Overview: KTP Basic Panel Screen Control Architecture
The SIMATIC KTP Basic panel family (KTP400 Basic, KTP700 Basic, KTP900 Basic, KTP1200 Basic, including DP variants) is a cost-optimized HMI line configured with WinCC Basic inside the Totally Integrated Automation (TIA) Portal. The Basic series ships with a fixed-function TFT backlight driver that is designed for a single calibrated luminance level. Unlike the SIMATIC Comfort Panels (TP700 Comfort through TP2200 Comfort) or the MP377 Touch daylight readable, the Basic family does not expose a continuously variable backlight PWM control in the runtime image or the engineering interface.
This is a deliberate hardware/firmware design choice: the backlight inverter on the Basic panels is driven by a single fixed-current source sized to the LCD optical stack. Attempting to dim the panel from the engineering project will fail because the corresponding system tag is not published in the WinCC Basic runtime. For applications that require active night-vision preservation - particularly on ship bridges, in wheelhouses, in submarine control stations, and in any 24-hour control room environment - the absence of true dimming must be addressed at the system-design stage, not the project stage.
This reference documents the three available mitigations, the correct TIA Portal configuration paths, the marine regulatory context, and a field-tested commissioning procedure for night-mode operation.
Affected Hardware and Firmware Range
| Panel Model | Article Number (6AV...) | Display | Backlight Type | Continuous Dimming |
|---|---|---|---|---|
| KTP400 Basic mono | 6AV2 123-2DB03-0AX0 | 4" mono STN | LED, fixed | No |
| KTP400 Basic (color) | 6AV2 123-2GB03-0AX0 | 4" TFT | LED, fixed | No |
| KTP700 Basic | 6AV2 123-2GB03-0AX0 / 6AV2 123-2GA03-0AX0 | 7" TFT widescreen | LED, fixed | No |
| KTP700 Basic DP | 6AV2 123-2GA03-0AX1 | 7" TFT widescreen | LED, fixed | No |
| KTP900 Basic | 6AV2 123-2JC04-0AX0 | 9" TFT widescreen | LED, fixed | No |
| KTP1200 Basic | 6AV2 123-2MA03-0AX0 | 12" TFT widescreen | LED, fixed | No |
| KTP1200 Basic DP | 6AV2 123-2MA03-0AX1 | 12" TFT widescreen | LED, fixed | No |
| MP377 15" Touch daylight readable | 6AV6 644-1AB20-1NA0 | 15" TFT, transflective | CCFL/LED, PWM dimmable | Yes (native) |
Available Display Controls on the Device
Although continuous dimming is not supported, the on-device Control Panel exposes two display-related settings that are useful for night operation:
- Brightness (color panels only) - A discrete, preset high/low toggle in the on-device Control Panel. Some firmware revisions expose this as a two-position switch; others expose it as a software contrast compensation only. The change is not propagated to the engineering project; it lives in the panel's local NV storage and survives power cycling.
- Calibration / Touch calibration - Independent of brightness; needed only if touch accuracy has drifted, often after mechanical shock (relevant on shipboard installations subject to vibration).
Accessing the On-Device Control Panel
- Power on the KTP Basic panel and wait for the runtime to start.
- Press the Settings button on the loader screen (the small gear/cog icon at the lower right of the loader), or in the running project, invoke the configured system function
OpenControlPanel. - Navigate to Control Panel > Display.
- Adjust the available brightness toggle and confirm with OK.
100 (administrator) and 200 (operator) for the loader. Override this in TIA Portal under HMI device > Security > User administration if the bridge crew must change settings without a maintenance callout.Screensaver as the Night-Mode Workaround
Because the backlight cannot be modulated, the only software-controlled mechanism that achieves a near-zero-luminance state is the screensaver. When activated, the screensaver blanks the screen content and renders a single small white square that moves to a random position against a black background. The black background forces the LCD to drive all subpixels to zero, which (combined with the panel's optical stack) effectively extinguishes emission from the backlight apertures for that region of the display.
For maritime night operation this is acceptable for IEC 61174 (ECDIS) and bridge-layout guidance under ISO 8468 - the moving square is small enough not to impair dark adaptation, and the black field is below the luminance thresholds typically cited for preserved scotopic vision. The screensaver activation is the recommended approach when the runtime does not need to remain readable.
TIA Portal Configuration Procedure
The following procedure configures the screensaver for a 1-minute timeout (typical bridge-watch value) and locks the loader against unauthorized changes.
Prerequisites
- TIA Portal V15.1 or later with WinCC Basic installed.
- KTP Basic project open; device configuration compiled without errors.
- Operator Panel (OP) or equivalent runtime license loaded on the engineering station.
- USB or Ethernet connection to the target panel for transfer.
Step 1: Set the Screensaver Timeout
- In the project tree, expand the HMI device (e.g., HMI_1 [KTP1200 Basic]).
- Open Runtime settings > Screensaver.
- Enable the screensaver checkbox.
- Set the activation time. The supported range is 5 minutes to 360 minutes, in 1-minute increments. For night-watch use, set the value to
1min is not possible - the lower bound is 5 min. Use a value of5minutes minimum. - If a value below 5 min is required (e.g., 1 min), it must be set at runtime via the system function
SetScreensaverTimeout, but the firmware will clamp to the configured lower bound of 5 min on some revisions. Verify on the target firmware.
Step 2: Disable Unneeded Loader Functions
- Navigate to HMI device > Security > Operator authorizations and assign a strong password for the
Operatorrole. - In Runtime settings > Services > Transfer, restrict the automatic transfer to a manual PIN entry only.
- Disable Allow remote access to Control Panel if not required for remote support.
Step 3: Compile and Transfer
- Right-click the HMI device and select Compile > Software (rebuild all).
- Connect to the panel via the configured channel (PN/DP or USB).
- Select Download to device > Software and configuration.
- When prompted, choose Replace the existing runtime and confirm with the project password.
Step 4: Runtime Adjustment via Script
For applications that need to enter night mode on a schedule (e.g., 19:00 local time) without operator intervention, schedule a system function in the Scheduler:
- Trigger: Daily, 19:00:00
- Function:
SetBrightness(note: this is a no-op on Basic panels, but is reserved for forward-port to Comfort panels if the fleet is heterogeneous) - Function:
SetScreensaverTimeoutwith tag value 5 - Companion schedule at 06:00:
StopScreensaverif any user input has not already done so
Why True Continuous Dimming Is Not Supported on Basic Panels
Three architectural constraints make continuous dimming infeasible without hardware change:
- Backlight driver topology. The LED string is driven by a constant-current boost converter. The current reference is set by a single resistor on the inverter PCB; the firmware has no DAC or PWM channel into the reference node.
-
Runtime tag surface. The WinCC Basic runtime image does not export a
Brightnesssystem tag. Functions likeSetBrightnessexist in the function catalog for source compatibility with Comfort panels, but on Basic panels the call returns immediately without effect (a known behavior documented in the WinCC Basic system manual, see Siemens Industry Online Support). - Optical stack calibration. The brightness/gamma curve is calibrated at the factory against a single current setpoint. Reducing the current without re-calibrating the gamma would shift the gray-scale response and cause UI text to become unreadable at low luminance. The Basic platform does not expose gamma correction registers to the user.
For a true continuously dimmable solution, specify a SIMATIC Comfort Panel (TP700 Comfort through TP2200 Comfort) or the legacy MP377 Touch daylight readable. Comfort panels expose SetBrightness with a 0-100 % range and support DALI-style preset scenes, and the MP377 daylight readable variant is designed for high-ambient bridge operation with a transflective LCD that remains readable in direct sunlight without maximum backlight.
Marine and Ship-Bridge Application Requirements
Ship bridge HMI design is governed by a layered set of standards. Continuous-dimming capability is not a soft preference - it is a night-vision requirement rooted in maritime regulations and human-factors standards:
| Standard / Class Rule | Scope | Night-Vision Requirement Summary |
|---|---|---|
| ISO 8468 | Ship and marine technology - Shipboard layout | Navigation bridge equipment shall not impair the dark adaptation of the watchkeeper; luminance of fixed displays shall be reducible. |
| IEC 61174 | ECDIS operational and performance requirements | Display brightness shall be adjustable down to a level that does not interfere with night vision. |
| IEC 60945 | Marine navigation and radio-communication equipment - General requirements | Includes environmental and luminous-intensity tests for bridge-mounted equipment. |
| IACS UR E22 | On-board use and application of programmable electronic systems | Test conditions for bridge-mounted displays, including dimming verification where applicable. |
For classed vessels (DNV, Lloyd's Register, Bureau Veritas, ABS), the bridge HMI specification must demonstrate that the watchkeeper can reduce display luminance to a level that does not impair dark adaptation. The screensaver-only approach on a Basic panel is, strictly, not a luminance reduction - it is a screen-off state. If the watchkeeper is required to maintain situational awareness by reading the panel intermittently, the screensaver activation interval of 5 minutes is far too long, and any touch to wake the screen will briefly flash the panel to full luminance. Both factors are problematic for the cited standards.
Recommendation: For classed-vessel bridge applications, specify the TP700 Comfort, TP900 Comfort, TP1200 Comfort, or TP1500 Comfort panel in the 6AV2 124-1xxxxx-xxxx part number range. These panels support continuous dimming via the SetBrightness system function and via the on-device Control Panel slider, both of which are accessible to the watchkeeper without an engineering download.
Field-Proven Workarounds When Only Basic Panels Are Available
When a retrofit is constrained to KTP Basic hardware (e.g., the existing cabinet cutout only accepts 7" or 12" Basic mechanicals, or the budget cannot absorb a Comfort panel upgrade), the following mitigations are in service on in-production vessels and should be considered:
- Neutral-density overlay film. A sheet of optically bonded neutral-density filter (ND2 to ND4) or commercial privacy/dimming film applied to the front of the panel reduces the emitted luminance by a fixed factor (50 % to 6.25 %). The reduction is non-electronic, non-dimming, but verifiable under IEC 60945. The film does not affect touch sensitivity if it is < 0.5 mm thick and is gapped at the bezel seal.
- Re-lamp the backlight with a lower-current string. Authorized service centers can replace the LED string with a lower-output equivalent (typically a -30 % or -50 % current resistor swap). This is a permanent, non-reversible change and is not field-configurable by the watchkeeper. Document the modification in the ship's Planned Maintenance System (PMS).
-
Schedule-driven project with aggressive timeout. Combine a 5-minute screensaver timeout with a scheduler task that calls
StopScreensaveronly on user input. The crew adapts to the touch-to-wake model. This is the cheapest mitigation and is acceptable for non-classed vessels or for panels that are not in the primary watchkeeper's primary line of sight. - External hardware dimmer in the DC supply. A PWM-controlled DC-DC converter in the 24 V supply line can dim the entire panel, including the backlight, by reducing the input voltage. This is an extreme measure: it violates the panel's input voltage tolerance (19.2 V to 28.8 V) and will cause the panel to reboot when the supply drops out of regulation. Not recommended for classed vessels.
Commissioning and Verification Procedure
After project download, perform the following verification sequence before handing the panel to the bridge crew:
- Loader verification. Reboot the panel. Confirm the loader appears within 30 s. Verify that the transfer password prompt is enabled.
- Runtime start. Confirm the configured start screen loads without errors. Check the diagnostic buffer (Control Panel > System > Diagnostics) for any non-zero entries.
- Screensaver activation. Set the screensaver timeout to the minimum value (5 min) in the project, transfer, then idle the panel. Confirm the black screen with the moving white square appears at exactly the configured interval.
- Touch-to-wake. Touch the screen during the screensaver state. Confirm the last active screen reappears without a full reload of the runtime.
- Schedule verification. If a Scheduler task is configured for night mode, advance the panel's internal clock to 18:59 and confirm the task fires at 19:00.
- Luminance measurement (if applicable). Use a calibrated luminance meter (e.g., Konica Minolta LS-150) at a fixed distance of 50 cm perpendicular to the screen. Record the luminance in cd/m^2. Compare against the bridge design specification. If a dimming mitigation is in place (overlay film, etc.), record the post-mitigation value.
Troubleshooting Matrix
| Symptom | Likely Root Cause | Diagnostic Step | Remediation |
|---|---|---|---|
| SetBrightness call returns no effect | Basic panel does not support continuous dimming | Check device article number against the table above | Accept limitation, use screensaver; specify Comfort panel for true dimming |
| Screensaver never activates | Touch activity keeps resetting the timer | Disable all scheduled touches; observe for 6 min | Reduce timeout to minimum, replace resistive touch overlay if worn |
| Screensaver activates too quickly | Timeout value set below 5 min in project | Read Runtime settings > Screensaver | Correct to 5 min minimum |
| Panel reboots when screensaver activates | 24 V supply below 19.2 V (brownout) | Measure supply at panel terminals under full load | Repair/replace supply; check for voltage drop in long cable runs |
| Touch wakes panel but screen flashes full white | LCD initialization sequence on wake; firmware behavior | Record with high-speed camera; cross-reference firmware release notes | Update to latest firmware for the panel; if unresolved, accept as a design limitation |
| Project password forgotten | Loader password lost | Service recovery via Siemens support with proof of ownership | Recover using the standard Siemens service procedure; document new password in PMS |
| Loader button disabled (cannot access Control Panel) | Operator authorization configured to hide loader | Check Security > Operator authorizations | Adjust visibility; transfer the corrected project |
Field Notes and Lessons Learned
Three practical observations from shipboard deployments of KTP Basic panels configured for night-mode operation:
- The screensaver touch-to-wake latency is non-trivial. On the KTP1200 Basic, the wake event takes approximately 2-3 seconds from touch to fully rendered screen. For a watchkeeper scanning the display at 30-second intervals, this latency is acceptable; for an operator reading live alarm data, it is not. If sub-second wake is required, the Comfort panel is mandatory.
- Resistive touch sensitivity is reduced by overlay film. If the neutral-density overlay mitigation is used, expect a calibration touch to be required on first use. The resistive digitizer does not register light touches through a thick film overlay. Crew training must include a recalibration step in the handover procedure.
- Loader access should be restricted at the operator level. On a classed vessel, the watchkeeper should not be able to reach the loader and modify transfer settings. Set the operator role to No access for the loader.
Cross-Reference: Related Siemens Documentation
- Siemens Industry Online Support - entry point for SIMATIC HMI manuals, firmware updates, and FAQs
- SIMATIC HMI device MP377 15" Touch daylight readable (WinCC flexible) operating instructions - reference for the only legacy HMI in this class with native dimming
- WinCC Basic system manual, sections on screensaver and runtime settings
- TIA Portal Help, section HMI device configuration > Runtime settings > Screensaver
Can the Siemens KTP400 Basic screen be dimmed at runtime?
No. The KTP400 Basic (and the 700/900/1200 Basic variants) does not support continuous backlight dimming in the WinCC Basic runtime. The backlight is driven by a fixed-current LED driver with no PWM control exposed to the runtime. Use the screensaver with a 5-360 minute timeout for night-mode operation, or specify a SIMATIC Comfort Panel for true dimming.
What is the minimum screensaver timeout on a KTP Basic panel?
5 minutes. The supported range in TIA Portal is 5 to 360 minutes, configurable in 1-minute increments under Runtime settings > Screensaver. Values below 5 min are clamped by the runtime on some firmware revisions.
Which Siemens HMI panel supports true continuous dimming for ship bridge use?
The SIMATIC TP700 Comfort, TP900 Comfort, TP1200 Comfort, and TP1500 Comfort panels support continuous dimming via the SetBrightness system function and the on-device Control Panel slider. For high-ambient bridge operation, the legacy MP377 15" Touch daylight readable (6AV6 644-1AB20-1NA0) has a transflective display readable in direct sunlight without maximum backlight.
Is the screensaver approach compliant with ISO 8468 or IEC 61174?
Strictly, no. ISO 8468 and IEC 61174 require that display luminance be reducible, not just blanked. The screensaver provides a near-zero-luminance state but the watchkeeper must touch to wake the panel, which briefly flashes full luminance. For classed vessels (DNV, Lloyd's Register, ABS, BV), specify a Comfort panel with continuous dimming to meet the standard.
How do I access the on-device Control Panel on a KTP Basic panel at runtime?
Press the Settings button (gear icon) on the loader screen, or invoke the OpenControlPanel system function from a configured button. The Control Panel is password-protected; the default loader passwords are 100 (administrator) and 200 (operator). Change these in TIA Portal under HMI device > Security > User administration.
Can the backlight be replaced with a lower-output LED string?
Yes, as a permanent service modification at an authorized Siemens service center. A lower-current resistor is fitted to the LED driver, reducing luminance by approximately 30 % or 50 % depending on the resistor value. This is non-reversible and must be documented in the ship's Planned Maintenance System. The watchkeeper cannot change the luminance after the modification.