Overview
When a Siemens TP1200 Comfort Panel is networked with an S7-1500 CPU such as the 6ES7513-1AM02-0AB0 (CPU 1513-1 PN), detecting whether the controller is in RUN, has switched to STOP, or has lost power entirely from the HMI side is not automatic. WinCC Advanced V15 only renders a small connection-interrupted indicator at the bottom of the active screen; it does not pop up an alarm view, change screens, or trigger an audible warning on its own. For most operator-facing panels this is insufficient: a stopped or dead PLC must produce an unmistakable, full-screen alarm within seconds of the event.
This article documents five field-proven methods that close the direction PLC to HMI (i.e., the panel learning the state of the CPU), covering custom heartbeats, the built-in connection error event, the System Diagnostics View control, the S7-1500 System Status List, and WinCC scheduled tasks driving a popup screen. Configuration is shown for TIA Portal V15.1 with WinCC Advanced V15.1 on a TP1200 Comfort (6AV2 124-1MC01-0AX0) talking to a CPU 1513-1 PN. All methods work from TIA V14 SP1 onward unless otherwise noted.
Prerequisites
- PLC: SIMATIC S7-1500 CPU (e.g., 6ES7513-1AM02-0AB0 CPU 1513-1 PN), firmware V2.0 or later. TIA Portal V15 supports S7-1500 firmware V1.8 onward.
- HMI: SIMATIC TP1200 Comfort (6AV2 124-1MC01-0AX0) or other Comfort / Comfort PRO panel running WinCC Advanced V15 (or later) runtime.
- Engineering: TIA Portal V15.1 or V15.5 with matching HSP for CPU firmware; WinCC Advanced is part of the TIA Portal install on a license-bearing engineering station.
- Network: The HMI and PLC must be reachable on the same PROFINET subnet; both devices configured under "Devices & Networks" with an HMI connection of type "S7 connection".
- Firmware compatibility: S7-1500 firmware V2.6 / V2.8 requires TIA Portal V15.1 with the matching HSP. Firmware V2.9 / V2.10 requires TIA V16 or later. TP1200 Comfort firmware V15.x supports TIA V15.1 projects.
- Licensing: WinCC Advanced runtime on a Comfort Panel is included with the panel firmware; no separate runtime license is needed for system diagnostics, alarm logging, or scheduled tasks on TP1200 Comfort.
Before implementing any detection method, confirm the basic HMI connection is healthy: download both projects, watch the HMI's connection status icon turn green at runtime, and verify the PLC's online diagnostics under Online & Diagnostics → Status report no errors. Tag errors in the HMI compile output must be resolved before continuing.
Detection Methods Compared
| Method | Direction | Detects STOP | Detects Power Loss | Complexity | TIA Portal Version |
|---|---|---|---|---|---|
| Custom heartbeat tag (INT or BOOL) | PLC → HMI | Yes (after timeout) | Yes (after timeout) | Low | V14 SP1+ |
| Clock memory bit + watchdog | PLC → HMI | Yes | Yes | Low | V14+ |
| @DiagnosticIndicatorTag | System | Yes (via diagnostics) | Yes | Low | V14 SP1+ |
| System Diagnostic View control | System | Yes | Yes | Medium | V14 SP1+ |
| SFC 51 / Get_Connection_Status | PLC → HMI (via DB) | Yes | Indirect | High | V15+ |
| Built-in connection error event | HMI internal | Yes | Yes | Lowest | V14+ |
For most operator-warning use cases, the custom heartbeat (Method 1) or the built-in connection error event (Method 2) is sufficient. Use the System Diagnostics View (Method 3) when you want full event logging with timestamps and acknowledgment. Use SFC 51 (Method 4) when the PLC project must know its own operating mode for interlocking logic, not just the HMI.
Method 1 - PLC Heartbeat (Life Bit) Tag
The heartbeat is a counter or bit in the PLC that toggles continuously while the CPU is in RUN. The HMI reads the tag and raises an alarm if the value stops changing within a defined window. This is the most field-proven and least version-sensitive technique.
Step 1 - Create the heartbeat tag in the PLC
In the S7-1500 project, open a global DB (e.g., DB_HMI_Interface) and create the following members. The DB must have the HMI-accessible attribute set if any optimized-block attribute is in use; non-optimized blocks are accessible by default.
| Name | Type | Initial value | Comment |
|---|---|---|---|
| HMI_Heartbeat | DINT | 0 | Free-running counter for HMI liveness check |
| HMI_LifeBit | BOOL | FALSE | 500 ms toggling bit, redundant to counter |
Use DINT instead of INT to avoid wrap-around at 32767 increments. At a 10 ms OB1 cycle the counter reaches INT max in roughly five minutes; DINT reaches the equivalent in just over 24 years.
Step 2 - Drive the heartbeat in OB1
In OB1 (Main), add the following code. The counter increments every scan; the bit toggles via a TON timer. Declare HMI_LifeBit_Toggle as a global TON instance or use the IEC_TIMER block from the "Timers" catalog.
// Free-running counter (DINT)
"DB_HMI_Interface".HMI_Heartbeat := "DB_HMI_Interface".HMI_Heartbeat + 1;
// 500 ms toggle for the life bit
"HMI_LifeBit_Toggle"(
IN := TRUE,
PT := T#500ms
);
IF "HMI_LifeBit_Toggle".Q THEN
"DB_HMI_Interface".HMI_LifeBit := NOT "DB_HMI_Interface".HMI_LifeBit;
END_IF;
Alternative: enable S7-1500 clock memory in the CPU properties under System & Clock Memory. With byte 100 set as the clock byte, bit M101.3 toggles at 0.5 Hz. This requires no user code at all and uses no DB.
Step 3 - Create the HMI tags
In the HMI project, open HMI Tags and add:
| Tag | PLC connection | Address | Length | Acquisition cycle |
|---|---|---|---|---|
| Heartbeat_counter | PLC_1 | DB_HMI_Interface.HMI_Heartbeat | 4 bytes | 500 ms |
| HMI_LifeBit | PLC_1 | DB_HMI_Interface.HMI_LifeBit | 1 bit | 250 ms |
Step 4 - Configure a scheduled task to evaluate the heartbeat
Under Scheduled Tasks on the HMI, create a task named PLC_Liveness_Check with cycle 1 minute. In the event, call a VBScript function that:
- Reads the previously stored counter value.
- Compares the current value to the previous.
- Increments a debounce counter if equal; resets it on change.
- Sets the
PLC_Offline_Alarmtag after two consecutive equal reads.
Dim prev, curr
prev = SmartTags("Heartbeat_prev")
curr = SmartTags("Heartbeat_counter")
If curr = prev Then
SmartTags("PLC_Offline_Counter") = SmartTags("PLC_Offline_Counter") + 1
If SmartTags("PLC_Offline_Counter") >= 2 Then
SmartTags("PLC_Offline_Alarm") = True
End If
Else
SmartTags("PLC_Offline_Counter") = 0
SmartTags("PLC_Offline_Alarm") = False
End If
SmartTags("Heartbeat_prev") = curr
Reduce the cycle to 1 second if a faster reaction is required. The trade-off is slightly higher HMI CPU load; TP1200 Comfort handles a 1-second scheduled task with negligible performance impact.
Step 5 - Display a popup screen
On the PLC_Offline_Alarm tag, configure a Value Change event. Add the system function ActivateScreen with the target screen ConnectionLost. The screen contains a red banner, the PLC name, and instructions for the operator ("Check 24 V supply, check PROFINET cable, contact maintenance").
Method 2 - Built-in Connection Error Event
WinCC Advanced already monitors the S7 connection state at runtime. When the connection drops, a system event of class "Connection" is generated. The simplest method requires no PLC code and no tags.
Steps
- In the TIA Portal HMI project, open the HMI device configuration.
- Navigate to Runtime Settings → Services.
- Confirm the system diagnostic service is enabled (default since V14 SP1).
- The "Errors and warnings" event log populates with entries such as
Connection to PLC disruptedandConnection to PLC restored. - Add an Alarm View control to the desired screens and bind it to the "Connection" event class.
To fire a popup on connection loss without writing VBScript, attach the ActivateScreen system function to the value-change event of the system's @ConnectionState tag (available from V15.1 onward). For older versions, use Method 1.
Method 3 - System Diagnostic View and @DiagnosticIndicatorTag
@DiagnosticIndicatorTag is a system tag added to the HMI's tag list automatically when you insert a System Diagnostics View or enable system diagnostics. It returns a 16-bit status word with bits that indicate pending diagnostic events.
| Bit | Meaning |
|---|---|
| 0 | At least one diagnostic event pending |
| 1 | At least one diagnostic event requiring acknowledgment |
| 2-15 | Reserved |
Steps
- Drag System Diagnostics View from the toolbox onto a screen.
- In the control's properties, set the connection to the S7-1500 CPU.
- The system tag
@DiagnosticIndicatorTagappears under "Show all tags" in the HMI tag table. - Bind the tag to a Symbolic IO Field or evaluate it in VBScript to drive a status indicator.
- Optional: bind a Value Change event on the tag to a popup screen.
The System Diagnostics View displays live events including:
- CPU operating mode transitions (RUN → STOP, STOP → RUN, STARTUP).
- PROFINET IO faults and station failure.
- Module diagnostics (channel faults, wire break, short circuit).
- Power events on the CPU / interface modules.
The view updates automatically and does not require a custom heartbeat. Operator acknowledgment can be enabled or disabled per the application's needs.
Method 4 - PLC Operating Mode from S7-1500 System Status List
There is no TIA area pointer that exposes the CPU's current operating mode in the direction PLC → HMI for read-only access. However, the S7-1500 exposes the operating mode through the System Status List (SSL). Read it in the PLC and expose it as a regular HMI tag.
Step 1 - Use SFC 51 to read SSL partial list 0x0121
In OB1 (or a cyclic OB such as OB30 at 100 ms), call SFC 51 "RDSYSST" with:
-
SSL_ID = W#16#0121(CPU status information) INDEX = W#16#0000-
SZL_HEADERandDRpointing to a DB of sufficient length (at least 34 bytes)
// Call SFC 51 once per second via rising edge
"Clock_1Hz"(CLK := "Clock_Memory_1Hz", RETAIN := FALSE);
IF "Clock_1Hz".Q THEN
"DB_Status".Busy := TRUE;
"RDSYSST_DB"(REQ := TRUE,
SSL_ID := W#16#0121,
INDEX := W#16#0000,
SZL_HEADER := "DB_Status".SSL_Header,
DR := "DB_Status".SSL_DR,
BUSY => "DB_Status".Busy,
DONE => "DB_Status".Done,
ERROR => "DB_Status".Error);
IF "DB_Status".Done AND NOT "DB_Status".Error THEN
// First data record byte = operating mode
"DB_Status".OperatingMode := "DB_Status".SSL_DR[0];
END_IF;
END_IF;
Operating mode byte values:
| Value | Mode |
|---|---|
| 01 | STARTUP (OB100 / OB101 / OB102) |
| 02 | RUN |
| 03 | STOP |
| 04 | HOLD |
| 05 | Unknown / startup sequence |
Step 2 - Expose as HMI tag
Map the OperatingMode byte to the HMI tag table as a USINT. On the HMI side, evaluate the value with VBScript and update a Symbolic IO Field showing "RUN" / "STOP" / "STARTUP" or drive a colored status bar.
Alternative - Use T_DIAG for PROFINET connection diagnostics
For PROFINET connection diagnostics, the S7-1500 instruction library includes T_DIAG. Use it when the HMI may itself be the cause of the connection failure (e.g., panel frozen) rather than the PLC.
"iGet_Connection_Status_DB".REQ := "Clock_1Hz";
"iGet_Connection_Status_DB".CONNECTION_ID := 1;
"iGet_Connection_Status_DB".STATUS := "DB_Status".Connection_Status_Word;
Refer to the SIMATIC S7-1500 Automation System system manual for the exact status word layout of T_DIAG.
Method 5 - WinCC Scheduled Tasks and Popup Logic
This is the display mechanism used after any of the detection methods above. For low-latency detection, bind a Value Change event directly to the heartbeat counter tag rather than relying solely on a scheduled task.
Scheduled-task configuration
- Open Scheduled Tasks on the HMI.
- Create a new task named
PLC_Monitoring. - Set the cycle to
1 second(or shorter). - In the event, add a VBScript function that reads the heartbeat and either does nothing or calls
ActivateScreen.
Tag change event
For sub-second reaction, also bind a Change Value event to the Heartbeat_counter tag. Inside the event, check that the counter has incremented and call ActivateScreen if not. The combined approach gives you redundant detection paths.
Step-by-Step Implementation Guide
The following ordered procedure combines Methods 1 and 2 for the recommended production setup.
Phase 1 - PLC Configuration
- Open the S7-1500 project in TIA Portal V15.x.
- Create a new global DB
DB_HMI_Interfacewith:HMI_Heartbeat(DINT, start 0),HMI_LifeBit(BOOL, start FALSE). Tick "Accessible from HMI" if the DB is optimized. - In OB1, add a TON timer
HMI_LifeBit_Togglewith PT = T#500ms. Toggle the BOOL on each Q edge. - Increment
HMI_Heartbeateach OB1 cycle. - Compile and download to the CPU. Verify in the watch table that the BOOL toggles and the INT/DINT increments.
Phase 2 - HMI Tag Configuration
- Open the TP1200 Comfort project.
- Add a connection of type "S7 connection" pointing to the CPU 1513 if not already present. Note the connection ID for Method 4.
- Under HMI Tags, add:
Heartbeat_counter→DB_HMI_Interface.HMI_Heartbeat(DINT), 500 ms cycle;HMI_LifeBit→DB_HMI_Interface.HMI_LifeBit(BOOL), 250 ms cycle. - Add internal tags:
PLC_Offline_Alarm(BOOL),PLC_Offline_Counter(INT),Heartbeat_prev(DINT). - Compile the HMI project. Resolve any tag errors before continuing.
Phase 3 - HMI Logic
- Create a VBScript function
CheckPLCConnectionwith the code shown in Method 1. - Add a scheduled task
PLC_Monitoringwith 1-second cycle calling this function. - Optionally, add a Value Change event on
Heartbeat_counterthat calls the same function directly.
Phase 4 - Popup Screen
- Create screen
ConnectionLost. - Add a text field reading "PLC Connection Lost - Check CPU 1513".
- Add a button "Acknowledge" with the system function
SetBittoPLC_Offline_Alarm_Ack. - In
PLC_Offline_Alarmtag's Change Value event, callActivateScreen→ConnectionLost.
Phase 5 - Verification
- Download both PLC and HMI programs.
- Switch PLC to RUN. Verify the heartbeat counter increments in the watch table and on the HMI.
- Switch PLC to STOP via the programming device. Confirm the
ConnectionLostscreen appears within one scheduled-task cycle plus debounce. - Pull the PROFINET cable. Confirm same behavior with the "Connection disrupted" system event also firing.
- Power off the PLC. Confirm the HMI raises both the system event and the heartbeat-based alarm.
- Restore RUN. Verify the screen clears automatically on the next counter change.
Verification Procedures
| Test | Expected Result | Pass Criterion |
|---|---|---|
| PLC RUN, both networks OK | HMI shows green status, counter increments | Counter > 0 within 5 s |
| Switch PLC to STOP | Heartbeat stops incrementing | Popup within 60 s |
| Pull network cable | System event "Connection disrupted" + popup | Popup within 60 s |
| Power off PLC | System event + popup | Popup within 60 s |
| Restart PLC into RUN | Popup clears automatically | Cleared within 30 s of resume |
| HMI restart while PLC RUN | HMI reconnects, no popup after warm boot | Popup only on real outage |
To shorten detection time below the 1-second scheduled-task cycle, use a 100 ms acquisition cycle on the heartbeat tag and a 100 ms scheduled task. Detection latency drops to roughly 200-300 ms. Trade-off: more HMI panel CPU load. TP1200 Comfort handles a 100 ms cycle with up to 200 polled tags without measurable slowdown.
Troubleshooting Matrix
| Symptom | Likely Cause | Remedy |
|---|---|---|
| Heartbeat tag shows constant value | PLC not running, or wrong address configured | Verify tag address matches DB; force PLC to RUN; check optimized-block access attribute |
| Popup fires immediately at startup |
Heartbeat_prev initialized to current value |
Initialize Heartbeat_prev only after first read; use a startup tag to gate the alarm |
| Connection disrupted alarm fires but popup does not | Scheduled-task cycle too long | Reduce cycle to 1 second |
| HMI shows "connection interrupted" but popup never fires |
ActivateScreen event not bound |
Add event on tag value change; verify the system function is ActivateScreen and not SetScreen (latter is deprecated) |
| Counter wraps and equals previous | INT range exceeded | Use DINT; reset counter to 0 on PLC restart |
HMI never shows PLC_Offline_Alarm when cable unplugged |
Acquisition cycle on tag > scheduled-task cycle | Reduce acquisition to ≤ scheduled-task cycle |
| Multiple screens have popup logic | Event fired from wrong screen | Use a single central scheduled task instead of per-screen events |
| System Diagnostics View shows blank | No PROFINET IO configured or S7 connection uses different path | Use S7 connection with diagnostics enabled; verify system diagnostic service is active |
T_DIAG block errors out |
Connection ID mismatch | Verify connection ID matches HMI configuration in Devices & Networks |
@DiagnosticIndicatorTag not visible |
HMI not in "System Diagnostics" mode | Insert the System Diagnostic View control once; the tag is generated automatically |
| Popup appears but never clears | Reset logic missing in VBScript | Ensure PLC_Offline_Alarm is set to FALSE on counter change |
| SFC 51 returns error 80B1 (length error) | SSL_DR destination too small | Increase DB_Status size to at least 34 bytes; verify partial list 0x0121 returns 26 bytes of payload |
| S7-1500 firmware mismatch error on download | HSP not installed | Install the matching HSP via TIA Portal Options → Support Packages |
For S7-1500 communication details, refer to the SIMATIC S7-1500 Communication function manual. For Comfort Panel runtime limits and tag counts, refer to the SIMATIC HMI Devices Comfort Panels operating instructions.
Can I use the Coordination area pointer life bit to detect PLC stop from the HMI?
No. The Coordination life bit toggles from the HMI into the PLC; it lets the PLC detect that the HMI is alive, not the other way around. For PLC → HMI liveness, use a custom heartbeat tag in a DB, the System Diagnostics View, or the built-in connection error event described in this article.
What is the fastest detection time I can achieve on a TP1200 Comfort?
With a 100 ms acquisition cycle on the heartbeat tag and a 100 ms scheduled task, you can detect a stopped or powered-off PLC in roughly 200-300 ms including the debounce counter. Below 100 ms the panel's update jitter rises and detection reliability drops.
Does the TP1200 Comfort support the System Diagnostics View?
Yes. From TIA Portal V14 SP1 onward, the System Diagnostics View control is available in WinCC Comfort / Advanced and works without extra licensing on TP1200 Comfort and above. The view displays live diagnostic events including operating-mode transitions.
Will the HMI show a connection error automatically if the PROFINET cable is unplugged?
The HMI shows a connection-interrupted status indicator at the bottom of the screen, but it does not automatically show a popup screen or change to an alarm view. You must implement one of the methods above, or bind ActivateScreen to the connection-state event, to switch to a custom alarm screen.
Do I need to change the CPU firmware to use @DiagnosticIndicatorTag?
No firmware change is required. @DiagnosticIndicatorTag is part of the WinCC runtime on the HMI panel, not the PLC firmware. The S7-1500 firmware version only needs to be compatible with the TIA Portal version used for engineering.
Can I get the PLC operating mode without writing any PLC code?
Indirectly, yes. The System Diagnostics View displays the operating mode as a live diagnostic event when it changes (RUN → STOP, etc.). The detection is event-driven, so no polling tag is needed. If your application requires the mode as a continuously readable tag, use SFC 51 with SSL partial list 0x0121 as shown in Method 4.