CP LED state. The
LINKLED on the CP 343-1 Lean must be solid green. TheRUNLED must be solid green.SFandBFmust be off. A litBFLED indicates a bus fault – typically an IP or TSAP mismatch on the partner side. - Online diagnostics in STEP 7. Right-click the CP in HW Config, choose PLC → Module Information (or use Diagnostics → Connections in NetPro). The S7 connection should be in state Established. The CP also shows byte counters per connection.
- DCS side – channel status. In the Experion server, the S7-TCP channel should show a green status and an increasing "successful reads" counter. A channel that stays in NOT CONN points to a TSAP, IP, or CP 1613 driver misconfiguration; a channel that goes to FAULT with "connection reset by peer" usually indicates a slot or rack mismatch on the PLC side.
-
Wireshark on the link. With a managed switch and port mirror, filter on
tcp.port == 102. You should see a TPKT/COTP connection setup (CR, CC) followed by S7 Read/Write requests. If only TPKT CR is visible without CC, the CP 1613 is not configured as a S7 server with the matching TSAP. -
Forced value test. In STEP 7, set Monitor/Modify on DB 100 byte 0..3 to a known pattern (e.g.
16#3F80 0000= 1.0 REAL) and verify the value appears on the DCS HMI within one poll cycle.
8. Common Errors and Recovery
| Symptom | Likely Root Cause | Diagnostic Step | Recovery |
|---|---|---|---|
CP BF LED on, no S7 connection in NetPro |
IP / TSAP / subnet mismatch | Compare PLC IP with partner IP; verify the partner TSAP matches CP 1613 NCM PC config | Correct TSAP or IP; re-download HW Config and NetPro |
| S7 connection comes up, but data is always 0 on the DCS | Wrong DB number or wrong start byte | Wireshark capture of S7 Read Request – check the DB area code and byte offset | Correct the DB number / start byte in the DCS channel configuration |
| AG_SEND returns STATUS 8183 / 80C3 | TCP connection not yet established, or partner port not listening | Check CP online connection list; verify port on partner with netstat -an
|
Correct the partner port; verify routing; restart the partner application |
| AG_SEND returns STATUS 80B0 / 80B1 | LEN field exceeds 8192 bytes for TCP, or 2048 for UDP, on CP 343-1 Lean | Inspect the LEN input of FC5 | Reduce LEN to 8192 for TCP / ISO-on-TCP, 2048 for UDP; segment in user program |
| Experion shows "0 records / 0 success" for an S7 block > 200 bytes | DCS driver not chunking – older S7-TCP channel versions require a manual block-size | Check channel configuration Max Read Length | Set Max Read Length = 200; driver will issue multiple GETs to cover the DB |
| PUT/GET from PLC side returns STATUS 80A1 / 80A7 | Partner does not allow PUT from the S7-300 server – CPU 315-2DP is a "passive" partner for SFB 14/15 unless configured active | NetPro: check the "Active connection establishment" flag for the S7 connection | Toggle active establishment to the PLC side; or rely on partner-initiated GET only |
| Connection drops every few minutes | Keep-alive mismatch, or firewall killing idle TCP 102 sessions | Check CP Connection diagnostics → Last error | Enable ISO-on-TCP keep-alive on the CP; ask network team to add a long-idle-session exception for port 102 |
9. Sizing Example – 1 000 Bytes of Process Data from PLC to DCS
Consider a process that exposes 1 000 bytes of structured data to the DCS. The choice of path determines the protocol mechanics:
9.1 If using S7 (Path A – the standard DCS case)
- DB 100 in the PLC, length ≥ 1 000 bytes, optimized access = false.
- DCS channel: read DB 100 from byte 0, length 1 000.
- Driver issues five GET requests of 200 bytes each (background, transparent to the user).
- Update rate on the DCS is set by the channel poll time; typical values 200 ms to 1 s.
9.2 If using SEND/RECEIVE over TCP (Path B)
- Configure a TCP connection to the DCS, port (e.g.) 2 000.
- Call FC5 AG_SEND with LEN = 1 000 – well within the 8 192-byte limit, no segmentation needed.
- DCS partner must speak raw TCP; this is not what the Honeywell S7-TCP channel does – the S7-TCP channel uses the S7 protocol (Path A), not a raw byte stream.
Conclusion for the typical Honeywell DCS integration: keep the data on the S7 connection (Path A), let the DCS chunk the 1 000 bytes into 200-byte GETs, and do not configure a TCP connection in the CP at all. This is the simplest, most supportable, and most diagnostic-friendly topology.
10. When Path B (TCP / SEND-RECEIVE) Is the Right Choice
There are legitimate cases for adding AG_SEND/AG_RECV on a CP 343-1 already carrying an S7 connection to a DCS:
- Event-driven push from PLC to a third-party system (a Python gateway, a custom reporting server) that polls would not be appropriate for. AG_SEND is the right tool here.
- High-throughput data dump to an OPC-DA or OPC-UA bridge that does not implement the S7 protocol.
- Replacement of legacy serial DF1 / Modbus to a free-form ASCII listener. Use ISO-on-TCP for a TSAP-based fixed partner, or TCP for an IP-port-based fixed partner.
In all three cases, the SEND/RECEIVE connection must be configured as a separate entry in NetPro; it must not be merged with the S7 connection. The CP 343-1 Lean supports multiple parallel connections, but the limit must be checked against the device's connection count (the Lean supports 4 S7 connections / 8 SEND-RECEIVE connections, depending on firmware; see the device manual for the exact number on the installed firmware).
11. Engineering Notes and Best Practices
- Do not enable the S7 connection and a TCP connection to the same partner with the same TSAP. The CP will not refuse the configuration, but the partner will only be able to use one of them. The unused one will hold a TCP socket open and consume a CP connection resource for no benefit.
- Keep AG_SEND/AG_RECV LEN at or below the documented limit (8 192 TCP, 2 048 UDP). A LEN that exceeds the buffer produces STATUS 80B1 and no transmission – the error is at the FC5 call, not at the network level.
- Match the SFB 12/13 LEN to the partner's expected per-call size (200 bytes for an S7-300 server). The CP 343-1 firmware is permissive, but the partner's buffer is the binding constraint.
- Use standard (non-optimized) DBs for any data that the DCS or third-party tool reads. Optimized DBs hide their real layout and break fixed-offset access that the S7 protocol relies on.
-
Tag the connection with a meaningful local ID in NetPro – the W#16#ID in BSEND/GET/PUT and the AG_SEND/AG_RECV parameter
IDboth point to the connection ID. Commenting the ID in the project (e.g. "ID 1 = DCS polling") saves a lot of time during commissioning. - Update the CP firmware before field deployment. The 6GK7 343-1CX10-0XE0 was revised several times; firmware V2.0 or later closes several TCP-edge bugs that otherwise surface as random disconnects under load.
- For redundant DCS paths, plan a second CP 343-1 (full version, not Lean) with separate IP and separate S7 connection. The Lean variant does not support parallel redundancy protocols.
12. Field Commissioning Checklist
- Verify the CP 343-1 Lean and CP 1613 are on the same subnet and can ping each other.
- Verify the S7 connection in NetPro is compiled without warnings, downloaded to the CPU, and the CPU is in RUN.
- Open Module Information on the CP and confirm the S7 connection state is Established.
- Open the DCS server console, enable the S7-TCP channel, and watch the channel transition from NOT CONN to OK.
- Force a known value in the interface DB, confirm it appears on the DCS HMI within one poll cycle, and release the force.
- Add the SFB 12/13/14/15 status words to the VAT if BSEND/PUT/GET are used, and confirm DONE pulses with each successful call and STATUS stays at 0.
- Capture a 30-second Wireshark trace on the port mirror and save it with the commissioning report.
- Document the connection ID, TSAP, IP, and DB layout in the project's network register.
13. Frequently Asked Questions
How many bytes can FC5 AG_SEND transmit per call on the CP 343-1 Lean over TCP?
FC5 AG_SEND on the CP 343-1 Lean (6GK7 343-1CX10-0XE0) supports a maximum of 8 192 bytes per call over TCP and ISO-on-TCP. Over UDP the limit is 2 048 bytes per call. LEN values above the limit return STATUS W#16#80B1 at the AG_SEND output and no data is transmitted.
What is the maximum user data per S7 PUT/GET request on a CPU 315-2DP?
For an S7-300 acting as the S7 server (CPU 315-2DP with CP 343-1), the practical limit per SFB 14 GET or SFB 15 PUT call is approximately 200 bytes. This is a firmware limitation of the S7-300 series, not of the CP. Honeywell Experion's S7-TCP channel driver transparently breaks larger DB reads into 200-byte GET requests.
Is the FC5 AG_SEND block required to talk to a Honeywell DCS over S7 Communication?
No. The S7 connection is managed by the operating system of the CPU 315-2DP and forwarded by the CP 343-1 Lean. The DCS reads data blocks using partner-initiated GET requests that the CPU answers automatically. The FC5/FC6 blocks belong to the SEND/RECEIVE (TCP/UDP) interface and are only needed if a raw TCP byte stream is also configured. They can be left in OB 1 if a separate TCP leg exists; they do not affect the S7 leg.
Can a single CP 343-1 Lean carry an S7 connection and a TCP connection at the same time?
Yes. The CP 343-1 Lean supports multiple parallel connections – one S7 connection plus up to 8 SEND/RECEIVE connections, depending on the firmware version. The two paths are independent: the S7 leg is OS-managed, the TCP leg requires FC5/FC6 in OB 1. Mixing them on a single CP is the standard topology for PLC-to-DCS integrations where the DCS is the S7 client.
What TSAP should be configured for the CP 1613 on the Honeywell DCS side?
On the SIMATIC PC station (CP 1613) in NCM PC, configure a S7 connection with a TSAP of the form CP1613.01.01 (rack 0, slot 0) or a similar hex form. On the CP 343-1 Lean side the local TSAP must match the partner TSAP that the CP 1613 expects. A typical configuration is local TSAP 01.01 and partner TSAP CP1613.01.01. Any TSAP mismatch surfaces as a BF LED on the CP and a NOT CONN state on the Experion channel.