D7-SYS CFC Memory Card Load: Fix Missing KAM001.msk Library

David Krause19 min read
HMI ProgrammingSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

D7-SYS CFC Memory Card Load Failure: Resolving Missing KAM001.msk Library Errors

When a D7-SYS project is downloaded to a SIMATIC S7 memory card (MMC or CF), the offline backup pipeline can abort with a missing-library fault that prevents the S7 program tree from being written to the card. The most common symptom is a dialog stating "Compile first" followed by a compiler log line such as Library KAM001 cannot be resolved or KAM001.msk not found. The root cause is almost always a version mismatch between the .a / .msk library pair shipped in the project ZIP and the installed D7-SYS service pack, and the remedy is to place the correct library pair in the appropriate sdblocks directory and re-run the compile.

This reference consolidates the field-proven diagnostic flow used by drive commissioning engineers to recover from a missing-library compile abort on a SIMATIC MMC/CF card, with explicit path tables, a .KMZ install procedure, version compatibility notes, and a verification matrix. The procedures apply to SIMATIC S7-300, S7-400, ET 200S, and SINAMICS / MASTERDRIVES applications programmed with SIMATIC S7-CFC under D7-SYS V6.x through V8.2.

Engineer field note: Always archive the project ZIP together with the \Global\sdblocks folder. The folder is mandatory for a successful offline backup load on a workstation other than the one that originally compiled the chart. A ZIP that contains only the chart sources and the S7 program files will not load into a memory card when the custom KAM library is missing.

1. Problem Overview

D7-SYS uses SIMATIC S7-CFC as the underlying engineering environment, with two layered compilation passes:

  1. CFC/SFC chart compiler — resolves all block instances in the chart and produces the chart sources (.src) and the call structure.
  2. S7 library loader — binds the chart to one or more master driver libraries (e.g. FBSGMC.A / FBSGMC.MSK) and any project-specific custom libraries (e.g. KAM001.A / KAM001.MSK) and generates the S7 program tree.

If the second pass cannot bind to a library, the compiler reports the missing file and refuses to write a valid S7 program to the target memory card. The Download to Memory Card button is disabled until the compile produces a valid S7 program tree. The fault is non-recoverable through the chart editor alone; the engineer must intervene on the disk.

The situation commonly arises in the following scenarios:

  • A machine builder ships a project ZIP exported from D7-SYS V6.x and the receiving maintenance engineer installs D7-SYS V8.x on the maintenance laptop.
  • The supplier delivers a .KMZ (CFC library archive) whose internal .msk was compiled against a different D7-SYS service pack than the one used to export the chart.
  • The original project folder was archived without the \Global\sdblocks subfolder, leaving only the chart sources and the S7 program files on disk.
  • The S7-CFC installation was upgraded in place, leaving stale .msk files in the global installation sdblocks directory.

2. Root Cause: Library Version Mismatch

A D7-SYS drive library is a paired file set:

Extension Role Required counterpart
.a Compiled S7 library archive containing the FB/FC/DB source code (STEP 7 archive format) .msk of the same block family
.msk Master/derivation mask describing the drive family, slot mapping, parameter list, and version stamp .a of the same block family

The two files must originate from the same D7-SYS build (major.minor.servicepack, optionally with hotfix). If .a is V6.0 SP4 and .msk is V8.1, the S7-CFC loader detects a header-version mismatch in the mask and aborts the compile with "Library cannot be resolved". The same abort is produced if the .a exists but the .msk is missing entirely.

For project-specific libraries (the KAM family — Kundenanpassungsmodul / customer adaptation module — e.g. KAM001), the version stamp is even more sensitive because the mask encodes the KAM slot, the parameter list, the protocol binding, and the CRC of the parameter set. A KAM001.MSK from one drive firmware revision will not bind to a project whose drive parameters were exported from a different firmware. This is the exact failure mode observed when a supplier ships a .KMZ of the wrong version: the .a may load but the .msk is rejected, and the compiler produces a generic missing-library error rather than a precise version-mismatch warning.

3. Library File Structure and Naming

Standard D7-SYS drive libraries follow the pattern FB<family>.a / FB<family>.msk. Common family codes used in production environments:

Family code Drive family Typical application
FBSGMC SIMOVERT MASTERDRIVES Motion Control Servo positioning, electronic camming
FBSGMI SIMOVERT MASTERDRIVES Inverter Vector control, V/f
FBSGSI SINAMICS S120 Servo and vector drives on PROFINET/Profibus
FBSGLI SIMOVERT MASTERDRIVES VC Standalone cabinet drives
FBSLIC SIMATIC LTi LIC Linear induction conveyor
FBSGSG SINAMICS G120 / G130 General-purpose drives

Custom libraries follow the convention chosen by the supplier. A KAM (Kundenanpassungsmodul) is typically named KAM<index>.a and KAM<index>.msk where <index> is a three-digit decimal. The user-visible example KAM001 indicates a single customer adaptation module integrated by the machine builder. Other custom prefixes in active use include:

Prefix Meaning
KAM Kundenanpassungsmodul (customer adaptation module)
CAM Customer application module
MAM Machine adaptation module
OEM OEM-supplied library

4. D7-SYS Compilation Log Interpretation

A typical aborted compile log reads (paths abbreviated for clarity):

=== Compile/Download statistics ===
Block list generated
S7 program : S7PROGR
Passive station handling: no
System data: from installation
Library: KAM001 (vendor: OEM)
... KAM001.msk not found in ...\Project\Global\sdblocks
   or in C:\Program Files (x86)\Siemens\Step7\s7cfc\sdblocks
Compilation aborted.

The two critical lines to extract from the log are:

  1. The block family declared in the log (e.g. KAM001). This identifies the missing library pair.
  2. The path in which the compiler searched. The searched path depends on the option in Options → Customize → Compile/Download.

Other useful log fields:

Log field Meaning
Library: <name> (vendor: ...) Identifies the missing library and its supplier
System data: from installation Search was performed in the global sdblocks
System data: from project folder Search was performed in the project sdblocks
Compilation aborted No S7 program was generated; the memory card write cannot proceed
Header version mismatch .a and .msk exist but originate from different D7-SYS builds
Engineer field note: When the log says "aborted by user" it means the engineer clicked No or Cancel in a follow-up dialog before the compiler wrote the S7 program. The dialog typically appears when the compiler needs to overwrite an existing S7 program on disk. Always click Yes to overwrite, or save the existing program under a versioned filename first.

5. Library File Placement Directories

D7-SYS looks for .a and .msk files in one of two locations, depending on the system-data option selected in the project:

Option Search path for .a and .msk Best for
System data from installation C:\Program Files (x86)\Siemens\Step7\s7cfc\sdblocks Workstations with a curated global library set installed by IT
System data from project folder <project>\Global\sdblocks Portable projects that must work on any laptop

On 64-bit STEP 7 installations the path may be C:\Program Files\Siemens\Automation\Step7\s7cfc\sdblocks. Verify against the actual STEP 7 install path on the workstation. On Windows 10/11 with UAC enabled, writing into Program Files requires the editor to be launched as administrator — the CFC editor does not auto-elevate.

Both files of a pair must be present in the same directory. If only the .a is present, the compiler reports the missing .msk even though the file is in the project ZIP. Symlinks and NTFS Junctions are not supported by the S7-CFC loader — use a real copy. File attributes also matter: if either file is marked read-only (e.g. restored from a CD image), the compiler may report a write failure rather than a missing-library error.

The two options are mutually exclusive per project. Switching the option forces a full re-link; the previous .msk is no longer consulted. This is by design: a project meant to be portable across workstations should use "System data from project folder", while a workstation with a curated global library set should use "System data from installation". On a maintenance laptop, the latter is often the better choice because the global sdblocks directory can hold many versions of the same library family and the loader can pick the one matching the chart's required major version.

6. Step-by-Step Resolution Procedure

The recommended recovery sequence for an offline backup load into a memory card is:

  1. Export the project ZIP from the original development laptop if you still have access to it. The ZIP must include the \Global\sdblocks folder that contains the originally compiled library pair. Use File → Archive in SIMATIC Manager with the "With S7 library references" option enabled, or in D7-SYS use Project → Export → Project archive.
  2. Open the project on the maintenance laptop with the D7-SYS version that matches the original development version. This is the only reliable way to load a backup from a project ZIP. If the original version is unavailable, request it from the supplier or commission a virtual machine with the required service pack.
  3. Inspect the compilation log to identify the missing library family. If the log shows KAM001, the missing pair is KAM001.a and KAM001.msk. Note the vendor field and the header version when present.
  4. Choose the system-data option in Options → Customize → Compile/Download that matches your working scenario:
    • System data from installation — for workstations with a curated global library set installed by IT.
    • System data from project folder — for portable projects that must work on any laptop.
  5. Place the library pair in the corresponding directory. Use Windows Explorer, copy from a command prompt, or robocopy to preserve attributes:
    REM System data from installation
    copy KAM001.a "C:\Program Files (x86)\Siemens\Step7\s7cfc\sdblocks\"
    copy KAM001.msk "C:\Program Files (x86)\Siemens\Step7\s7cfc\sdblocks\"
    
    REM System data from project folder
    copy KAM001.a "<project>\Global\sdblocks\"
    copy KAM001.msk "<project>\Global\sdblocks\"
  6. Re-run the compile/download. The CFC compiler must report "0 errors, 0 warnings" and generate the S7 program files (S7PROGR.S7P, the system data blocks, and the chart sources) into the project download folder.
  7. Write to the memory card using the standard SIMATIC transfer sequence:
    • Power down the PLC and remove the MMC/CF card from the CPU (CPU 314/315/317/319, ET 200S, etc.).
    • Insert the card into the programming device's PC card slot (or use a SIMATIC USB card reader such as 6ES7792-0AA00-0XA0).
    • In STEP 7 Manager, choose PLC → Download to Memory Card.
    • Select the target card slot and the S7 program tree. Confirm the overwrite prompt.
  8. Re-insert the card into the CPU and perform an overall reset (MRES) before the first download. The MRES clears the RAM work memory and forces a fresh load of the S7 program from the card.
Engineer field note: If the project ZIP was created with a D7-SYS version newer than the one installed, the chart may use FB/FC block numbers (e.g. FC 9200+) that are not allocated in older STEP 7 symbol tables. The S7-CFC loader will allocate the numbers automatically on the first compile, but if the compile succeeds and the PLC still rejects the card, re-export the symbol table from the S7 program sources and re-import on the target CPU.

7. Working with .KMZ Library Archives

A .KMZ file is a ZIP archive that contains a D7-SYS library in compressed form. The archive bundles the .a and .msk files together with metadata so the library can be versioned and distributed. To install a .KMZ file:

  1. Open D7-SYS / S7-CFC on the maintenance laptop.
  2. Choose Options → Library → Install / Uninstall.
  3. Browse to the .KMZ and confirm the installation. The installer extracts the files into the sdblocks directory of the current mode (installation or project).
  4. Verify both files appear in the chosen directory using Windows Explorer or dir from a command prompt.
  5. Restart the D7-SYS editor so the library registry is re-read. S7-CFC caches the library list at editor start.

To verify the contents of a .KMZ without installing, treat it as a ZIP and list its members:

powershell Expand-Archive -Path KAM001.kmz -DestinationPath C:\temp\kmz_inspect
dir C:\temp\kmz_inspect
type C:\temp\kmz_inspect\manifest.xml

The manifest (if present) typically records the D7-SYS version that produced the archive, the library family, and the block version. Cross-check this against the version stamp in the chart's compilation log.

Engineer field note: A .KMZ provided by a third party can be older or newer than the chart that references it. The mask version must match the chart's drive family. Always request the .KMZ of the same D7-SYS service pack that produced the chart export. When in doubt, ask the supplier for the PROJECT_INFO.TXT that documents the build environment, then reproduce the same environment on the maintenance laptop.

8. Version Compatibility Between D7-SYS Releases

D7-SYS is the Siemens engineering framework that sits on top of SIMATIC STEP 7 and adds the CFC and SFC editors tailored to drive applications. Major releases have introduced support for new drive families and added STEP 7 version compatibility. Verify the exact release notes for your target version at the Siemens Industry Online Support portal before planning a migration.

General compatibility rules of thumb (verify against the D7-SYS release notes for the specific service pack):

  • Standard libraries (FBSG*, FBSLIC) can be updated automatically by D7-SYS' Project → Update libraries function. The function reads the chart's required version stamp, locates a compatible pair in the global sdblocks, and re-binds. This works across major D7-SYS versions for standard libraries.
  • Custom libraries (KAM, CAM, MAM, OEM) cannot be updated automatically. The mask encodes a CRC of the parameter set that the supplier's tool produced, and the CRC is opaque to D7-SYS. A custom KAM library must be re-exported from the original supplier engineering environment.
  • STEP 7 base compatibility depends on the D7-SYS service pack. Newer D7-SYS releases may require a newer STEP 7 SP and will refuse to install on an older STEP 7 base. Refer to the D7-SYS installation manual for the exact STEP 7 compatibility matrix.
  • CPU firmware is independent. A D7-SYS V8.x project can be loaded into a CPU 315-2 PN/DP running an older firmware, as long as the S7 program tree is valid. The memory card format (FAT16 with a 16 MB partition for older MMCs, FAT32 for newer 256 MB+ cards) is determined by the CPU, not by D7-SYS.

For projects with standard libraries only, the Update libraries function is the recommended path. For projects with custom libraries, the only reliable path is to install the source D7-SYS version on the maintenance laptop (or in a virtual machine) and load the project ZIP with the original \Global\sdblocks folder intact.

9. Verification Procedure

After a successful compile/download, verify the following checkpoints before declaring the memory card load complete:

Check Command / location Expected result
Compile log shows zero errors CFC editor → Chart → Compile "0 errors, 0 warnings"
Both library files present Windows Explorer in sdblocks KAM001.a AND KAM001.msk
S7 program files generated Project download folder S7PROGR.S7P, S7PROGR.S7L present
Memory card image valid STEP 7 Manager → PLC → Memory Card Image opens, system data blocks visible
Card directory structure Card slot in Windows Explorer \SIMATIC.S7S, \CRACKES7, \FWUPDATE.S7S visible (older MMCs)
Online compare Online vs. offline blocks No SDB mismatch warning
CPU boot after MRES CPU diagnostic LEDs SF off, BF off (or expected BF for unconnected Profibus), RUN solid green
Drive online STARTER / SCOUT commissioning tool Drive visible, drive parameters loaded, no F-faults

If any of the above fails, repeat the placement step and re-verify that the option in Options → Customize → Compile/Download still matches the directory where the files were placed. Switching the option without copying the libraries to the new location will reproduce the missing-library abort.

10. Troubleshooting Matrix

The following matrix maps the most common fault messages to their root cause and remedy. Use it as a fast diagnostic aid in the field.

Symptom / log message Likely root cause Remedy
KAM001.msk not found in ... Library pair absent from active sdblocks Copy .a + .msk into the active sdblocks directory
Header version mismatch .a and .msk from different D7-SYS builds Request matching pair from supplier; do not mix versions
Compilation aborted by user Engineer clicked No/Cancel in the overwrite dialog Click Yes to overwrite; or rename the existing S7 program first
Compile OK, but Download to Memory Card button greyed out No S7 program tree in the project download folder Re-run PLC → Compile and Download Objects from STEP 7 Manager
Card write fails with Access denied Card is write-protected (mechanical slider on MMC) or filesystem is read-only Unlock the MMC slider; re-format the card using the SIMATIC card formatter
CPU stays in STOP after card insert and MRES S7 program on card is corrupt or compiled against wrong STEP 7 base Re-compile with matching D7-SYS / STEP 7 service pack; verify CPU firmware compatibility
SF LED on, diagnostic buffer shows Area length error in FB / FC Multi-instance DB mismatch, usually from a KAM update that changed the parameter set Perform overall reset, delete all DBs, reload from card
BF LED on after load, no Profibus communication Profibus configuration on the card does not match the connected slave topology Re-export HW Config from the source project; check DP slave addresses
Compile log: Library X not registered The .KMZ was installed but D7-SYS was not restarted Close and reopen D7-SYS; re-run compile
Compile log: Cannot write to sdblocks UAC blocking the write to Program Files Run D7-SYS as administrator, or switch to System data from project folder

11. Preventive Measures and Best Practices

  1. Always archive the project with the \Global\sdblocks folder in the ZIP. The folder contains all linked library pairs and is mandatory for cross-version load. Use File → Archive → User-defined in SIMATIC Manager and check the S7 libraries option.
  2. Document the D7-SYS version and service pack used to create the project. Save this in a PROJECT_INFO.TXT next to the project file, e.g.:
    Project: PressLine42
    Created with: D7-SYS V6.0 SP4 HF7
    STEP 7: V5.4 SP3
    Library sources: MASTERDRIVES VC (FBSGVC.A v2.4.1), KAM001 v1.2.0
    CRC of KAM001.msk: 0xA1B2C3D4
  3. Use "System data from project folder" when delivering the project to a third party. This avoids the workstation's global library set and guarantees the shipped libraries are exactly what the chart expects.
  4. Keep a clean, versioned library repository for custom KAM/CAM/MAM modules. A Subversion or Git LFS repository with the .a / .msk pairs stored next to the project ZIPs is the most robust approach. Tag each release with the chart's CRC of the parameter set.
  5. Avoid automatic library updates on custom modules. The dialog may report success while silently re-binding to a different parameter set. Always keep a backup of the original pair and verify the CRC after an update.
  6. If the supplier's .KMZ is suspect, request a new export from the original engineering laptop that produced the project ZIP. The export must use the same D7-SYS service pack. Do not rely on a verbal confirmation of the version — request the manifest.xml from the .KMZ as proof.
  7. Use a dedicated MMC card reader rather than the PG slot when possible. Native PG slots occasionally corrupt the FAT16 filesystem on industrial MMCs, especially on MMCs that have been re-inserted many times. The SIMATIC USB card reader (6ES7792-0AA00-0XA0) and the Field PG M4/M5/M6 built-in readers are the only recommended devices.
  8. Lock the maintenance laptop's D7-SYS version to the project's required build. Do not auto-update the S7-CFC installation; verify any Windows update does not trigger a STEP 7 SP upgrade that re-allocates library paths.
  9. Build a virtual machine template per D7-SYS version. For multi-version support, a VM per major version (V6.0, V6.1, V7.0, V7.1, V8.0, V8.1, V8.2) is faster and more reliable than side-by-side installs on a single Windows instance. Snapshot the VM after install so the maintenance environment can be recreated in minutes.
  10. After every successful load, store a checksum of the card image in the project archive. A simple certutil -hashfile S7PROGR.S7P SHA256 is enough to verify that the on-card S7 program matches the offline backup.

12. Flowchart: Compile/Download Recovery Path

The following inline SVG summarises the decision flow an engineer follows when the compile aborts on a missing library. Use it as a quick reference card on the shop floor.

Compile/Download Library missing (e.g. KAM001) Read log: identify family Option: System data from installation? (Options → Customize → Compile/Download) Option: System data from project folder? Copy .a + .msk to C:\Program Files (x86)\Siemens\Step7\s7cfc\sdblocks\ Copy .a + .msk to <project>\Global\sdblocks\ Re-run compile/download 0 errors, 0 warnings? Yes → Write to MMC No → Check version stamp Get matching .msk from supplier

13. Related Siemens Documentation

For the authoritative description of the library loader and the compile/download pipeline, refer to the following Siemens documentation (always cross-check the document revision against the D7-SYS service pack installed on your workstation):

14. FAQ

Why does D7-SYS refuse to load a backup to the memory card even though the project opens?

Because the compile/download pipeline is two-stage. The chart editor opens the chart, but the S7 program generator still needs the linked libraries. A missing .a/.msk pair aborts the compile, and the "Download to Memory Card" button is disabled until the compile produces a valid S7 program tree.

Where do I place the KAM001.msk file so the compiler finds it?

Either C:\Program Files (x86)\Siemens\Step7\s7cfc\sdblocks (if "System data from installation" is selected) or <project>\Global\sdblocks (if "System data from project folder" is selected). The .a companion file must sit next to the .msk in the same folder; symlinks are not supported.

Can I load a D7-SYS V6.x project with D7-SYS V8.1?

Yes, but only for projects that use standard libraries (FBSG*, FBSLIC). For projects with custom KAM/CAM/MAM libraries you must use the original D7-SYS version or obtain a V8.1-compatible KAM library from the supplier. The "Update libraries" function cannot rewrite custom modules.

What is the difference between .a and .msk files?

The .a file is the compiled S7 archive containing the FB/FC/DB source code; the .msk is the mask that describes the drive family, slot mapping, and parameter list. The compiler requires both files of a pair to originate from the same D7-SYS build. A version mismatch between .a and .msk is treated as a missing library.

The supplier sent a .KMZ file — how do I install it?

Open D7-SYS and choose Options → Library → Install/Uninstall, then browse to the .KMZ. The installer extracts the .a/.msk pair into the current sdblocks directory. Verify both files appear, restart the editor so the library registry is re-read, and re-run the compile. If the compiler still reports the library missing, request a .KMZ of the same D7-SYS service pack that produced the project.

What does "Compilation aborted by user" in the log actually mean?

It means the engineer clicked "No" or "Cancel" in a follow-up dialog before the compiler wrote the S7 program tree, typically the overwrite-existing-program prompt. Click "Yes" to overwrite, or rename the existing S7 program to a versioned filename first.

Can the project ZIP be loaded into a virtual SIMATIC PLC (S7-PLCSIM) for testing?

Yes, once the compile succeeds and the S7 program tree is generated. S7-PLCSIM can load the same S7 program you would write to the memory card. Use it to verify the compile result before touching real hardware, especially for a missing-library recovery that is not yet trusted.

Back to blog