Fixing ET200SP V90 PROFINET Connection Through Network Switch

David Krause19 min read
Industrial NetworkingSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Description and Symptoms

A recurring commissioning problem in small PROFINET cells built around the SIMATIC ET 200SP, SINAMICS V90 PN, SIMATIC HMI KTP700, and an engineering PC is the partial-visibility fault: the HMI panel connects and exchanges data with the controller through the network switch and is fully operable, while the controller (ET 200SP CPU or interface module) and the drive (SINAMICS V90 PN) remain unreachable from the engineering PC on the same switch. Direct point-to-point cabling between the PC and the PLC works perfectly. The moment traffic is forced through an unmanaged consumer switch (TP-Link TL-SG series is the most commonly reported brand), the PC loses the ability to ping, browse, download to, or run PROFINET diagnostics against the PLC and the V90.

Observable symptoms in the field:

  • PC pings succeed to the HMI (192.168.0.4) but time out to the PLC (192.168.0.6) and drive (192.168.0.20).
  • PRONETA 3.3 (Siemens PROFINET commissioning tool) discovers the HMI but does not list the PLC or the V90 when the switch is in the path.
  • TIA Portal "Online > Accessible devices" returns only the HMI; the PLC and V90 are missing.
  • Direct PC-to-PLC cabling with a Cat5e patch cord works without any change to the TIA project.
  • After a blank program download, the V90 surfaces alarm F7490 "No startup inhibit set", even when p8641 (STO/SS1 selection) is configured.
  • The PROFINET device names appear empty in PRONETA, meaning the controllers have never completed DCP identification.
  • Replacing the suspect switch with a Siemens SCALANCE XB005 immediately restores visibility of every device.

The defining clue is the asymmetry: the HMI connects, the PLC and drive do not, and direct cabling works. This is the signature of an Ethernet Layer-2 problem on the switch, not a TIA Portal project error or an IP addressing mistake. The HMI uses standard TCP/IP for its connection to the PLC; the PLC and V90 also use PROFINET DCP (Discovery and Configuration Protocol, EtherType 0x8892) for discovery and LLDP (IEEE 802.1AB, EtherType 0x88CC) for neighbour detection. A switch that mishandles these multicast frames causes the partial-visibility fault.

Reference Network Topology

The topology below is the canonical example reported in field service calls. All four devices use static IP addresses in the 192.168.0.0/24 subnet with a 255.255.255.0 mask, no default gateway, and the same IP assignment method on every device (S7-REGSVC or static PROFINET addressing via PRONETA).

Table 1 — Device addressing for the failing cell
Device Siemens article number / family IP address Subnet mask PROFINET name Role
Engineering PC Generic x86, TIA Portal V17 / V18 192.168.0.10 255.255.255.0 — PG/PC (IO supervisor)
KTP700 HMI 6AV2 128-3GB06-0AX0 (KTP700 Basic, PN) 192.168.0.4 255.255.255.0 ktp700-hmi IO Device (HMI station)
ET 200SP CPU 6ES7 510-1DJ02-0AB0 (CPU 1510SP-1 PN) 192.168.0.6 255.255.255.0 et200sp-cpu IO Controller
V90 PN drive 6SL3 210-5FB10-4UA0 (V90 PN, 400 V, 0.4 kW) 192.168.0.20 255.255.255.0 v90-drive IO Device (drive)
Network switch TP-Link TL-SG108 (unmanaged, suspect) — — — Layer-2 fan-out

The HMI runs as a PROFINET IO Device only for process-data exchange with the CPU; its IP stack is implemented in WinCC flexible / TIA WinCC. The V90 PN is a pure PROFINET drive that exchanges process data (telegram 1 or telegram 3) over the same network. All three IO stations must be reachable via DCP (multicast 01-0E-CF-00-00-00, EtherType 0x8892) for the IO Controller to assign names and parameters.

Subnet rule. Every device and the engineering PC must sit in the same IP subnet. The fact that the HMI is reachable from the PC confirms the subnet is correct; the problem is therefore not Layer-3 routing but Layer-2 forwarding on the switch.

Root Cause Analysis

Six Layer-2 mechanisms are responsible for the partial-visibility fault in approximately 90% of field cases. They are listed below in order of likelihood for a TP-Link consumer switch in PROFINET service.

1. Energy Efficient Ethernet (IEEE 802.3az) breaking PROFINET RT

Many unmanaged switches, including multiple revisions of the TL-SG105, TL-SG108 and TL-SG116, advertise 802.3az Energy Efficient Ethernet (EEE) as a default-enabled feature. EEE puts the PHY into a Low Power Idle (LPI) state during inter-frame gaps. PROFINET RT Class 1 uses a 1 ms send clock and 31.25 µs bit time at 100 Mbit/s. The LPI wake-up latency on some PHYs exceeds 4 ms, which is longer than the PROFINET watchdog window, breaking the AR (Application Relationship) before it is fully established. The drive or CPU drops the AR, DCP responses are lost, and the device becomes invisible to PRONETA even though the link LED is solid green.

EEE is also enabled by default on many PC NICs (Intel I219-V, Realtek RTL8111) and on Windows 10/11 "Power Saver" profiles. Disable EEE on the PC NIC as well as the switch; one without the other leaves the problem in place.

2. Auto-negotiation collapsing to 10 Mbit/s or half-duplex

ET 200SP CPUs and V90 PN ports are factory-set to auto-negotiate, but they strongly prefer 100 Mbit/s / full-duplex. If the switch port is forced to 10 Mbit/s or half-duplex (often the default on legacy "green" switch settings, or on a switch whose auto-negotiation logic is buggy), the PLC link comes up but DCP multicast responses are dropped silently. Half-duplex on a 100 Mbit/s link is also the canonical trigger for late collisions, which PROFINET treats as a transport error.

3. IGMP / MLD snooping filtering PROFINET multicast

PROFINET uses the multicast group 01-0E-CF-00-00-00 for DCP identification, 01-0E-CF-00-00-10..1F for PROFINET RT frames, and LLDP multicast 01-80-C2-00-00-0E for neighbour detection. Unmanaged switches with IGMP snooping enabled (or "optimised for video streaming" presets on consumer switches) may treat unknown multicast as flooded, but during switch warm-up the snooping table is not yet populated, and DCP frames for 5-15 s after the first packet are dropped, during which PRONETA's first scan misses the device. MLD snooping for IPv6 multicast behaves the same way and is a common cause when Windows 10/11 IPv6 is left enabled on the PC.

4. MAC address table aging or reset on port events

Default MAC aging is 300 s on most consumer switches. This is normally fine. However, some switches (and the TL-SG108E in particular when set to "Flow Control Off" mode) reset the MAC table on any port-down event, which re-triggers a learning phase. During that phase, DCP responses from the PLC to the PC may arrive before the switch has learned the PC's MAC on that port, and the response is flooded but not necessarily returned to the originator. The visible symptom is that PRONETA discovers the device on some scans and misses it on others.

5. Auto-MDI/MDIX failure on damaged or shielded cables

Cat5e cables with a broken pair, a missing shield termination, or a poorly-crimped RJ45 plug can show full link on a direct connection (because both PHYs use the same MDI/MDIX logic) but fail on a switch that maps different pairs. The PLC link light comes on, but no frames are exchanged. Swap the patch cord first; this is the cheapest diagnostic step and resolves approximately 15% of field cases.

6. Loop or broadcast storm from a miswired daisy-chain

If the cell was previously wired in a ring or with two uplink ports back to the same switch, the unmanaged switch can spend 30-60 s in a learning/forwarding transition. Some low-end switches do not implement STP at all and flood broadcasts, masking the issue until PC traffic is heavy. A single Ethernet loop can also hold the switch's CPU at 100% and prevent it from forwarding PROFINET frames at all.

Diagnostic Procedure

Follow this sequence. Each step is independent; do not skip ahead to TIA Portal diagnostics until the Layer-2 health checks pass.

  1. Verify the PC link state. Open "Network and Sharing Center > Ethernet > Status" and confirm 100 Mbit/s or 1 Gbit/s / full-duplex. If the link is 10 Mbit/s or half-duplex, the switch port is the problem and the rest of the cell will not work.
  2. Substitute the switch. Use a different unmanaged switch known to handle PROFINET, e.g. a Siemens SCALANCE XB005 (article 6GK5 005-0BA00-1AB2). If the cell now works, the original switch is the defect and should be replaced.
  3. Substitute the cables. Replace every Cat5e patch cord with a known-good one, even if the link LED is green on every port. Patch cords are the most common source of intermittent Layer-2 faults.
  4. Disable 802.3az on the PC NIC. In Windows Device Manager > Network Adapter > Power Management, uncheck "Allow the computer to turn off this device to save power". In the adapter's Advanced properties, disable "Energy Efficient Ethernet" and "Green Ethernet". Realtek, Intel and Broadcom NICs all expose these properties.
  5. Disable 802.3az on the switch. On a managed switch (TL-SG108E, TL-SG116E, SCALANCE XC208), log in and disable EEE per port. On a fixed-function unmanaged switch, EEE cannot be disabled, so the switch is unfit for PROFINET — replace it.
  6. Force port speed/duplex on the PC. Set the PC NIC to 100 Mbit/s / full-duplex (no auto-negotiate) to remove one variable. PROFINET devices always run 100 Mbit/s full-duplex, so this is a safe configuration.
  7. Run PRONETA in network analysis mode. PRONETA 3.3+ exposes a "Network analysis" tab that walks every subnet in parallel. It will display the missing PLC with a yellow "no DCP response" badge. This is the smoking gun that the Layer-2 path is broken.
  8. Capture with Wireshark. Filter on eth.addr == <PLC MAC> and check whether DCP Identify requests (EtherType 0x8892, subfunction 0x01) ever leave the PC. If yes, but no Identify Response (subfunction 0x04) is seen, the PLC is not receiving them, or the response is filtered by the switch.
  9. Check the PLC diagnostics buffer. In TIA Portal, "Online > Online & Diagnostics" on the CPU lists the most recent 100 entries. Look for "PROFINET IO system error" with details "DCP timeout" or "AR establishment failure". The exact error code (16#0001, 16#0002, 16#0010) maps to a specific cause; see Table 5 below.
  10. Verify the V90 PN port directly. Use the V90's built-in web server (port 80) or STARTER / SINAMICS commissioning software to read r8970 (PROFINET state) and r8971 (PROFINET error). A value of 4 in r8970 means the AR is down. A value of 3 means the AR is established and the Layer-2 path is healthy.

Useful commands and capture filters

The following Windows and Wireshark commands are used throughout the diagnostic procedure.

ping 192.168.0.6 -t
ping 192.168.0.20 -t
arp -a
ipconfig /all
netsh interface show interface
Wireshark filter for DCP identify requests:
eth.type == 0x8892 && pn_dcp.subfunction == 0x01

Wireshark filter for DCP identify responses:
eth.type == 0x8892 && pn_dcp.subfunction == 0x04

Wireshark filter for PROFINET RT:
eth.type == 0x8892 && pn_rt

Wireshark filter for LLDP:
eth.type == 0x88cc

IP Address and Subnet Configuration

Although the partial-visibility fault is dominated by Layer-2 issues, IP misconfiguration is a fast-to-check co-conspirator. The reference addressing used in the failing cell is below; verify it on every device.

Table 2 — Static IP and PROFINET configuration checklist
Parameter PC HMI PLC V90
IP address 192.168.0.10 192.168.0.4 192.168.0.6 192.168.0.20
Subnet mask 255.255.255.0 255.255.255.0 255.255.255.0 255.255.255.0
Default gateway 0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0
PROFINET device name — ktp700-hmi et200sp-cpu v90-drive
PROFINET role Supervisor IO Device IO Controller IO Device
PN interface subnet name — PN/IE_1 PN/IE_1 PN/IE_1

To make sure the PC is correctly addressed, run ipconfig /all from an elevated command prompt and confirm the IPv4 address, subnet mask, and that "DHCP Enabled" is "No" if static addressing is intended. If the PC is on a different /24 (for example, 192.168.1.10), the HMI would not work either. The fact that the HMI works confirms the PC's IP is in the same /24 as the cell.

To verify the PROFINET device name has been assigned correctly, run PRONETA, "Network analysis", click the device, and read the "Name of station" field. An empty field means the controller has never received a name from TIA Portal or PRONETA; the AR will not come up.

Switch Selection and Hardening for PROFINET

For cells with one IO Controller and up to ~8 IO Devices, a managed switch is strongly recommended. Siemens provides a PROFINET-conformant line; the most common field picks are listed in Table 3.

Table 3 — Siemens SCALANCE switches suitable for ET 200SP / V90 cells
Article number Model Ports Managed PROFINET CC-A Notes
6GK5 005-0BA00-1AB2 SCALANCE XB005 5 No Yes (limited) Entry-level, no EEE, 100 Mbit/s.
6GK5 008-0BA00-1AB2 SCALANCE XB008 8 No Yes (limited) Compact unmanaged, suitable for small cells.
6GK5 008-0GA00-1AB2 SCALANCE XB208 8 No Yes PN-friendly, 100 Mbit/s, no EEE.
6GK5 008-0BA10-1AB2 SCALANCE XC208 8 Yes Yes Web-managed, full PROFINET diagnostics.
6GK5 016-2GS00-2AC2 SCALANCE XC216 16 Yes Yes For cells with more than 8 IO devices.
6GK5 324-0BA00-3AR3 SCALANCE XC324 24 Yes Yes (CC-B) Gigabit, for high-performance cells.

If the existing TP-Link must be kept, the following measures make it usable:

  • Disable EEE per port via the switch's web UI (TL-SG108E, TL-SG116E). On a fixed-function TL-SG108 without a UI, EEE is hardware-enabled and cannot be disabled — replace the switch.
  • Disable "Green Ethernet" / "Power Saving" mode if present in the switch's UI.
  • Set every port to "Auto Negotiation" with "Flow Control Off" to remove any priority-pause interference with PROFINET RT.
  • Keep cable lengths below 80 m even though Cat5e supports 100 m; headroom helps PROFINET timing on 100 Mbit/s full-duplex.
  • Do not mix the PROFINET cell with general office traffic on the same switch; broadcast storms from Windows or DHCP will stall PROFINET AR bring-up.
  • Do not connect the engineering PC and the cell through a Wi-Fi bridge or Powerline adapter; the latency and jitter will break PROFINET RT Class 1.
Hard rule. PROFINET conformance class A (CC-A) requires switches to either disable EEE or to advertise a wake-up latency of ≤ 25 µs. Most consumer switches fail this. Replacing the switch is faster than fighting the firmware.

PROFINET Device Discovery with PRONETA

PRONETA is the standard tool for verifying Layer-2 reachability before opening TIA Portal. Download PRONETA 3.3 or later from the Siemens support portal. The verification procedure is:

  1. Connect the PC, HMI, PLC, and V90 through the suspect switch.
  2. Launch PRONETA and click Network analysis.
  3. Set the IP range to 192.168.0.0/24 and start the scan.
  4. After 5-15 s the tool lists every PROFINET-capable device, including the HMI if it answers DCP.
  5. Devices that respond to DCP but whose IP is in a different subnet are flagged yellow. Devices that do not respond are flagged red.

For every red device:

  • Check the link LED on the switch port — solid green means PHY is up.
  • From the PC, run arp -a and verify whether the MAC of the missing device is in the ARP cache. If yes, the switch forwarded the DCP response; the upper layers are at fault. If no, the switch is filtering.
  • Use PRONETA's "Set IP address" function to force an IP from the PC. If the device accepts the IP but the project still fails, the Layer-2 path is repaired; if it refuses, the device is unreachable.
  • Use PRONETA's "I/O Test" function to test the PLC's PROFINET ports directly. With the PLC connected directly to the PC, run "I/O Test" and verify that all configured slots are reported. This isolates the PLC's PROFINET stack from any switch issue.

PRONETA can also read the ET 200SP station's neighbour list (LLDP), which shows every PROFINET device visible to the CPU through the switch. If the CPU's neighbour list is empty, the Layer-2 path is broken; if it lists the HMI but not the V90, the V90's PROFINET port is the suspect.

TIA Portal Project and Download

Once the switch is verified and every device pings, configure TIA Portal to use the same PROFINET topology as the physical cell. The mandatory settings in the project are:

  • PC interface: "PN/IE" with the active NIC, "TCP/IP (Auto)" mode.
  • PLC PROFINET interface: same subnet (192.168.0.x / 255.255.255.0).
  • V90 PN: same subnet, PROFINET name "v90-drive", IP 192.168.0.20.
  • HMI: same subnet, name "ktp700-hmi", IP 192.168.0.4.
  • Use the device-name assignment function in TIA Portal (Online > PROFINET device name assignment) to push the name to the V90 and the HMI; DCP cannot complete the AR without a name.
  • For the ET 200SP CPU 1510SP-1 PN, ensure firmware V2.9 or later is installed. Earlier firmware has a known PROFINET AR timeout bug fixed in V2.9 SP1.

If the HMI was connecting through the switch in the failing cell, the TIA Portal project for the HMI is almost certainly correct. The remaining work is to align the PLC and V90 with the same PROFINET configuration and assign the names. Once the names are assigned, restart the PLC; the AR with the V90 should come up within 5 s.

The PROFINET diagnostics in TIA Portal can be used to confirm the AR state. Open "Online > Online & Diagnostics > PROFINET diagnostics" on the CPU. The "I/O systems" tab should show the V90 with a green check and the cycle time 1 ms.

V90 Drive Startup Inhibit Handling

The "NO STARTUP INHIBIT SET" alarm is fault F7490 on the V90 PN and is independent of the Layer-2 fault, but it is reported in the same context. The alarm is raised when the drive has been powered up but the safety startup inhibit has not been acknowledged.

Table 4 — V90 PN parameters for the safety startup inhibit
Parameter Name Recommended value Notes
p9601 SI enable, integrated functions 0 (no safety) or 1 (STO via PROFIsafe) Set before p8641 is acknowledged.
p8641 STO/SS1 selection 0 (deselect STO/SS1) after PROFIsafe handshake Acknowledges the startup inhibit.
r8970 PROFINET state 3 = AR established Confirms the Layer-2 path is up.
r8971 PROFINET error code 0 = no error Non-zero values map to F08501 / F08502.
p0922 PROFIdrive telegram selection 1 (standard) or 3 (with actual speed) Match the TIA project configuration.
p2051[0] PROFIdrive PZD receive word count Match p0922 Determines IO data length.

The alarm is cleared by acknowledging the inhibit through the safety configuration or, in non-safety applications, by setting p9601 to 0. The fact that a blank TIA Portal program download clears the alarm suggests that the previous configuration was generating the alarm; the network fault and the alarm are coincident, not causal.

To verify the drive's PROFINET state without using STARTER, browse to the V90's web server (http://192.168.0.20) and open "Diagnostics > PROFINET". The web server is enabled by default on V90 PN drives with firmware V1.04 or later.

PROFINET AR Error Code Matrix

The following table maps the most common PROFINET AR error codes reported in the ET 200SP CPU's diagnostic buffer to their root cause and corrective action. The codes are reported in hex.

Table 5 — PROFINET AR error code mapping
Error code (hex) Meaning Likely root cause Corrective action
16#0001 DCP timeout Switch filtering DCP multicast Disable EEE / IGMP snooping on switch
16#0002 LLDP timeout Switch dropping LLDP multicast Replace switch with SCALANCE
16#000A AR establishment timeout PROFINET name not assigned Assign PROFINET name via PRONETA
16#0010 AR Consumer Protocol violation Mismatched telegram configuration Match p0922 with TIA project
16#0011 AR Consumer watchdog timeout Late frames, switch adding latency Reduce send clock or replace switch
16#001F AR Vendor-specific error Drive-specific alarm (e.g. F7490) Check drive alarm buffer
16#002D AR no IP address Device has no IP Assign IP via PRONETA
16#002E AR IP address conflict Duplicate IP on network Verify IP table

Verification Checklist

Use this matrix to confirm the cell is fully operational after the switch replacement or hardening.

Table 6 — End-to-end PROFINET verification
Check Tool Expected result
Ping PLC from PC cmd.exe ping 192.168.0.6 -t Reply from 192.168.0.6 in < 1 ms, 0% loss
Ping V90 from PC cmd.exe ping 192.168.0.20 -t Reply from 192.168.0.20 in < 1 ms, 0% loss
PRONETA network analysis PRONETA 3.3 All four devices listed, all green checkmarks
TIA Portal accessible devices TIA V17 / V18 PLC, HMI, V90 visible
PROFINET device name assignment TIA Online > PROFINET name Names persist after PLC restart
V90 r8970 Web server of V90 or STARTER 3 (AR established)
V90 alarm buffer STARTER or web server Empty, F7490 cleared
PC link speed/duplex Windows NIC status 100 Mbit/s / full-duplex
Switch port LEDs Visual Solid green, no amber, no flashing
PROFINET cycle time TIA Online > Diagnostics 1.0 ms, jitter < 50 µs
CPU diagnostic buffer TIA Online > Diagnostics No entries with PROFINET errors

Frequently Asked Questions

Why does the HMI connect through the switch but the PLC and V90 do not?

The HMI uses standard TCP/IP for its connection to the PLC. The PLC and V90 also use PROFINET DCP (EtherType 0x8892) for discovery and LLDP for neighbour detection. The switch's handling of multicast and EEE is selective; TCP-based HMI traffic passes, while the DCP discovery frames used to find the PLC and V90 are filtered or delayed, leaving the IO devices invisible to the engineering PC.

Is a managed switch required for an ET 200SP / V90 cell?

For cells with one IO controller and up to 8 IO devices, an unmanaged switch with PROFINET conformance is acceptable. A managed switch (e.g., SCALANCE XC208, article 6GK5 008-0BA10-1AB2) is strongly recommended because it lets you disable EEE, force 100 Mbit/s full-duplex per port, and run PROFINET diagnostics. Consumer switches such as the TP-Link TL-SG108 are not PROFINET-conformant out of the box and frequently cause the partial-visibility fault.

What is the meaning of F7490 "No startup inhibit set" on the V90 PN?

F7490 is the safety startup inhibit alarm on the SINAMICS V90 PN. The drive raises it at power-up until p8641 (STO/SS1 selection) has been acknowledged. The alarm is independent of the network fault but appears in the same diagnostic context; clear it by setting p9601 = 0 (no safety) or by completing the PROFIsafe handshake.

How do I confirm the Layer-2 path is the problem and not the PLC?

Bypass the switch: connect the PC directly to the ET 200SP CPU's PROFINET port with a Cat5e patch cord. If the PC now pings 192.168.0.6 and PRONETA lists the CPU, the PLC is healthy and the switch is at fault. If the direct connection also fails, the CPU's PROFINET port is suspect and the diagnostic buffer should be read in TIA Portal.

Does EEE (Energy Efficient Ethernet) really break PROFINET?

Yes. PROFINET RT Class 1 sends frames every 1 ms; EEE introduces Low Power Idle (LPI) cycles of up to 4-8 ms on some PHYs, which can exceed the PROFINET watchdog and force the AR to drop. Disable EEE on every port of the switch and on the PC's NIC, or replace the switch with a PROFINET-conformant model such as a SCALANCE XB005 or XC208.

What is the cheapest way to make the cell work without buying a SCALANCE?

Disable 802.3az and Green Ethernet on the PC NIC first, then disable EEE on the switch (only on managed variants). If the switch is unmanaged, replace it with a SCALANCE XB005 or XB008. Trying to tune a TP-Link unmanaged switch is not recommended; the EEE implementation cannot be turned off on most revisions.

Can the V90 PN be connected directly to the CPU without a switch?

Yes. PROFINET supports direct device-to-controller topologies. With the V90 PN and the CPU 1510SP-1 PN in the same subnet, the AR comes up without a switch. This is a useful diagnostic configuration to isolate the V90's PROFINET port from the suspect switch.

Back to blog