CPU314C-2PN PROFINET to SINAMICS G120 CU250S-2: PIO & Telegram

David Krause21 min read
S7-300SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

A very common commissioning scenario on a Siemens PROFINET network is a SIMATIC S7-300 CPU 314C-2PN/DP that downloads and runs its program correctly, has a valid link to a SINAMICS G120 CU250S-2 PN, reports no PROFINET diagnostic or station failure on either device, but still cannot exchange useful cyclic process data with the drive. The control word sent by the PLC never appears in the drive's r2050 / r2090, and the status word read back by the PLC never updates. This article documents the three root causes that account for roughly 95 % of these no-data-but-no-fault cases on S7-300 / G120 PROFINET links:

  • The I/O address the user is moving to lies outside the configured process image of the CPU 314C-2PN/DP, so the cyclic frame never updates the symbolic operand the program is reading.
  • The I/O direction is reversed in the user's mind (a QW on the PLC is an IW on the drive, and vice versa), so the program is writing the control word into the status-word slot or reading the control word slot as input.
  • The telegram selected in the G120 and the device configuration in TIA Portal do not match the actual I/O length the program is moving, so the slots are offset by one or more words.

Each is addressed with concrete parameter numbers, register addresses, and a verification procedure that any field engineer can apply without an oscilloscope or PROFINET analyzer.

Hardware Topology

The reference installation is a line topology with no external switch. The integrated 2-port switch of the CPU 314C-2PN/DP is used as the PROFINET backbone.

S7-300 CPU314C-2PN/DP192.168.0.100Port1 / Port2PC / HMI192.168.0.10G120 CU250S-2 PN192.168.0.2P922 = 1 (Telegram 1)Port1 / Port2 (P2 unused)Port 1 (link green)Port 2 → Port 1 (data yellow)

Network addresses used throughout this reference:

Device IP address PROFINET role Port usage
CPU 314C-2PN/DP 192.168.0.100 IO Controller Port 1 → PC/HMI; Port 2 → G120
PC / TIA Portal / HMI 192.168.0.10 Supervisor Connected to CPU Port 1
G120 CU250S-2 PN 192.168.0.2 IO Device Port 1 to CPU; Port 2 left un-terminated/unused
When port 2 of the G120 is left unused it must be left open (no RJ45 plug, no termination). Closing an unused PROFINET port with a 100 Ω terminator rather than a working link partner can suppress the link on that port but does not affect Port 1. The yellow activity LED still indicates the cyclic frame is being received on Port 1.

Root Cause 1: Process Image versus Peripheral I/O

On an S7-300, the integrated PROFINET interface (X1 / X2) maps the cyclic I/O of every configured IO Device into the CPU's process image if the I/O address falls inside the configured process image range, or into the peripheral I/O area if it falls outside that range. The CPU 314C-2PN/DP ships with a default process image of 256 bytes for inputs and 256 bytes for outputs, which means only addresses IB 0 ... IB 255 and QB 0 ... QB 255 (or word-level IW 0 ... IW 254 and QW 0 ... QW 254) are accessible by the bit/byte/word process image instructions. A value moved into a symbolic operand backed by, for example, QW 256 will not actually reach the PROFINET frame because QW 256 is outside the process image.

On S7-1200 and S7-1500 this distinction does not exist in user code: every I/O is automatically in the process image and the peripheral prefix P is not normally required. Engineers who move from TIA Portal with an S7-1200 to an S7-300 keep writing IW 256 / QW 256 and get silent failures. There are two correct fixes:

  1. Use the peripheral prefix: address the slot as PIW 256 (read directly from the peripheral input area) and PQW 256 (write directly to the peripheral output area). This works for any address in the peripheral I/O area and does not require any change in the CPU configuration.
  2. Extend the process image: in TIA Portal open the CPU properties, select Process image, and increase the process image size for inputs and outputs to at least the highest I/O address used by the drive (for example, 512 bytes if the last slot ends at 300). After this, IW 256 and QW 256 resolve as normal process-image accesses and can be used freely in OB1.
On the CPU 314C-2PN/DP the process image is split into two halves. The integrated PROFINET interface occupies the upper half by default. If you raise the process image size from 256 to 512 bytes, the second half of the integrated PN interface will still occupy the original range; you are simply leaving room for the slots that the IO Devices occupy. Always check the address overview that TIA Portal generates under Devices & Networks → PROFINET IO → IO Devices → Address overview to know which byte range the drive actually uses.

Root Cause 2: Direction Mapping (PLC Output equals Drive Input)

The second source of confusion is the direction of the data word. In TIA Portal, the user looks at the device view of the G120, sees two slots (one input slot, one output slot) and assigns addresses in the CPU address space. The mapping rules are:

  • What the CPU writes (its outputs, QW / PQW) is what the drive receives as an input (its IW, parameter r2050[0]). The control word and speed setpoint go from the PLC to the drive, so they live at QW / PQW addresses in the CPU program.
  • What the CPU reads (its inputs, IW / PIW) is what the drive transmits as an output (its QW, parameter r2051[0]). The status word and actual speed come from the drive to the PLC, so they live at IW / PIW addresses in the CPU program.

It is impossible to write to a PLC IW from the user program. The MOVE instruction that loads the control word into an IW address either does nothing, raises a peripheral-access error, or compiles to a no-op depending on the firmware version. The user must always write the control word to a QW / PQW address and read the status word from an IW / PIW address. This is the same rule on every Siemens PLC, including S7-1200 and S7-1500; what changes is only the addressing notation.

Process Image Configuration on CPU 314C-2PN/DP

The default process image of the CPU 314C-2PN/DP is 256 bytes for inputs and 256 bytes for outputs. Telegram 1 of the SINAMICS G120 occupies 2 PZD words in each direction (4 bytes input + 4 bytes output), which means the drive's I/O always sits inside the default 256-byte process image. If TIA Portal has shifted the drive's address range to byte 256 or higher (for example, when additional IO Devices occupy the lower range), the drive falls outside the process image and the P-prefix becomes mandatory.

  1. In the TIA Portal project tree, select the CPU 314C-2PN/DP.
  2. Open Properties → General → Process image.
  3. Confirm the size of the process image. Increase it if the drive's start address is at or above the current boundary.
  4. Verify the size of the process image of the integrated PROFINET interface (under PROFINET interface → Properties → Process image). Both halves are sized independently.
  5. After changing the size, recompile and download the hardware configuration. The CPU goes into STOP during the download of the hardware.

Address conflicts are reported by TIA Portal as a red border in the device view. A red border on the G120 device icon in Devices & Networks indicates that the chosen start address is either already in use by another slot or falls outside the maximum I/O range of the CPU. The CPU 314C-2PN/DP supports up to 8192 bytes of input and 8192 bytes of output peripheral I/O; the process image is a subset of that range.

Telegram 1 Configuration on the SINAMICS G120

Standard Telegram 1 (sometimes called "PZD 2/2" or "Speed control, 2 words") is the simplest useful telegram for a SINAMICS G120 PROFINET drive. It carries two PZD words in each direction. The assignment is fixed by the PROFIdrive profile and is the same on every SINAMICS G / S / V series drive that supports PROFINET.

Direction PZD word Name PROFIdrive signal Drive parameter (received / sent word) Drive parameter (BICO interconnect)
PLC → Drive PZD1 STW1 Control word 1 r2050[0] (received word) P2050[0] = r2090.0 (default)
PLC → Drive PZD2 NSOLL Speed setpoint (16-bit, normalization 0x4000 = 100 %) r2050[1] P2050[1] = speed setpoint channel
Drive → PLC PZD1 ZSW1 Status word 1 r2051[0] (sent word) P2051[0] = r2089[0] (default)
Drive → PLC PZD2 NIST Actual speed value (16-bit, normalization 0x4000 = 100 %) r2051[1] P2051[1] = r0063 (default)

To select this telegram on the G120 with a CU250S-2 PN:

  1. Open the STARTER / Startdrive / IOP project for the drive.
  2. Navigate to Communication → PROFINET → Telegram configuration.
  3. Set P922 = 1 (Standard Telegram 1, PZD 2/2).
  4. Do not change the BICO defaults of P2050[0], P2050[1], P2051[0], P2051[1] unless a non-default routing is required. The defaults route STW1 to the control-word BICO sink and ZSW1 from the standard status-word BICO source.
  5. Copy RAM to ROM and, if a BOP/IOP is fitted, perform a power cycle to activate the change.
About parameter r2090: r2090 is the bit-serial interconnection display of the received PZD1. It is not the raw word value. The raw word value of received PZD1 is r2050[0]. When the PLC writes 0x047E to the control-word slot, r2050[0] reads 0x047E and the BICO sink connected through r2090.0-15 receives the corresponding bit pattern. Reading r2090 only ever returns 0 or 1 at each bit, so monitoring r2090 in the parameter view will not show a clean 16-bit hex value. Monitor r2050[0] for the actual control word received from the controller.

Address Map Reference

The table below is the most useful single page to print and bring to the panel. It ties the symbolic operand visible in TIA Portal, the absolute address used in the user program, the direction, and the drive parameter together. The example assumes the G120 occupies input address 256 ... 259 and output address 256 ... 259, which is the typical assignment when the lower 256 bytes are reserved for central I/O and the second PROFINET slot starts the drive at byte 256.

Slot TIA Portal name PLC absolute address (process image) PLC absolute address (peripheral) Direction Drive parameter Meaning
PZD1 receive (STW1) G120_ControlWord QW 256 PQW 256 PLC → Drive r2050[0] (BICO via r2090) Control word 1 (16-bit)
PZD2 receive (NSOLL) G120_SpeedSetpoint QW 258 PQW 258 PLC → Drive r2050[1] Speed setpoint (0x4000 = 100 % of p2000)
PZD1 send (ZSW1) G120_StatusWord IW 256 PIW 256 Drive → PLC r2051[0] Status word 1 (16-bit)
PZD2 send (NIST) G120_ActualSpeed IW 258 PIW 258 Drive → PLC r2051[1] Actual speed (0x4000 = 100 % of p2000)

Sample OB1 code (SCL or LAD) for the CPU 314C-2PN/DP using direct peripheral access so that no process-image extension is required:

// OB1 - cyclic PROFINET exchange with G120 CU250S-2 PN
// Telegram 1, PZD 2/2, drive start address 256

// --- Send: PLC output area (PLC -> drive) ---
// Control word 1 = 16#047E (OFF1, no OFF2/OFF3, enable, control from PLC)
// To run the drive, set bit 0 (ON) -> 16#047F
#CtrlWord := 16#047F;            // 0x047F = ready to operate, setpoint enabled
#SpeedSet  := 16#1000;            // 0x1000 = 25 % of p2000 (100 % = 0x4000)

// Write to the drive via peripheral output area
MOVE_BLK(VARIANT:=#CtrlWord,  COUNT:=1,  OUT  => PQW256);
MOVE_BLK(VARIANT:=#SpeedSet,  COUNT:=1,  OUT  => PQW258);

// --- Receive: PLC input area (drive -> PLC) ---
// Read status word and actual speed from peripheral input area
MOVE_BLK(IN :=PIW256,  COUNT:=1, OUT => #StatusWord);
MOVE_BLK(IN :=PIW258,  COUNT:=1, OUT => #ActualSpeed);

For the equivalent LAD/ST approach inside STEP 7 V5.x or TIA Portal using the symbolic names assigned in the device view:

// LAD: place a MOVE box with IN = 16#047F and OUT = "G120_ControlWord"
//      place a MOVE box with IN = PIW256 and OUT to a data word (e.g. DB42.DBW0)
// ST:  "G120_StatusWord" := PIW256;
//      PQW256 := 16#047F;

TIA Portal Device and Telegram Setup Procedure

The procedure below assumes the SINAMICS G120 GSDML-G120-X.xml has been installed under Options → Manage general station description files (GSD) and that the device name has been assigned to the drive using the topology editor or the online "Assign PROFINET device name" function.

  1. Open the project in TIA Portal and select the CPU 314C-2PN/DP from the project tree.
  2. Open Devices & Networks and drag the G120 CU250S-2 PN from the hardware catalog into the PROFINET subnet. Assign IP 192.168.0.2 and the previously assigned PROFINET device name.
  3. Connect Port 1 of the CPU to Port 1 of the G120 in the topology view. Confirm Port 2 of the G120 is left disconnected.
  4. Open the device view of the G120. Right-click on the PROFINET interface slot and confirm that the device is configured as an IO Device, not an IO Controller. The Operating mode field of the PROFINET interface must show IO Device.
  5. In the device view, the Device overview shows the slot list. Slot 0 is the drive itself. Sub-slot 1 (telegram) contains the PZD configuration. Confirm the slot shows Standard Telegram 1 (PZD 2/2). If the slot is empty, add the standard telegram 1 by drag-and-drop from the catalog under PROFINET IO → Telegrams → Standard Telegram 1.
  6. Open the slot properties and verify the input and output start addresses. The default depends on the slot order; for a clean project the drive occupies the first free area after the central I/O. With central I/O consuming bytes 0-15, the drive typically starts at byte 256 (QW 256 / IW 256). If the address is at byte 256 or higher, the process image must be enlarged or the P-prefix must be used.
  7. Compile the project and download the hardware configuration to the CPU. The CPU performs an overall reset and goes through STOP → RUN during the download.
  8. In the online view of the G120, monitor r2050[0], r2050[1], r2051[0], r2051[1] and r2090. With the example MOVE in OB1 active, r2050[0] must show 0x047F and r2051[0] must show 0x0C37 or similar (a healthy status word from the drive).
If the project was created from scratch in TIA Portal with the SINAMICS G120 HSP (Hardware Support Package) rather than the GSD, the catalog entry of the drive is SINAMICS G120 CU250S-2 PN F-Vector or ... PN Vector. The slot list is identical. The HSP installs the GSD into the project automatically and also exposes the SINAMICS drive parameters directly inside TIA Portal, which makes step 7 and 8 much easier because the user can navigate to the same parameter tree that STARTER / Startdrive would show.

LED Diagnostics Interpretation

The PROFINET link is healthy when the port LEDs on the CPU and the G120 match the table below. Diagnose from the physical layer upwards: link first, then activity, then cyclic-data state on the drive.

Device LED Color State Meaning
CPU 314C-2PN/DP Port 1 / Port 2 link Green On Physical link established, 100 Mbit/s full duplex.
CPU 314C-2PN/DP Port 1 / Port 2 activity Yellow Flashing PROFINET frames are being received or transmitted on the port.
CPU 314C-2PN/DP BF (bus fault) Red Off No bus fault; configuration matches the connected IO Devices.
CPU 314C-2PN/DP SF / MAINT Red / Yellow Off No group fault and no maintenance demanded.
G120 CU250S-2 PN BF (bus fault) Red Off PROFINET communication is OK.
G120 CU250S-2 PN LNK (Port 1 / Port 2) Green On Physical link on the corresponding port.
G120 CU250S-2 PN RX/TX (Port 1 / Port 2) Yellow Flashing PROFINET frames are being received on the port.

The scenario "port 1 of the 314C green, port 2 of the 314C yellow" simply means "the PC link is up and the drive port is exchanging data". It is not an error condition. The bus is healthy. The drive is happily receiving and sending PROFINET frames. The reason the user cannot see the control word is purely an address-direction or process-image issue in the user program, not a PROFINET fault.

Control Word and Status Word Reference (PROFIdrive Profile)

The control and status words of Telegram 1 follow the PROFIdrive application class 1 profile. Only the bit combinations that matter during commissioning are listed below; the full bit map is in the SINAMICS G120 List Manual (LH1) – Communication section.

Word Bit Name 1 = ... 0 = ...
STW1 (control) 0 ON / OFF1 ON (drive energises and ramps to setpoint) OFF1 (ramp down to 0, then pulse inhibit)
STW1 (control) 1 OFF2 No OFF2 (drive may run) OFF2 (immediate pulse inhibit, free run to stop)
STW1 (control) 2 OFF3 No OFF3 OFF3 (fast stop, ramp p1135)
STW1 (control) 3 Enable operation Enable inverter operation Inhibit operation (pulse inhibit)
STW1 (control) 4 Enable ramp generator Enable ramp generator (RFG) Freeze RFG output (setpoint frozen)
STW1 (control) 5 Unfreeze ramp generator Unfreeze RFG Freeze RFG
STW1 (control) 6 Enable setpoint Enable setpoint at RFG input Inhibit setpoint (RFG input = 0)
STW1 (control) 7 Fault acknowledge Acknowledges a pending fault (rising edge) No effect
STW1 (control) 10 Control by PLC PLC controls the drive (PROFINET is the active command source) Drive ignores the PROFINET control word
ZSW1 (status) 0 Ready to switch on Power supply OK, no OFF2, no OFF3 active Not ready
ZSW1 (status) 1 Ready to operate STW1 bit 0 may be set; drive ready to run Not ready
ZSW1 (status) 2 Operation enabled Drive follows the setpoint Drive not running (pulses enabled or inhibited)
ZSW1 (status) 3 Fault present At least one unacknowledged fault is active No fault
ZSW1 (status) 6 Switching on inhibited Drive cannot be switched on until STW1 bit 0 toggles 0→1 again Switch-on allowed
ZSW1 (status) 10 Control requested Drive requests control from the PLC (automatic for PROFINET) Drive is in local / panel control

Useful hex values during commissioning:

  • 0x047E = STW1 ready (no OFF2, no OFF3, enable operation, enable RFG, unfreeze RFG, enable setpoint, control by PLC). Bit 0 is OFF, so the drive sits in the "Ready to switch on" state. This is the safe state to apply during commissioning.
  • 0x047F = same as 0x047E with bit 0 = 1 (ON). The drive leaves the "Switching on inhibited" state and enters "Operation enabled". From this point, the speed setpoint takes effect.
  • 0x04FE = OFF2 active (bit 1 = 0). Use this for an emergency stop from the PLC.
  • 0x04FA = OFF3 active (bit 2 = 0). Use this for a controlled fast stop.

Verification Procedure

After the hardware and program changes are downloaded, run the following verification sequence on the panel. Each step has a binary "pass / fail" outcome that does not require the motor to be turning.

  1. Link LEDs: CPU Port 1 = green, CPU Port 2 = green or yellow, G120 Port 1 = green. If any link LED is off, the issue is cable / port / partner-device, not program addressing.
  2. Bus-fault LEDs: BF LED on the CPU and on the G120 are both off. If BF is red on the G120, the device name or IP does not match the controller's configuration.
  3. PROFINET state on the drive: connect STARTER or Startdrive to the G120, go online, and confirm the drive is reachable under IP 192.168.0.2.
  4. Cyclic I/O on the drive: monitor r2050[0] (received control word) and r2051[0] (sent status word) in the parameter view. With the example OB1 active, r2050[0] must follow the value the PLC is writing to PQW 256. If r2050[0] stays at 0x0000, the slot is not being written; the I/O address or the process image is wrong.
  5. Cyclic I/O on the PLC: in TIA Portal open Online & diagnostics → Monitor / modify on the G120 device. Confirm the input slot shows the drive's status word (typically 0x0C37 at standstill with command "ready to operate") and the output slot shows the controller's control word (0x047F when the example code is active). This view decouples the user program from the diagnostic and is the fastest way to confirm the slot is alive.
  6. Direction test: force the control word to 0x04FE from the watch table and confirm the drive enters OFF2 and ramps out (or free-runs to stop). If OFF2 is not honoured, the IO Device is in local control (command source = manual / IOP) and not PROFINET control; set p700 / p1500[0] back to the BICO defaults so that the PROFINET control word reaches the control-word BICO sink.

Common Pitfalls and Troubleshooting Matrix

Symptom Most likely cause Confirm by Fix
Yellow link LED on the G120 but r2050[0] stays 0x0000 PLC program writes to a wrong slot / wrong direction Watch PQW 256 and PQW 258 online; verify the value moves into PQW and the G120 input slot shows the same value in Monitor/Modify Use PQW instead of QW and write to the correct slot (256-259 for Telegram 1)
Yellow link LED, no bus fault, r2051[0] never updates in the PLC Process image too small or wrong direction Watch PIW 256 online; if it is always 0, the address is outside the process image Use PIW / PQW prefixes or increase process image size in CPU properties
Yellow link LED, r2050[0] is the correct value, but the drive ignores it Command source is not PROFINET Check p700 (command source selection) and p1500[0] (setpoint source) in STARTER/Startdrive Set p700 = 6 (PROFINET control word) and p1500[0] = 6 (PROFINET speed setpoint); do a power cycle
BF red on the G120 Device name or IP mismatch Compare the PROFINET device name assigned in TIA Portal with the name programmed into the drive (p8940/p8941) using the web server or STARTER Re-assign the PROFINET device name using Online → Assign PROFINET device name in TIA Portal
BF red on the CPU Configuration mismatch (telegram length, slot type, family) Compare the telegram type in the device view with P922 on the drive Set P922 to the same standard telegram selected in TIA Portal (typically 1, 2, 3, 4, 20, 350, 352, 353, 354)
SF on the CPU, "Peripheral access error" in the diagnostic buffer Read or write to an address that does not exist (e.g. IW 300 on a CPU whose PN interface only maps 280 bytes) Open the diagnostic buffer, read the I/O address that triggered the access error Use the correct I/O address; re-check the address overview under Devices & Networks → Address overview
r2090 shows 0x0000, r2050[0] is correct, drive still does not react BICO has been rewired away from the standard PROFIdrive routing Read p2050[0] and p2051[0] in STARTER/Startdrive Restore p2050[0] and p2051[0] to the default values from the List Manual
Firmware caveat: the CPU 314C-2PN/DP must run firmware V3.3 or later to support all of the S7-300 PROFINET features described above. Firmware V2.x of the same CPU has a smaller process image and a different set of supported telegrams. Always cross-check the CPU order number (6ES7 314-6EH04-0AB0) and the firmware version under Online → Accessible nodes before assuming the default 256-byte process image.
Star-delta, parallel, or other non-standard drive configurations: when the G120 is part of a multi-motor drive group, only the active drive receives the control word from the PROFINET slot. Make sure that the active drive is the one whose telegram is mapped into the slot range used by the user program, and that the inactive drives are parked or in slave mode via p815.

Why is the S7-300 process image only 256 bytes by default, while S7-1200 is unlimited?

On the S7-300, the process image size is configured per CPU and is limited because the process image is refreshed cyclically by OB1 (or OB35 for the partial process image). The CPU 314C-2PN/DP defaults to 256 bytes input and 256 bytes output to keep this refresh cycle within the cycle time. On S7-1200/S7-1500, every I/O is automatically in the process image and is updated as a copy-on-write, which is why the P-prefix is rarely used there.

What is the difference between QW 256 and PQW 256 on the CPU 314C-2PN/DP?

QW 256 reads or writes a copy of the I/O located in the process image. If byte 256 is outside the configured process image, the access triggers a peripheral access error or returns 0 silently. PQW 256 reads or writes the physical I/O directly, bypassing the process image. PQW is the correct choice for any drive slot whose start address lies outside the process image and is the safest choice even when the slot is inside, because the change is written to the slot in the same OB1 cycle.

Why does r2090 stay at 0x0000 even though the PLC is sending a control word?

r2090 is a BICO bit source that mirrors the bit pattern of r2050[0]. When the PROFINET frame is received correctly, r2050[0] shows the raw 16-bit value. r2090 displays the BICO bit-serial state. If r2050[0] is also 0x0000, the slot is not being written: the PLC is using the wrong address or wrong direction, or the PROFINET frame is not reaching the drive. If r2050[0] is the correct value but r2090 is 0, the BICO source has been re-routed by a previous commissioning session; restore p2050[0] to its default (r2090.0 for PZD1).

What telegram should I select for a simple speed-controlled G120 on PROFINET?

Telegram 1 (PZD 2/2) is the standard PROFIdrive speed-control telegram and is the right choice for 95 % of G120 applications. Use Telegram 2 if you need the speed setpoint as 32-bit, Telegram 3 if you need one 16-bit and one 32-bit setpoint, or Telegram 20 if you need a separate encoder channel. Avoid free telegrams (Telegram 999) for the first commissioning; get the standard telegram working first and then rewire the BICO if a non-standard word assignment is needed.

How do I confirm the drive is in PROFINET control, not local panel control?

In STARTER or Startdrive, online with the drive, check parameter p700 (command source selection). p700 = 6 means "PROFINET control word". p700 = 1 means "BOP/IOP panel". If p700 is not 6, the drive is ignoring the PROFINET control word. Also check r0050 (active command source bit field): bit 0 = 1 means PROFINET is the active command source. Setting p700 to 6 and powering the drive off and on is the standard way to hand control back to the controller.

Back to blog