Fix SFC Interconnection Cannot Be Moved Error in TIA Portal

David Krause16 min read
SiemensTIA PortalTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Fix SFC Interconnection Cannot Be Moved Error in TIA Portal

The error message "The SFC interconnection cannot be moved to this connection" is raised by the TIA Portal (STEP 7) editor when an engineer performs an Alt+drag-and-drop operation to relocate an existing Sequential Function Chart (SFC) access from one block input/output to another and the proposed target fails the editor's internal validation. This article documents both root causes observed in field service work, the diagnostic workflow to identify which one applies, and the resolution steps to complete the move without losing the SFC linkage semantics.

Platform context: The error message, the reserved names "Interlocked" / "Not interlocked," and the "0" / "Run" sequencer state tokens are specific to Siemens S7 GRAPH running inside TIA Portal (V15 and later). The diagnostic workflow below applies to S7-300, S7-400, and S7-1500 targets. For third-party SFC implementations (CoDeSys 3, Beckhoff TwinCAT, Allen-Bradley Connected Components Workbench), the message text differs but the underlying type/semantic mismatch causes are equivalent.

1. Problem Description

The error is triggered by the following editor sequence:

  1. An SFC step, transition, interlock, or supervision already has an access bound to a boolean block input (for example "Conveyor_FB".ModLiOp where ModLiOp is a BOOL input).
  2. The engineer selects the SFC access on the interconnection line in the S7 GRAPH editor or the SFC view.
  3. While holding the Alt key, the engineer drags the access to a different block input/output (for example "Conveyor_FB".SP_Ext).
  4. TIA Portal runs a type check and a semantic check on the proposed target.
  5. If either check fails, the editor displays the message and aborts the move. The original interconnection is preserved.

The error is editor-side only; no download is required to trigger it. It is raised in both the offline and online views of the project. In German-localized installations the same message reads "Die SFC-Verschaltung kann auf diese Verbindung nicht verschoben werden."

2. SFC Interconnection Architecture in TIA Portal

Siemens TIA Portal exposes two SFC implementations:

Implementation Target Hardware Feature Set
S7 GRAPH S7-300 / S7-400 / S7-1500 (with limitations) / ET 200S CPU Full: steps, transitions, interlocks, supervisions, actions, qualifiers, manual/auto modes
Basic SFC (IEC 61131-3) S7-1500, ET 200SP CPU Steps, transitions, actions only — no interlock/supervision concept

An SFC interconnection is the binding between an SFC element (transition, interlock, supervision, action qualifier) and the boolean tag or block parameter that supplies the value at runtime. The SFC evaluation cycle samples the bound boolean on every scan and interprets it according to the assignment mode stored in the SFC metadata.

For S7 GRAPH, the assignment mode is one of two reserved semantics:

  • Interlocked — the condition is ACTIVE when the bound boolean equals TRUE (1).
  • Not interlocked — the condition is ACTIVE when the bound boolean equals FALSE (0).

These are not the same as binding the literal constants TRUE or FALSE. The SFC engine stores the assignment mode as a separate attribute of the step/transition and consults it during evaluation. This distinction is the source of one of the two root causes discussed below.

3. Root Cause 1 — Data Type Mismatch

The most common cause of the error is a data type mismatch between the original SFC access and the proposed target. TIA Portal enforces strict type compatibility because the SFC evaluation engine always reads the bound value as a BOOL.

3.1 Typical Scenario

A function block exposes two parameters:

Parameter Data Type Purpose
ModLiOp BOOL Manual operating mode signal
SP_Ext REAL External setpoint (analog value)

The SFC transition was originally bound to ModLiOp (BOOL). During refactoring the engineer attempts to move the access to SP_Ext (REAL). TIA Portal detects the mismatch and rejects the move. The original message "The SFC interconnection cannot be moved to this connection" is displayed.

3.2 Why the Editor Rejects the Move

If the move were allowed, the SFC evaluation engine would attempt a non-boolean comparison at runtime. The resulting behavior depends on the CPU family and firmware:

  • S7-300 / S7-400: implicit conversion of REAL to BOOL is not defined for transitions; the SFC fault bit is set and the affected step enters the error state.
  • S7-1500 with strict type checking (default since firmware V2.0): the SFC block fails to compile, or the OB1 cycle raises a Type Conflict error and the CPU enters STOP.
  • S7-1500 with permissive type checking: the conversion is performed as BOOL := (REAL <> 0.0), which is almost never the intent of the original logic.

TIA Portal blocks the move at editor time to prevent these runtime faults. The validation is performed against the IEC_Type field of the source and target block interfaces, not against runtime values.

3.3 Detecting the Mismatch

Open both block interfaces:

  1. In the project tree, right-click the source FB instance → Open.
  2. In the block editor, navigate to the Interface section.
  3. Note the data type column for the input/output currently bound to the SFC access.
  4. Repeat for the target FB instance.
  5. Compare the data types. If they differ, you have identified Root Cause 1.

You can also enable the View → Details → Data Type Information overlay in the interconnection editor to see the resolved data type of each line at a glance.

4. Root Cause 2 — Boolean Assignment Mismatch

The second cause applies specifically to S7 GRAPH interlock and supervision conditions. Even when both source and target connections are BOOL, the editor may still reject the move if the assignment mode of the original SFC access differs from the assignment mode stored for the target connection.

4.1 Reserved Sequencer Names

S7 GRAPH reserves four boolean assignment tokens that the sequencer interprets specially:

Reserved Token Meaning Allowed Use
0 Step inactive / not running Sequencer state read-back only
Run Step active / running Sequencer state read-back only
Interlocked Interlock/supervision active when bound boolean = TRUE S7 GRAPH interlock & supervision
Not interlocked Interlock/supervision active when bound boolean = FALSE S7 GRAPH interlock & supervision

The literal values TRUE and FALSE are not interchangeable with Interlocked / Not interlocked. When a step's interlock was defined with assignment Interlocked and you attempt to drag the access to a connection that was previously used with assignment TRUE, TIA Portal raises the same "cannot be moved" error.

4.2 Why the Assignment Mismatch Fails

The SFC access in the project DB stores two pieces of metadata:

  • The tag reference (DB number, byte offset, bit offset for BOOL).
  • The assignment mode (Interlocked / Not interlocked / TRUE / FALSE / direct).

When Alt+drag is invoked, the editor copies both pieces to the target connection. If the target connection's previous SFC access used a different assignment mode and the editor's consistency check decides the two are incompatible (for example, swapping Interlocked for TRUE would invert the runtime meaning of the same boolean), the move is rejected.

4.3 Diagnosing the Assignment Mismatch

  1. Double-click the SFC step or transition in the S7 GRAPH editor.
  2. For interlock conditions: open the Interlock tab.
  3. For supervision conditions: open the Supervision tab.
  4. Note the assignment dropdown — it will read Interlocked or Not interlocked.
  5. Open the Properties dialog of the target block input/output. Look for any previous SFC access reference and its stored assignment mode.
  6. If the modes differ, you have identified Root Cause 2.

5. Diagnostic Workflow Summary

Step Action Outcome
1 Open both block interfaces and compare data types If they differ → Root Cause 1 (type mismatch)
2 Open the SFC step / transition properties and note assignment mode If assignment differs from target → Root Cause 2 (semantic mismatch)
3 Check the compile output window (View → Output → Compile) for SFC warnings Warnings often pinpoint the exact access line number
4 Verify the target parameter direction (IN/OUT/IN_OUT/CONST/TEMP) TEMP and CONST cannot host SFC interconnections
5 Confirm both blocks belong to the same program cycle and are not in different AS stations Cross-station SFC access is blocked

6. Resolution Procedures

6.1 Resolving a Data Type Mismatch

Choose one of the following options:

Option A — Select a matching target. Identify a different input/output on the target block that exposes a BOOL parameter and attempt the Alt+drag operation again.

Option B — Add a new BOOL input. Open the target FB and add a new parameter (for example bEnableExt : BOOL). Recompile the FB and retry the move to the new parameter.

Option C — Use a comparison block. Insert a comparator (for example GE_REAL from the standard library) that converts the REAL signal to a BOOL output. Connect the comparator's BOOL output to the SFC access. This is the recommended approach when the analog signal represents a threshold.

Option D — Modify the source type. If the application permits, change the source parameter's data type to match the target. Update all downstream consumers of the source.

6.2 Resolving a Boolean Assignment Mismatch

  1. Open the SFC step/transition and navigate to the Interlock or Supervision tab.
  2. Change the assignment dropdown to the mode required by the target connection (typically Interlocked for interlock conditions, Not interlocked for inverted conditions).
  3. If you change the assignment mode, also invert the bound expression to preserve the original logic. For example, an interlock of "FB".bFault with mode Not interlocked is equivalent to NOT "FB".bFault with mode Interlocked.
  4. Save the SFC block and recompile the project.
  5. Retry the Alt+drag operation.

6.3 Verification Checklist

  • [ ] Source and target parameter data types match (both BOOL for SFC).
  • [ ] Assignment modes are compatible (Interlocked / Not interlocked / TRUE / FALSE).
  • [ ] SFC block compiles without errors.
  • [ ] SFC block compiles without SFC-specific warnings in the output window.
  • [ ] Alt+drag completes without the error message.
  • [ ] The interconnection appears in the new position in the cross-reference list.

7. Block Interface Compatibility Rules

Source Type Allowed SFC Target Types Notes
BOOL BOOL Direct match; always allowed
BOOL WORD / DWORD / INT / REAL Not allowed; SFC engine requires BOOL
INT / REAL / WORD / DWORD BOOL Not allowed; insert a comparator first
BOOL (multi-instance) BOOL Allowed; multi-instance FBs are first-class citizens
BOOL (PLC tag) BOOL Allowed; PLC tags are referenced by absolute address

7.1 Access Direction Restrictions

SFC interconnections can target the following parameter directions:

  • Input (IN) — allowed.
  • Output (OUT) — allowed (the SFC reads the output value).
  • InOut (IN_OUT) — allowed but uncommon for SFC conditions.
  • Static (STAT) — allowed for multi-instance FBs.

The editor will reject moves to:

  • Constant (CONST) parameters.
  • Temporary (TEMP) parameters.
  • Read-only system-side connections.

7.2 Block Identity Independence

The source and target blocks do NOT need to be the same FB type, instance, or even from the same library. The editor validates only the parameter data type and assignment compatibility, not the block identity. Moving an SFC access from "FB_Conveyor_1".bRun to "FB_Conveyor_2".bRun is permitted as long as both bRun parameters are BOOL.

8. S7 GRAPH vs Basic SFC Behavioral Differences

The boolean assignment mode (Interlocked / Not interlocked) is unique to S7 GRAPH. If you are working with the basic SFC editor available for S7-1500 and ET 200SP CPUs (added in TIA Portal V14 SP1), the assignment concept does not apply — transition conditions are evaluated directly as boolean expressions. The data type mismatch cause (Root Cause 1) still applies.

If you encounter the "cannot be moved" error in basic SFC, the cause is almost always a data type mismatch. Diagnose by following the procedure in Section 3.

9. Multi-Instance and Cross-Station Considerations

9.1 Multi-Instance FBs

When the source or target SFC access targets a parameter of a multi-instance FB (an FB instantiated inside another FB's STAT section), the editor stores the access path as a fully qualified instance name. The path looks like "Parent_DB".Child_Instance.Parameter. When moving the access between two multi-instances, ensure both instance names resolve correctly in the compiled SCL/ST/FBD source.

9.2 Cross-Station SFC Access

If the source and target blocks are in different AS stations or different S7-1500 CPUs of the same project, Alt+drag cannot move the access across the station boundary. TIA Portal raises a different error ("Interconnection across station boundaries is not permitted"). In this case, create a proxy tag in the SFC block's home station and link the proxy to the remote tag via PUT/GET or via an Open User Communication connection.

10. Verification and Field Testing

10.1 Offline Verification

  1. Compile the project (Project → Compile → Software (rebuild all)).
  2. Open the cross-reference list (Right-click the SFC block → Cross-references) and confirm the new interconnection appears.
  3. Check that no orphaned references remain on the old connection.

10.2 Online Verification

  1. Back up the current PLC program (Online → Backup).
  2. Download the modified SFC block to the PLC.
  3. Open the S7 GRAPH viewer (or SFC viewer) in online mode.
  4. Force the boolean source to TRUE and observe the transition or interlock activate.
  5. Force the boolean to FALSE and observe the transition or interlock deactivate.
  6. Test all sequencer paths that depend on the moved access.

10.3 Functional Test Cases

Test Case Expected Behavior
Bound boolean = TRUE (Interlocked) Interlock active, step waits / faults per configuration
Bound boolean = FALSE (Interlocked) Interlock inactive, step can transition
Bound boolean = TRUE (Not interlocked) Interlock inactive
Bound boolean = FALSE (Not interlocked) Interlock active
Power cycle while step active Step state restored per remanence setting
CPU restart with new SFC version Sequencer initializes at initial step

11. Troubleshooting Matrix

Observed Symptom Likely Cause Resolution
Error on first Alt+drag attempt Data type mismatch Match BOOL types or insert comparator
Error after target is highlighted Boolean assignment mismatch Change assignment mode in step/transition properties
Move succeeds but compile fails Inconsistent cross-reference Recompile all blocks; check SFC output window
Move succeeds, runtime fault on first scan Type conversion error Add explicit conversion block
Move succeeds, logic inverted Assignment vs expression flipped Invert the bound expression to restore original logic
Move succeeds, no runtime effect Wrong target block selected Verify the qualified instance name in the cross-reference
Error on first attempt, succeeds on second retry Editor cache stale Save, close, reopen the SFC block
Error only on a specific CPU model Firmware version difference in SFC handling Update TIA Portal to a version that matches the CPU firmware (refer to the TIA Portal release notes)

12. Related SFC Errors and Edge Cases

Engineers troubleshooting this error frequently encounter related SFC errors that share the same root causes:

  • "SFC access cannot be created" — raised when creating a new SFC access (rather than moving one) to an incompatible connection. Resolution is identical: match types or change assignment.
  • "Transition condition invalid" — raised at compile when the transition references a non-boolean expression. Add a comparator or change the source tag.
  • "Step qualifier conflict" — raised when S7 GRAPH step qualifiers (N, S, R, L, D, etc.) are inconsistent with the interlock mode. For example, qualifier "L" (limited) on a step with a permanent interlock causes an infinite wait state.
  • "Sequencer overflow" — raised when the SFC structure exceeds the CPU's maximum step count. Refer to the CPU's SFC resource limits in the device manual.
  • "SFC initial step missing" — raised when the SFC has no defined initial step after a refactor.

13. Platform and Firmware Notes

The error and resolution apply to the following TIA Portal versions and target hardware:

TIA Portal Version S7 GRAPH Status Notes
V13 SP1 / V14 Legacy Some Alt+drag quirks; menu navigation differs
V15 / V15.1 Supported Stable behavior
V16 / V17 Supported Improved cross-reference integration
V18 / V19 Supported Current LTS and latest release
V20 Supported Latest as of this writing; verify CPU firmware compatibility

For legacy STEP 7 V5.x projects with S7 GRAPH V5.x, the same root causes apply. The menu path to the Interlock assignment differs slightly (S7 GRAPH → Step properties → Interlock tab → Assignment dropdown).

Always consult the Siemens Industry Online Support portal for the latest function manuals, application examples, and firmware compatibility matrices before applying the resolution to a production system.

14. Best Practices for Avoiding the Error

  • Standardize tag names. Avoid PLC tag names that collide with reserved SFC tokens (0, Run, Interlocked, Not interlocked). Prefix all boolean tags with a project-specific identifier.
  • Use wrapper FBs for mode bits. Centralize mode and interlock signals in a dedicated FB with explicit BOOL inputs. This makes future refactors cleaner and reduces direct PLC-tag dependencies in the SFC.
  • Document assignment modes. Add comments to each SFC step explaining why Interlocked vs Not interlocked was chosen. This prevents the next engineer from "fixing" the assignment during a routine refactor.
  • Test refactors in a sandbox project. Before applying an Alt+drag move to a production SFC, replicate the structure in a test project and verify the move succeeds and the logic remains equivalent.
  • Keep S7 GRAPH and basic SFC separated. Do not mix S7 GRAPH and basic SFC in the same S7-1500 CPU if avoidable; the assignment mode differences cause confusion.

What does "The SFC interconnection cannot be moved to this connection" mean in TIA Portal?

It is an editor-side validation error raised during an Alt+drag operation that attempts to relocate an existing SFC access from one block input/output to another. The move is rejected because either the target connection's data type does not match the original (typically the target is not BOOL while the source is) or the target connection's stored boolean assignment mode (Interlocked / Not interlocked / TRUE / FALSE) differs from the source's assignment mode.

Why can I not drag an SFC connection to a BOOL input even though both are BOOL?

For S7 GRAPH interlock and supervision conditions, the assignment mode matters as much as the data type. The original access was likely created with assignment "Interlocked" while the target connection was previously used with assignment "TRUE" or a different mode. Open the step's Interlock or Supervision tab and change the assignment dropdown to match the target connection before retrying the move.

Does the same error occur in basic SFC (IEC 61131-3) on S7-1500?

The "Interlocked" / "Not interlocked" assignment mode does not exist in basic SFC, so Root Cause 2 does not apply. However, Root Cause 1 (data type mismatch) still applies. If you see the error in a basic SFC block, verify that the target connection is BOOL and insert a comparator block if you need to derive a boolean from an INT, REAL, or WORD value.

Can I move an SFC access between two different function block types?

Yes. TIA Portal validates only the parameter data type and the boolean assignment mode; it does not validate the block identity or the block library. As long as both the source and target parameters are BOOL and both have compatible assignment modes, the move is permitted between any two FB types.

How do I find the stored assignment mode of an S7 GRAPH interlock?

Open the SFC step in the S7 GRAPH editor, navigate to the Interlock or Supervision tab, and view the assignment dropdown. The available options are Interlocked and Not interlocked. If neither option appears, the step uses a direct boolean expression (no interlock/supervision mode) and the assignment concept does not apply.

Will this error ever reach the running PLC?

No. The error is caught at editor validation time and prevents the invalid move from being saved to the project. The PLC will not attempt to execute an invalid SFC configuration. However, if you bypass the editor (for example by manually editing the SFC source XML or by importing a corrupted project archive), the error could reach runtime and cause an SFC fault or CPU STOP.

Where can I find official Siemens documentation for S7 GRAPH and SFC troubleshooting?

The Siemens Industry Online Support portal at support.industry.siemens.com hosts the S7 GRAPH function manual, the TIA Portal SFC programming guide, and a large library of application examples and FAQ entries. Search for "S7 GRAPH" or "SFC TIA Portal" on that portal for the most current documentation for your installed TIA Portal version.

Back to blog