The board connects while the PC uses automatic IPv4 configuration, then disappears when the PC is changed to 192.168.1.200. The static PC address changes the Layer 3 path; the board must also have a unique address that falls within the same subnet under the selected subnet mask. A proposed board address is 192.168.1.201, provided that address is unused.
Address plan and prerequisites
Before anything else, confirm the device identity. The supplied information uses both “Konga” and “Kogna.” Check the label or configuration utility and use the exact product selection shown there; the naming difference does not change the IPv4 procedure.
| Component | Required setting | Candidate address | Acceptance check |
|---|---|---|---|
| Control PC | Manual IPv4 | 192.168.1.200 |
The active Ethernet adapter displays this address |
| Board | Manual IPv4 | 192.168.1.201 |
The address is unused and saved in the board |
| Both endpoints | Matching subnet definition | Use the same subnet mask | Each endpoint classifies the other address as local |
The last octet alone does not prove that two addresses share a subnet. The configured subnet mask makes that decision. Read the mask used by the working automatic configuration or obtain it from the network address plan, then apply the same mask to both endpoints. A default gateway is not the path between two devices that classify each other as local; the gateway matters only when traffic must leave the local subnet.
- Record the PC address, subnet mask, gateway, and board address while automatic configuration still works.
- Check that
192.168.1.200and192.168.1.201are not already assigned to other devices. - Identify the physical Ethernet adapter connected to the board or its switch.
Do not move on until the working configuration is recorded and both proposed addresses are unique.
Temporary restoration of board access
The board cannot be readdressed through a path that the PC can no longer reach. Restore the last working PC mode before changing the board.
- Return the connected Ethernet adapter to automatic IPv4 configuration.
- Reconnect to the board using the same application and cabling that worked previously.
- Open the board’s network configuration and record its current address mode, IPv4 address, and subnet mask.
- Confirm that the application is communicating with the intended physical board before writing any setting.
Automatic operation proves that the Ethernet link and application can work together, but it does not prove that 192.168.1.200 is compatible with the board’s current subnet. Changing only the PC can place the endpoints in different logical networks even though the cable and link indicators remain normal.
Do not move on until the board is accessible again and its current network values have been captured.
Board static IPv4 assignment
Assign the board a fixed address before placing the PC permanently at its required address. The proposed pair keeps the endpoints distinct: PC 192.168.1.200 and board 192.168.1.201.
- Verify once more that
192.168.1.201is unused. An address conflict can produce intermittent communication, unexpected disconnects, or traffic reaching the wrong device. - Select the board’s manual or static IPv4 mode in its configuration interface.
- Enter
192.168.1.201as the board address. - Enter the subnet mask selected from the working configuration or approved network plan.
- Apply or save the configuration. Expect the current session to drop if the address changes immediately.
- If the board stores network settings persistently, use the interface’s normal commit operation before removing power.
Do not copy a gateway value merely to make the fields look complete. For direct local communication, the decisive values are the two unique IPv4 addresses and the matching subnet definition. If the board requires a gateway field, enter the value defined by the network plan.
Do not move on until the board reports 192.168.1.201 or the saved configuration can be read back.
PC static IPv4 assignment
Configure only the adapter that physically carries board traffic. Editing a wireless, virtual, or disconnected adapter leaves the real Ethernet path unchanged.
- Open the IPv4 properties of the active Ethernet adapter.
- Select manual addressing and enter
192.168.1.200. - Enter the same subnet mask used for the board.
- Enter gateway and name-server values only when required by the wider network design; they are not needed to select a directly connected local board.
- Apply the settings, then read the adapter status back to confirm that
192.168.1.200is active.
Check for another active adapter with an overlapping route to the same address range. Wireless connections, virtual-machine adapters, VPN clients, and secondary Ethernet ports can cause the operating system to choose an unintended interface. Temporarily disabling an unrelated overlapping path is a valid diagnostic step, but preserve its original settings so it can be restored.
Do not move on until the connected adapter shows 192.168.1.200 with the intended subnet mask.
Layered connection checks
Test the path below the control application first. Application discovery can depend on broadcast traffic, adapter selection, or firewall policy, while direct communication uses the board’s assigned address.
| Observed symptom | Check | Corrective action |
|---|---|---|
| No Ethernet link | Cable, connector, switch port, and adapter state | Restore the physical link before changing addresses |
| Link present, board unreachable | PC address, board address, and subnet masks | Correct the mismatched subnet or duplicate address |
| Direct reachability works, discovery fails | Application adapter selection and firewall treatment | Select the board-facing adapter or permit the required discovery traffic |
| Connection reaches an unexpected device | Address uniqueness | Remove the duplicate and assign a free address |
| Works until restart | Saved versus temporary board configuration | Commit the static setting using the board interface |
- Confirm the physical link on both ends.
- Run the operating system’s normal reachability test against
192.168.1.201. - If that fails, inspect whether the PC resolves a hardware address for
192.168.1.201. Failure at this stage points to link, subnet, duplicate-address, or board-configuration problems rather than application logic. - If direct reachability succeeds, configure the control application to target
192.168.1.201explicitly when it provides a manual-address option. - If manual targeting works but discovery does not, inspect application adapter binding and firewall policy without changing the endpoint addresses again.
Do not move on until the PC reaches 192.168.1.201 independently of automatic discovery.
End-to-end verification
- Connect the application to the board at
192.168.1.201. - Confirm that the application identifies the intended board and can perform the required control operation.
- Disconnect and reconnect the application to prove that the address is repeatable.
- Restart or power-cycle the board through the normal commissioning procedure, then verify that it returns at
192.168.1.201. - Confirm that the PC remains at
192.168.1.200and that communication works without returning either endpoint to automatic configuration.
FAQ
How do I connect the board after setting my PC to 192.168.1.200?
Assign the board a unique address in the same subnet, such as 192.168.1.201, and apply the same subnet mask to both endpoints. Confirm that 192.168.1.201 is unused before saving it.
How do I change the board address when I can no longer connect?
Temporarily return the board-facing PC adapter to the automatic mode that previously worked. Connect to the board, save 192.168.1.201 with the correct subnet mask, and then restore the PC to 192.168.1.200.
How do I diagnose discovery failure when direct communication works?
Select the correct Ethernet adapter in the application, check for overlapping wireless, VPN, or virtual-adapter routes, and inspect firewall handling of discovery traffic. Keep the working static addresses unchanged while testing the application layer.
How do I verify that the static board address is permanent?
Read back 192.168.1.201, reconnect the application, restart the board through the normal commissioning procedure, and complete the final control test from the PC at 192.168.1.200.