Decoding Siemens MASTERDRIVES DriveMonitor Hex Parameter Values

David Krause12 min read
SiemensTechnical ReferenceVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Siemens SIMOVERT MASTERDRIVES family (converters 6SE70 / 6SE70-MC / 6SE70-VC) communicates engineering data to commissioning tools through DriveMonitor and the successor STARTER commissioning platform using a mix of fixed-point, floating-point, hexadecimal, and bit-coded formats. Decimal parameter values (P554 = 1, P554 = 65, etc.) are read directly, while signal-source and bit-coded parameters are translated to hexadecimal because the integer value is a packed bit field or a connector/binector index. This produces readings such as 0x1001, 0x2111, or 0x2011 in the parameter editor.

A 6SE7038-2EH85 is the Siemens catalog designation for an MC-series MASTERDRIVES inverter in the 38-class (approx. 700 V DC class / 660-690 V AC 3-phase) frame, sized for 38 A armature/line current with a 2-style book-size construction and EH85 control electronics. When commissioning this unit through DriveMonitor V05.05.00.01_00.00.02.94, every parameter that selects a binector (boolean signal source) or connector (analog/word signal source) inside the firmware will display a hexadecimal source address, not a text description. The reading is correct, but untranslated, because the firmware-32 display library of DriveMonitor releases prior to V05.10 does not contain all textual mappings for MC firmware 02.xx and later. Reading the value as raw firmware data still reveals the underlying bit assignment.

Critical: Hex values shown in DriveMonitor are not faults, not parameters to enter, and not the values to be programmed into the drive. They are display translations of the signal-routing table. Re-entering 0x1001 anywhere will be interpreted as the firmware signal source, not as a hexadecimal constant.

Control Word Architecture

The Siemens MASTERDRIVES defines a 16-bit control word (German: Steuerwort, abbreviated SSt) that is interrogated by the inverter every 2 ms (equivalent to one time slice at the default 10 kHz current-loop tick, sub-multiple 5). Bit assignments are firm-defined by firmware and printed in the operating instructions as Figure 4.4 (FC) / Figure 4.4.2 (MC). The mapping for firmware 02.xx and later is:

Bit Name (EN) Designation Function
0 ON/OFF1 SBus StW.0 0 = ramp-down + lockout, 1 = enable
1 OFF2 StW.1 0 = pulse inhibit, 1 = OK
2 OFF3 StW.2 0 = fastest stop, 1 = OK
3 Inverter enable StW.3 0 = pulse inhibit, 1 = enable
4 Ramp generator enable StW.4 0 = freeze, 1 = run
5 Ramp freeze StW.5 0 = ungated ramp, 1 = freeze
6 Setpoint enable StW.6 0 = droop to 0, 1 = use setpoint
7 Acknowledge (rising edge) StW.7 Reset faults on 0->1
8 Fixed setpoint bit 0 StW.8 Encoder
9 Fixed setpoint bit 1 StW.9 Encoder
10 Direction of rotation (negated) StW.10 0 = CCW, 1 = CW
11 Halt StW.11 0 = halt, 1 = run
12 Speed setpoint source bit 0 StW.12 Encoder
13 Speed setpoint source bit 1 StW.13 Encoder
14 Parameter set bit 0 / quick stop StW.14 Source dependent
15 Parameter set bit 1 StW.15 Source dependent

The status word (German: Zustandswort, ZSW) mirrors the same indexing but reflects drive telemetry. Common status bits include:

Bit Name Meaning
0 Ready to switch on Setup complete, no lockout
1 Ready to operate OFF1 condition met
2 Operation enabled Output stage active
3 Fault present Fault bit set
4 OFF2 active Low-active stop in progress
5 OFF3 active Emergency stop active
6 Switch-on inhibit Interlock present
7 Alarm active No fault but warning present
8-9 Speed deviation / set-actual difference Within tolerance
10 Speed controller reached Setpoint reached
11 I-limit reached Current limit active
12 Line/arming contactor check Power section OK
13 Motor overheat PTC/Pt100 alarm
14-15 Active parameter set / reverse direction Encoding

Parameter P554 Source Mapping

P554 is the master Control Word Bit 0 source selector on the MC build. The expected raw numeric value is the binector address, an integer that DriveMonitor formats as hexadecimal because the firmware stores it as an unsigned 16-bit index. The most common mapping referenced in 6SE70 commissioning guides is:

Hex display Binector assignment Source identification
0x0000 B0 Fixed logic 0 (always low)
0x1001 DI1 / B1025 Terminal X101.1 (digital input 1)
0x1n01 DI n+1 Indexed by terminal number
0x2n00 USSw internal bit Internal serial-port or USS slot routing
0x2111 USS channel / fieldbit 11 on channel 1 Profibus/USS slot 1 word bit 11 routing
0x3011 Profibus slot 1 field-bit 1 PROFIBUS source word index
0x4010 PMU control panel Operator panel command
0xA001 Function generator output Internal test function

The DriveMonitor firmware database may carry the binector-to-text mapping for the most common indices (terminal DI inputs) but will show raw hex where the routing crosses fieldbus, parameter-data-set, or compounded bit-assignment paths. Where 0x2111 is shown and the manual excerpt does not list it, the value should be interpreted as not yet labeled in the engineering tool version in use rather than as a missing or invalid entry.

Ambiguity path: When the manual leaves the upper-nibble routing (>0xA) ambiguous between function generator, technology controller, or fieldbus, verify by following two firmware-trace steps before modifying: (1) Read the SOURCE index in DriveMonitor at P554.r and P554.X; (2) Toggle the suspected DI/USSw on the host while tracing the live bit in TraceX via r0002/r0003 status display. Do not overwrite without confirming that the active source is not a safety-rated input (OFF2 / OFF3 must be hard-wired).

Compound Parameters P312 and P315

The values appearing in P312 and P315 are not encrypted or random nibble-patterns; they are nibble-coded configuration words in which each 4-bit half-byte selects a function.

P312 — Current-controller average mode

P312 selects the averaging mode used by the IDC-current regulator inside the MASTERDRIVES MC firmware function block Id control (Figure 4.4.2 of the RRU / Id Firmware Operating Instructions shipped with 6SE7038 builds).

Value (dec) Average mode Description
0 Instantaneous current Latest sampled Iq at every 105 us tick
1 Sliding average of three 3-tap FIR filter on raw Iq
2 Intermittent mode Average of three continuous; instantaneous during transients

P315 — Pulse-pattern / firing mode

P315 selects the firing-pulse pattern in conjunction with the relevant firmware function. The nibble structure is preserved on select MC firmware 02.xx branches. Always verify against the firmware-revision-specific operating instructions because late-revision firmware may repurpose the upper nibble to vector-control or dead-time compensation.

Hex values such as 0x2011 shown against display parameters (e.g., r-parameters) are display only. They are not parameter write sources. Do not attempt to program a control word into a read-only r-parameter; the firmware will reject the write.

Hex-to-Bit Decoding Procedure

Where the manual does not give the source behind a hexadecimal display, perform this engineer-grade decode sequence in DriveMonitor or STARTER:

  1. Capture the raw value in integer mode (decimal) by switching the parameter display to DEC under Settings -> Display format. The decimal equivalent, not the hex text, is the canonical value used by the firmware.
  2. Convert to binary using a calculator. Each bit corresponds to a fixed signal source per the binector table; for MC firmware 02.xx the standard binector map is in the operating instructions section "BICO converters".
  3. Cross-reference each set bit against the binector numbering scheme. Upper nibble commonly designates the source class (digital input, USS slot, Profibus, PMU, internal flag). Lower nibble designates the bit/terminal index inside that class.
  4. Confirm with the live trace by setting DriveMonitor online and dragging the suspected binector onto a trace channel (x-power x-numeric value) together with the parameter under investigation.
  5. Document the result in the commissioning log so future field service engineers reading the same hex string can resolve without firmware manuals.

Worked Example: 0x1001 Decoded

Hex   : 0x1001
Bin   : 0001 0000 0000 0001
Upper nibble 0x1 : Digital input class
Lower nibble 0x1 : Terminal 1
Result: P554 is sourced from terminal X101.1 (binector B1025 by MASTERDRIVES routing)

Worked Example: 0x2111 Decoded

Hex   : 0x2111
Bin   : 0010 0001 0001 0001
Upper nibble 0x2 : USS / serial field bit class
Middle byte      : 0x11 (slot 1, channel 1)
Lower nibble     : 0x1 (bit index 1)
Result: P554 is sourced from Profibus/USS slot 1, channel 1, bit 1

DriveMonitor Tool Configuration

DriveMonitor V05.05.00.01_00.00.02.94 with release baseline V05.05.00.00_20.00.00.00 ships a default text mapping library that supports firmware 02.0x baseline. To extend the translation table for later MC firmware revisions:

  1. Launch DriveMonitor and connect via PROFIBUS, USS, or RS232-C (MPI on the SICOM interface, baud 19 200-115 200 bps depending on option board).
  2. Open File -> Update Device Database and verify that the latest device description files (DDP, .dpv variants) are loaded from the Siemens Industry Online Support portal for 6SE70 / SIMOVERT.
  3. Select Tools -> Option Packages and confirm that "Drive ES" option bit for HEXEXT or extended COM-Master is enabled if fieldbus source mapping beyond DI is required.
  4. Restart DriveMonitor to refresh the parameter browser cache.

Version compatibility matrix

DriveMonitor release Baseline release Supported MC firmware Hex display behavior
V04.04.xx — 01.xx Text where available
V05.05.00.01 V05.05.00.00_20.00.00.00 02.0x/02.1x Hex where textual mapping missing
V05.10.00.00 V05.10.00.00_30.00.00.00 02.2x and later Wider BICO text coverage
STARTER V4.x — 02.3x, 04.xx Full text with converter tooltips

Where a translated descriptor is missing, the workaround is to either (a) upgrade DriveMonitor to V05.10 or later, (b) migrate to STARTER (Siemens part number 6SL3072-0AA00-0AG0 for license) which carries an updated COM database, or (c) keep DriveMonitor and rely on the manual BICO table for manual decode as covered above.

Status Word Decoding in Online Mode

For online monitoring of a running 6SE7038-2EH85, DriveMonitor exposes the live status word through parameter r0002 (firmware-32 parameter model: status word, decimal) and r0003. The values are produced already in decimal; to interpret hex:

  1. View r0002 in decimal (e.g., 0x6F03 displayed under hex mode). Note the running pattern.
  2. Switch to bit-level visualization via Tools -> Display -> BICO bit inspector.
  3. Match against the ZSW table above. A value of 0x6F03 decodes to bits 0, 1, 8, 9, 10, 11, 12, 13 which corresponds to "Ready to switch on + Ready to operate + speed reached + n-controller released + drive running + direction active + torque limit reached".

Field Commissioning Verification

After resolving any hex-source parameter that drives a safety-rated input, perform this verification sequence before returning the drive to production:

  1. Source freeze: Write-read-back each affected P-number (P553-P567 family) and confirm that the decimal value persists through a drive cold start (power off, capacitor discharge > 5 minutes for 690 V MC class).
  2. Safe stop route: Wire the hard-wired OFF2 (terminal) through a path that cannot be overridden by software, then pulse OFF2 by removing the source edge. Output stage must pulse-suppress within 50 ms.
  3. Bench trace: With motor unloaded, capture r0002 status word trace, P554 effective source bit, and DI1 line through TraceX into a .trc file; confirm source bit-to-DI mapping matches the decoded plan.
  4. Fault injection rehearsal: Trip an F-coded fault (e.g., F011 overcurrent) and verify that Acknowledge (StW bit 7) reaches the firmware via the route selected by your hex source, not via an unintended alternate route such as USS slot 0 or PMU button.
  5. Document sign-off by recording the binector trace route, software revision, the operator panel version, and the date in the device's parameter card (DriveMonitor File -> Save Parameter Set).

Common Pitfalls and Field Notes

The following are the most frequent field issues encountered on 6SE70 / 6SE7038 hardware:

  • Hex value mistaken for a fault address. 0x1001 is not a fault code; the F-coded fault indices are 0xFxxx values (visible only on the F-queue).
  • Writing hex to a display-only parameter. P and r parameters are not interchangeable. Hex like 0x2011 shown for an r-parameter must never be entered back to the firmware as a P write.
  • Safety inputs routable by software. STOP-C, Stop-D safe functions on the 6SE70 use a separate terminal path through the option board (S01/S02). Hex control-word bit selection is not a substitute for the safety wiring.
  • DriveMonitor language file drift. When the connected drive firmware exceeds the DriveMonitor version baseline, some binector indexes revert to hex even for normally-text-displayed sources (DI1, DI2, DI3). Confirm by checking the firmware hash shown in DriveMonitor against the device database version.
  • P312/P315 changed silently after firmware update. Firmware 02.xx to 03.xx migrators may shift the nibble significance for current-control mode. Always re-write P312 / P315 after a firmware upgrade.
  • PROFIBUS header bit confusion. Slot 0 word-and-bit indexing into the binector table is non-intuitive; 0x2111 often looks similar to 0x2011 and is often mistaken for one. Maintain a project-specific mapping table in the engineering repository.

Cross-Reference Summary Table

Parameter Display semantics Edit semantics If hex shown, decode as
P554 Binector / connector source for StW.0 Set binector index Bit-coded source class
P555 StW.1 source Set binector index Bit-coded source class
P312 Current average mode (0,1,2) Set decimal 0/1/2 Decimal fixed (no hex)
P315 Firing mode Set nibble pattern Nibble pattern, not bit-pattern
r0002 Status word read-only Read-only Hex or dec, never write
r0003 Status word 2 read-only Read-only Hex or dec, never write

Why does DriveMonitor show hexadecimal values such as 0x1001 instead of a text description for P554?

P554 selects the binector source for control-word bit 0 (ON/OFF1). DriveMonitor displays the binector index numerically; because firmware 02.xx MC builds carry more binector classes than the device-description library of DriveMonitor V05.05 covers, the value is rendered as raw hexadecimal such as 0x1001, which decodes to digital input 1 (terminal X101.1). Updating DriveMonitor or migrating to STARTER restores the textual mapping for these classes.

What does the hexadecimal value 0x2111 in P554 mean on a 6SE7038-2EH85?

The upper nibble (0x2) indicates a USS or serial-link source class; the middle byte (0x11) refers to slot 1 / channel 1 on the serial interface; the lower nibble (0x1) is the bit index inside that slot. The result is control-word bit 0 sourced from the USS/PROFIBUS slot 1 bit 1. The reading is correct; the manual does not catalog it because 0x2111 is a derived binector index reserved for fieldbus class routing.

Are P312 and P315 hexadecimal or decimal on the MASTERDRIVES MC?

P312 (current-average mode) is decimal and accepts 0, 1, or 2. P315 (firing-pattern selection) is a nibble-coded hex pattern in the order low-nibble first; each nibble selects an option. Neither should be entered as full-bit hex values such as 0x1001.

Can I enter 0x1001 directly as a DriveMonitor parameter value?

Yes for parameter numbers that the firmware treats as binector indices (P554, P555, P556, P417, etc.). Do not enter it into read-only r-parameters or into parameters that the firmware interprets as decimal counts (P312, P315 in their low-decimal significance). Always cross-check against the operating instructions section for the parameter before editing.

Which version of DriveMonitor removes the hex-only display on MASTERDRIVES 6SE70?

DriveMonitor V05.10.00.00 baseline V05.10.00.00_30.00.00.00 and the STARTER V4.x commissioning platform carry the extended BICO binector text map. For 6SE7038-2EH85 (MC 02.xx/02.1x builds) the upgrade adds descriptions to previously hex-only sources and supports the safe-stop option firmware variants as well.

Back to blog