The operator can ping the DOP-W127B, but a project upload reports ethernet cant be opened. Trying COM2 reports no response, and both Ethernet connectors appear to behave the same way. That combination points to transfer-session setup or interface selection, not proof of a failed network link or damaged project.
What is the screen telling you?
A successful ping answers one narrow question: an IP endpoint replied to an ICMP echo request. It does not prove that the project-transfer software can open its required application session, that the reply came from the intended HMI, or that the selected HMI interface accepts the requested operation.
| Observation or setting | Location | Diagnostic effect |
|---|---|---|
| Ping succeeds | Engineering computer | Confirms basic IP reachability to a responding device; it does not validate project transfer. |
ethernet cant be opened |
Transfer software | The Ethernet transfer path did not open. Check the selected computer adapter, target address, interface choice, routing, filtering, and transfer mode. |
no response |
COM2 attempt |
No valid serial response reached the software. This is a separate fault path from Ethernet. |
Boot Display: On |
System Settings | Describes startup display behavior; it does not establish Ethernet transfer availability. |
Blue LED Function Mode: Disabled |
System Settings | Controls the indicated LED function; it is not evidence that LAN communications are disabled. |
No CDC entry shown |
System Settings menu | Do not use an absent menu item as proof that Ethernet or COM2 must work. Diagnose each physical path from its own settings. |
This failure occurs before runtime tag processing. A tag, driver, or controller binding cannot cause the transfer client itself to fail to open Ethernet. Establish a project-transfer session first; troubleshoot tags and controller communications only after the project can be transferred or opened.
Which connection path should you test first?
The installation presents three candidates: LAN1, LAN2, and COM2. Test them independently. Switching between incomplete Ethernet and serial configurations creates multiple variables and hides the first failed layer.
| Approach | What it requires | What the present result proves | Recommendation |
|---|---|---|---|
LAN1 |
Correct HMI address, subnet path, computer adapter, transfer target, and an open application session | Ping works, but the transfer session does not open | Test first with an isolated, known network path |
LAN2 |
The same checks performed specifically for the second connector and its configured address | The same reported symptom occurred | Test only after documenting the LAN1 result |
COM2 |
Matching physical interface, wiring, serial format, station selection, and transfer support |
no response identifies no valid reply, not the reason for it |
Use after Ethernet isolation, unless the serial configuration is already known |
LAN1 and LAN2 are both valid diagnostic candidates, but neither should be treated as a transparent substitute for the other. The recommended approach is to validate one Ethernet connector from end to end, then repeat the identical sequence on the other connector. This produces comparable results and reveals an interface-specific configuration error.
Why does ping work while project upload fails?
Ping and project transfer operate at different layers. Ping can succeed while the transfer application is pointed at the wrong network adapter, follows an unintended route, is blocked by host security controls, targets a duplicate IP address, or cannot establish the HMI transfer service session.
First confirm identity, not merely reachability. Disconnect the HMI Ethernet cable and ping the same address again. A continuing reply identifies another device or route answering at that address. If replies stop, reconnect the selected HMI connector and continue.
Next inspect the engineering computer's active adapters and route to the target address. Disable unrelated paths temporarily where site policy permits, or explicitly select the adapter used for the HMI network. A wireless, VPN, virtual-machine, or secondary wired interface can carry the ping differently from the transfer client's selected interface.
Host firewall or endpoint security can also distinguish between ICMP and application traffic. Test under the site's approved diagnostic policy, and restore protection after the comparison. Do not guess a TCP or UDP port number; read the transfer software or product documentation for the required service and inspect the blocked-event log for the actual executable and traffic.
How should LAN1 and LAN2 be tested separately?
- Record the current IP address, subnet mask, gateway entry, selected transfer model, and computer network adapter. Capture the settings before changing them.
- Connect only
LAN1. RemoveLAN2from the test path so that link indication and traffic belong to one connector. - Confirm that the computer address belongs to the intended subnet and does not duplicate the HMI address. Use the configured subnet mask for the comparison rather than assuming an address class.
- Ping the HMI address, then disconnect
LAN1and repeat the ping. The response must disappear when the target is disconnected. - Reconnect
LAN1. In the project-transfer software, select the DOP-W127B target and enter the address assigned to that interface. Bind the transfer operation to the computer adapter on the same test network if the software provides that choice. - Attempt the project upload and record the exact message and time. If it still reports
ethernet cant be opened, inspect local firewall, endpoint-security, and route diagnostics at that time. - Disconnect
LAN1, connect onlyLAN2, and repeat every step with the address and settings assigned toLAN2. Do not carry an assumedLAN1address into theLAN2test.
If both connectors pass identity and routing checks but fail at the same transfer-opening stage, focus on the transfer software configuration, selected HMI target, computer adapter, host filtering, and HMI transfer state. Two identical errors do not by themselves prove two defective Ethernet ports.
Why does COM2 report no response?
COM2 is an independent serial path. A no response result can arise from the wrong physical interface, incorrect transmit/receive wiring, missing signal reference, mismatched serial format, wrong station selection, or using a port role that does not accept the requested transfer operation.
- Read the configured electrical interface and communication format from the HMI settings or retained project. Do not infer them from the connector label alone.
- Compare the cable pinout with both endpoint definitions. Check signal direction and reference conductors with power removed where required by the equipment procedure.
- Configure the engineering interface to match the recorded serial format and target selection.
- Monitor transmit and receive activity during one request. Transmit with no receive activity directs the check toward wiring, interface type, HMI port role, or target selection. Receive activity with rejected frames directs it toward mismatched communication settings.
The missing CDC menu item does not resolve any of these checks. Use the functions actually exposed by the installed HMI configuration and software combination.
How do you verify the fix without creating another fault?
Do not use firmware updating as the first connectivity test. Firmware work writes to the device and can introduce a second problem while the original transfer path remains unresolved. First obtain a repeatable project-transfer connection with the existing configuration.
| Verification | Pass condition |
|---|---|
| Target identity | Ping replies stop when the tested HMI cable is disconnected and return when it is reconnected. |
| Interface isolation | Results are recorded separately for LAN1 and LAN2. |
| Transfer opening | The software progresses beyond ethernet cant be opened and establishes the device session. |
| Project upload | The upload completes and the resulting project opens without a transfer interruption. |
| Repeatability | A second connection attempt succeeds through the same adapter, connector, and target address. |
After access is restored, compare the uploaded project's communication configuration with the live tag, driver, and controller path. The tag can be correct while its driver or device binding points elsewhere. Verify runtime values only after the transfer layer remains stable.
FAQ
Why does my DOP-W127B ping but not upload?
Ping validates an ICMP reply, while upload requires the transfer application to open its own session. Confirm target identity, the selected computer adapter, the HMI interface address, routing, and host filtering.
Why does the DOP-W127B show ethernet cant be opened?
ethernet cant be opened means the transfer path did not open; it does not identify a bad cable by itself. Test one LAN connector at a time and inspect adapter selection, routes, duplicate addressing, and blocked application traffic.
Why do LAN1 and LAN2 give the same transfer error?
A shared software selection, computer route, firewall rule, target address, or HMI transfer state can affect both tests. Repeat the full procedure separately for LAN1 and LAN2 using each interface's recorded settings.
Why does COM2 return no response?
no response means no valid serial reply arrived. Check the configured electrical interface, cable pinout, signal reference, communication format, station selection, and whether COM2 accepts that transfer operation.
How do I confirm the DOP-W127B transfer problem is fixed?
Complete a project upload, open the retrieved project, then repeat the connection through the same computer adapter, HMI connector, and target IP address. The final pass condition is a second successful transfer session without ethernet cant be opened.