ET200S vs ET200SP: Selecting Distributed I/O for S7-1200 PROFINET

David Krause15 min read
I/O ModulesSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The SIMATIC ET200S and SIMATIC ET200SP are two generations of modular, IP20 distributed I/O systems designed for cabinet-mounted operation behind a SIMATIC controller. Both are PROFINET-capable, both connect as I/O devices to an S7-1200 CPU such as the 6ES7214-1AG40-0XB0 (CPU 1214C DC/DC/DC), and both expose the same logical channel image to the controller through a GSD file imported into TIA Portal. They differ in mechanical footprint, power structure, diagnostic depth, module catalog, and lifecycle status.

The ET200S is the legacy platform; the ET200SP is the current platform and the recommended choice for new machines. Both are still maintained for spare-part and migration scenarios, but new projects should be specified against the ET200SP catalog. The product overview PDF from Siemens (re-hosted on the Digi-Opus catalog portal) summarizes the position:

SIMATIC ET 200SP Catalog and Overview (PDF) — "a multi-functional and finely scalable distributed I/O system ... about 50% narrower than" the prior generation.

System Architecture: ET200S

The ET200S is built around a backplane that accepts one Interface Module (IM) followed by a stack of I/O modules terminated by a terminating module. The IM is the only fieldbus gateway in the station; everything downstream is backplane I/O. Key architectural properties:

  • IM variants: PROFIBUS IM151-1 (6ES7151-1BA02-0AB0), PROFINET IM151-3 PN (6ES7151-3BA23-0AB0), and PROFINET IM151-3 PN HF (high-feature, 6ES7151-3BA23-0AB0 family) — verify the exact order suffix in the current Siemens Online Help for your firmware target.
  • Power structure: PM-E power modules feed 24 V and load-voltage into the backplane. The PM-E sits after the IM and before any digital output or analog output modules that require a separate load group.
  • Channel density: Standard DI/DO modules are 15 mm wide with up to 4 or 8 channels; analog modules are 15-25 mm wide.
  • Configuration: Each module position is fixed; modules are inserted left-to-right with a terminator at the end of the rack.

System Architecture: ET200SP

The ET200SP replaces the screw-in ET200S backplane with a click-in BaseUnit system. Every I/O module plugs onto a BaseUnit (BU), and the BaseUnit carries the backplane contacts and the load-voltage distribution.

  • IM variants: IM155-6 PN ST (standard, 6ES7155-6AU01-0BN0), IM155-6 PN HF (high-feature, supports shared device, MRP, MRPD, isochronous mode, 6ES7155-6AU00-0BN0), IM155-6 PN BA (basic, lower-cost, fewer slots), and PROFIBUS IM155-6 DP ST (6ES7155-6BA00-0BN0). Confirm the firmware version required for the desired PROFINET conformance class.
  • BaseUnits (BU): Type A0 (no AUX terminal, no voltage group feed-through), Type A1 (AUX terminal, no feed-through), Type B0 (new load group, feed-through), Type B1 (new load group + AUX). The baseunit type controls how 24 V and load voltage are routed between adjacent modules.
  • Channel density: Standard digital modules are 15 mm wide with 8 or 16 channels; analog modules are 15 mm wide; the overall station is approximately 50% narrower than the equivalent ET200S station.
  • Color-coded labeling: Each module uses a color code on the slot and on the side of the module (CCxx) to prevent wrong-insertion; the BU label set is also color-coded by voltage group.

ET200S vs ET200SP Feature Comparison

Feature ET200S ET200SP
Status Legacy, phase-out announced for some IM variants Current platform
Footprint per station Reference baseline Approx. 50% narrower than ET200S
Module interface Screw-in / clamp-in backplane Click-in onto BaseUnit
Power distribution PM-E power modules inserted in rack BaseUnit type A0/A1/B0/B1 controls load groups
Max modules per station Up to 63 modules (IM-dependent) Up to 64 modules (IM-dependent); HF IM supports larger configs
Digital I/O channel density 4 or 8 channels per module (15 mm) 8 or 16 channels per module (15 mm)
Analog I/O 2-4 channels per module 2-4 channels per module; F-variant AQ supports higher accuracy
PROFINET IM family IM151-3 PN / IM151-3 PN HF IM155-6 PN BA / PN ST / PN HF
PROFIBUS IM family IM151-1 / IM151-1 HF IM155-6 DP ST
Shared device support HF variant only HF variant only
Isochronous mode (IRT) HF variant, restricted HF variant, full IRT class 3 with PROFINET V2.3+
Diagnostic detail Channel-level via standard PN diagnostics Channel-level + value status (QR/QI) + isochronous diagnostics
Hot-swap modules Limited (HF) Yes, all modules hot-swappable without station stop (HF IM)
Firmware update Via TIA Portal / SIMATIC Automation Tool Same; HF IM supports runtime firmware update
Energy metering module Not natively available AI Energy Meter ST / HF (400 V AC measurement)
Motor starter / F-CM modules Direct-on-line, reversing, FOC starters as separate modules Direct-on-line and reversing starters; F-CM contactor modules for safety
Fail-safe (PROFIsafe) modules Selected F-modules in catalog Selected F-modules in catalog
Typical spare-part availability horizon Limited; verify in Siemens Product Lifecycle portal Active

S7-1200 CPU 1214C Compatibility

The S7-1200 CPU 1214C is a PROFINET IO Controller with a single PROFINET port on the CPU body. The PROFINET port on the CPU is the only network interface available for connecting PROFINET IO devices; there is no integrated PROFIBUS port and no PROFIBUS module add-on for the S7-1200. Therefore, when connecting ET200S or ET200SP, the choice of fieldbus is effectively PROFINET.

  • CPU 1214C PROFINET variant (firmware V4.x and later) acts as PROFINET IO Controller per IEC 61158 / PROFINET specification, conformance class A; the PROFINET port supports real-time class 1 (RT) and, with CPU firmware V4.2 and TIA Portal V14 SP1+, real-time class 2/3 (IRT) where the IO device supports it.
  • Direct-attach architecture: Both ET200S and ET200SP are wired directly to the CPU's PROFINET port via a managed or unmanaged switch. A typical cabinet topology uses a SCALANCE XC switch between the CPU and one or more I/O stations.
  • Maximum IO devices: The CPU 1214C supports up to 16 PROFINET IO devices. Both ET200S and ET200SP count as a single IO device each, regardless of slot count.
  • Device configuration in TIA Portal: IM155-6 PN ST and IM155-6 PN HF are imported via GSDML file; the IM155-6 PN BA is supported natively in TIA Portal V14 SP1 and later without an external GSD import. ET200S IM151-3 PN modules are similarly imported through GSDML or selected from the catalog if the HSP is installed.
CPU firmware requirement: ET200SP HF features such as shared device, MRP client, and IRT class 3 require CPU 1214C firmware V4.2 or higher. If you plan to use a CPU 1214C DC/DC/DC with firmware V4.0 for ET200SP basic features only, no firmware update is required.

Interface Module (IM) Selection

The IM is the gateway between the fieldbus (PROFINET or PROFIBUS) and the backplane. Choose based on the fieldbus, the required feature set, and the available firmware on the CPU.

Family IM Order Number Fieldbus Feature Set Recommended Use
ET200SP IM155-6 PN BA 6ES7155-6AU30-0BN0 family PROFINET Basic, RT only, max 12 slots Cost-optimized small stations
ET200SP IM155-6 PN ST 6ES7155-6AU01-0BN0 PROFINET RT, IRT, MRP, up to 64 slots Standard PROFINET ET200SP
ET200SP IM155-6 PN HF 6ES7155-6AU00-0BN0 PROFINET ST + shared device + isochronous + larger config Motion / Safety / shared device
ET200SP IM155-6 DP ST 6ES7155-6BA00-0BN0 PROFIBUS DP-V0/V1 DP slave, up to 32 slots Legacy PROFIBUS retrofit (not for CPU 1214C)
ET200S IM151-3 PN 6ES7151-3BA23-0AB0 PROFINET RT, basic diagnostics Existing ET200S stations
ET200S IM151-3 PN HF 6ES7151-3BA23-0AB0 family PROFINET Shared device, expanded diagnostics Existing ET200S stations with shared device
Order numbers above are based on the public Siemens Online Help and catalog. Always confirm against the live Siemens Product Master and the Product Lifecycle status portal before procurement; some suffixes (BN0 vs BP00 vs AR00) vary by region and release.

I/O Module Catalog Highlights

Both platforms share the same channel-level interface to the S7-1200 (process image, value status, channel diagnostics). The catalog however differs.

Module Class ET200S Examples ET200SP Examples
Digital Input 6ES7131-4BDx1 (8 DI, 24 V DC, 15 mm) 6ES7131-6BFx1 (8 DI, 24 V DC, type 1/3), 6ES7131-6BHx1 (16 DI)
Digital Output 6ES7132-4BDx1 (8 DO, 24 V DC / 0.5 A) 6ES7132-6BFx1 (8 DO, 24 V DC / 0.5 A), 6ES7132-6BHx1 (16 DO)
Analog Input 6ES7134-4FByx (4 AI, ±10 V / 0-10 V / 4-20 mA) 6ES7134-6GFx1 (4 AI, ±10 V / 4-20 mA), 6ES7134-6HDx1 (8 AI)
Analog Output 6ES7135-4FByx (4 AO) 6ES7135-6GFx1 (4 AO), 6ES7135-6HE0x (8 AO, HF)
Relay Output 2 DO relay module Available as RQ module (2-channel) — select appropriate BU type
Technology Counter, SSI, IO-Link, pneumatic valve modules IO-Link master (4-port), FCM contactor, energy meter, motor starter

The ET200SP catalog is the active catalog and continues to receive new modules; the ET200S catalog is in maintenance. For new builds, prefer the ET200SP catalog unless a legacy module type is required.

PROFINET Topology and Cabling

Wiring between the CPU 1214C PROFINET port and the ET200S/ET200SP IM uses standard RJ45 patch cabling. Use Cat 5e or higher, industrial-grade, with M12 D-coded connectors at the cabinet cable entry for vibration-tolerant installations.

  • Star topology: Each IM connects to a port on a managed switch (e.g., SCALANCE XC206-2SFP). The CPU 1214C and the switch sit on the same subnet. This is the most common topology for cabinet-internal wiring.
  • Linear topology: ET200SP IM155-6 PN ST and HF support the PROFINET device as a 2-port switch; you can daisy-chain them. The ET200S IM151-3 PN variants also act as 2-port switches in linear topology. Linear is convenient for distributed cabinets but requires all devices to be PROFINET conformant.
  • MRP / MRPD: Use Media Redundancy Protocol only with a managed switch acting as MRP manager. IM155-6 PN HF supports MRPD (seamless redundancy) for high-availability lines.
  • Cable length: Up to 100 m between two devices per PROFINET specification; copper only. For longer distances use SCALANCE media converters or fiber modules (SFP).

TIA Portal Configuration Procedure

Configure both ET200S and ET200SP as PROFINET IO devices under the CPU 1214C in TIA Portal. The procedure is similar; the differences are in catalog selection and slot counts.

  1. Add CPU 1214C to the project from the device catalog. Match the firmware version to the CPU's actual firmware (read from the CPU's online diagnostics under "Online & Diagnostics" > "Identification").
  2. Open the PROFINET port on the CPU (X1) in the device view. Confirm the IP address (default 192.168.0.1, mask 255.255.255.0) and device name (default s7-1200). Device name must be unique on the subnet for PROFINET LLDP discovery.
  3. Install the matching HSP (Hardware Support Package) for ET200SP from the Siemens Support site (entry ID 109751706 is the consolidated TIA Portal HSP collection; verify the latest in your TIA Portal installation). For ET200S, the older HSP is required if your TIA Portal is V14+.
  4. Add the IM from the catalog (Devices & Networks > Network view > drag the IM into the rack view). The IM appears as a new IO device. Connect its PROFINET port to the CPU PROFINET port. TIA Portal assigns an IP and a device name.
  5. Populate the station by dragging I/O modules from the catalog into the IM's rack in the same slot order as the physical build. The first slot after the IM is slot 1; the BaseUnit or backplane slot number is fixed.
  6. Set the device name on the IM physically via TIA Portal "Assign PROFINET device name" or via PRONETA / Topology Editor. The device name must match the configured name exactly, including case.
  7. Compile and download the hardware configuration to the CPU. The CPU will establish PROFINET AR (application relationship) to each IM; the IM will then negotiate slots.
  8. Verify in the Online & Diagnostics view that the IO device status is "OK" and that each module reports "No fault".
Name resolution gotcha: A frequent fault on commissioning is the IM not coming online. Check (a) the device name matches the TIA Portal configuration, (b) the IM is on the same subnet, (c) any managed switch is not blocking LLDP multicast, and (d) the topology editor connections agree with the physical cabling if topology rules are enforced.

Hardware Configuration Rules

  • Slot rules — ET200S: Maximum slot count depends on the IM. PM-E power modules occupy slots like any other module but are not addressable; they configure the load group. End the rack with a 6ES7193-4JA00-0AA0 terminating module.
  • Slot rules — ET200SP: Maximum slot count depends on the IM: BA = 12, ST = 32, HF = 64. Insert a server module (6ES7155-6AU00-0CN0 family) in the last slot to terminate the backplane and hold the cover. The first BaseUnit must be type A0 or A1 (after the IM) unless your configuration requires a B-type in slot 1; the BU type after that controls whether the next module is in the same load group.
  • Load group sizing: Each load group can source up to 10 A continuous on the load-voltage rail; verify the digital output module's total continuous current against this limit. For ET200SP use BU type B0/B1 to start a fresh group.
  • Derating: Both platforms require derating above 40 °C horizontal mounting or 50 °C vertical mounting. Derate analog modules per module datasheet; digital output modules typically derate to 0.5 A at 60 °C.

Migration: ET200S → ET200SP

Migration is usually driven by spare-part availability or by a desire to consolidate onto the current platform. It is mechanical and electrical work, plus software re-work.

  1. Inventory the existing ET200S rack: Capture module order numbers, slot positions, and the IO addresses in the S7-1200 project. Export the S7-1200 hardware configuration from TIA Portal.
  2. Map each ET200S module to its ET200SP equivalent. For most DI/DO and AI/AO modules there is a direct replacement in the ET200SP catalog. For specialty modules (e.g., 1Count24V, SSI, old pneumatic valve modules) verify availability; some legacy types were not migrated.
  3. Plan the cabinet layout: The ET200SP rack is approximately 50% narrower, so the new station will fit a shorter DIN section. You may need to relocate the existing station.
  4. Select the IM: Replace IM151-3 PN with IM155-6 PN ST (typical) or HF (if shared device or isochronous was used). Re-import the new GSDML file into TIA Portal.
  5. Rewire power: ET200S used PM-E power modules; ET200SP uses BU type B0/B1 to define load groups. Re-wire the load-voltage feed and AUX terminal to the new BUs.
  6. Re-assign addresses: ET200SP module I/O addresses are configurable per slot. Reassign to match the original S7-1200 program addresses if possible, otherwise update the program to the new addresses.
  7. Download and verify: As in the TIA Portal configuration procedure above.

Troubleshooting Matrix

Symptom Likely Root Cause Diagnostic Fix
IM does not appear in TIA Portal online view Device name mismatch Online & Diagnostics > Ethernet > Assign device name Reassign device name from TIA Portal to match configured name
IM reports "Station failure" Missing or wrong GSDML; module inserted at wrong slot Compare physical rack with TIA Portal rack view Reimport correct GSDML; correct slot mismatch
Digital output module does not energize load Missing load voltage / wrong BU type Measure 24 V at load terminals; check BU color code Use BU type B0/B1 to feed load voltage; check PM/PSU capacity
Analog input reads zero or full scale Wire break or sensor not powered Module diagnostics buffer; value status (QR) bit Check sensor supply and shield; verify wiring against module data sheet
Module reports "Parameter assignment error" Configuration mismatch Module diagnostics > channel diagnostics Match measurement range (e.g., 4-20 mA vs 0-10 V) and diagnostic enable bits
CPU PROFINET port shows "IO controller fault" Subnet misconfigured; LLDP blocked Online & Diagnostics > PROFINET diagnostics Confirm same subnet, no VLAN mismatch, allow LLDP on switch
IO device disconnects intermittently MRP not configured / cable noise / grounding issue Topology view with port statistics Enable MRP or fix grounding; replace damaged patch cable
Module hot-swap does not reconnect IM does not support hot-swap or function is disabled IM155-6 PN ST/HF supports hot-swap; BA does not Upgrade IM to ST or HF; enable hot-swap in IM configuration

Selection Recommendations

  • New machine build: Specify ET200SP with IM155-6 PN ST as default. Add IM155-6 PN HF only if shared device, isochronous, or MRPD is required.
  • Cost-optimized small station (≤12 slots, RT only): IM155-6 PN BA is appropriate.
  • Existing ET200S station, no spare parts available: Plan a migration; do not stock new ET200S modules long-term.
  • PROFIBUS only available on a legacy line: Stay on ET200S (IM151-1 DP). For a new PROFIBUS station the ET200SP IM155-6 DP ST can be considered, but on the CPU 1214C path PROFINET is the only fieldbus option.
  • Motion / isochronous / Safety: ET200SP IM155-6 PN HF with F-modules in the ET200SP catalog. CPU 1214C supports PROFIsafe via the IO device, not via the local CPU.

Verification Checklist

  1. CPU 1214C PROFINET port link LED is green; the port speed autonegotiates to 100 Mbit/s full duplex (PROFINET requirement).
  2. IM reports its assigned PROFINET device name and IP via TIA Portal online view; the device's MAC address matches the physical label.
  3. Every slot in the IM's TIA Portal configuration matches a physically inserted module of the same order number and firmware version.
  4. Each output channel can be forced in TIA Portal and the corresponding field voltage is present at the load terminal.
  5. Each input channel toggles when the field device is actuated and the corresponding bit in the process image reflects the change within the configured update time.
  6. Diagnostic buffer on the IM contains no entries after the station has been operating under load for at least one hour.
  7. Power group current draw on each BU type B0/B1 load group is below the 10 A continuous limit; verify with a clamp meter on the load feed.

References (linked inline)

Documentation references cited in this article:

Is the S7-1200 CPU 1214C compatible with both ET200S and ET200SP?

Yes. The CPU 1214C with PROFINET (firmware V4.x or higher) is a PROFINET IO Controller and supports both ET200S IM151-3 PN and ET200SP IM155-6 PN variants as PROFINET IO Devices. The CPU has no PROFIBUS port, so only the PROFINET IM variants of ET200S and ET200SP are applicable.

Which IM should I choose for an ET200SP station on CPU 1214C?

For a standard station, choose IM155-6 PN ST (6ES7155-6AU01-0BN0). For shared device, isochronous mode, or MRP/MRPD, choose IM155-6 PN HF (6ES7155-6AU00-0BN0). For cost-optimized small stations of up to 12 slots, IM155-6 PN BA is sufficient.

How many ET200SP or ET200S stations can I attach to a CPU 1214C?

The CPU 1214C supports up to 16 PROFINET IO Devices. Each ET200S or ET200SP station counts as one IO Device regardless of slot count. The total number of slots across all IO Devices is bounded by the CPU's process image size; verify in the TIA Portal "Number of IO devices / submodules" device configuration screen.

Does the ET200SP require a server module?

Yes. The ET200SP rack is terminated by a server module inserted in the last occupied slot. The server module closes the backplane and supports the right-side end cover. It is mandatory; without it the IM will report a station configuration error.

Can I migrate from ET200S to ET200SP without rewriting the S7-1200 program?

If you reuse the same I/O addresses in the ET200SP rack, the existing program references will continue to work. Re-map the module order numbers in the TIA Portal hardware configuration and re-import the GSDML; reassign the I/O addresses per slot so they match the original symbolic addresses in the program.

Back to blog