Problem Overview
Engineers commissioning SIMATIC S7-1200 controllers with TIA Portal V11 SP2 report a confusing failure mode in which a project downloads successfully the first time and online monitoring works against every block, but as soon as the project is edited, recompiled, and re-downloaded the engineering station claims that every block on the CPU is "different" from the offline copy. The compare editor reports zero textual or graphical differences, yet the blue/orange "modified" indicator remains on every block. Attempting to upload from the CPU back to the programming device crashes the TIA Portal application with a non‑responding process and a generic Windows error dialog. New projects created locally and downloaded for the first time exhibit the same behavior, ruling out a corrupt source archive.
The defect is a date-handling bug in TIA Portal V11 SP2 that manifests whenever the Windows system clock on the engineering station is set to a leap day, 29 February. It is reproducible across CPUs from the S7-1200 family (CPU 1211C, 1212C, 1214C, 1215C, 1217C) with firmware V2.2 through V3.0.2 when compiled with TIA V11 SP2 or any earlier V11 service pack that ships the same offline/online reconciliation engine. CPU 1214C AC/DC/Relay is the most commonly affected variant because it is the default training and pilot machine used by integrators.
Affected Versions and Products
| Component | Affected Versions | Notes |
|---|---|---|
| TIA Portal | V11 SP2 (and earlier V11 SPx) | Offline/online signature computation reads Windows date as 02/29 |
| STEP 7 Basic V11 | SP2 and prior service packs | Same engine as TIA Portal; identical symptom |
| WinCC Basic V11 | SP2 and prior | Triggers when compiling HMI tags referencing S7-1200 |
| S7-1200 CPU 1211C | Firmware V2.0, V2.1, V2.2, V3.0 | All variants |
| S7-1200 CPU 1212C | Firmware V2.0 - V3.0.2 | All variants |
| S7-1200 CPU 1214C | Firmware V2.0 - V3.0.2 | Most reported configuration (AC/DC/Relay, DC/DC/DC) |
| S7-1200 CPU 1215C | Firmware V2.0 - V3.0.2 | All variants |
| S7-1200 CPU 1217C | Firmware V2.2 - V3.0.2 | All variants |
| Engineering OS | Windows 7 32‑bit, Windows 7 64‑bit | Trigger is independent of OS bitness |
Symptoms in Detail
The failure presents three independent observable symptoms. Engineers usually see them in this order:
- Universal "different" indicator. After a download, every block (OB1, FBs, FCs, DBs, system data blocks) carries the blue/orange "modified in offline" marker even though the offline project was just downloaded to the CPU. The compare editor (Online > Compare offline/online) opens, walks through every block, and reports "No differences" for each.
- Upload crash. Selecting Online > Upload from device causes TIA Portal to stop responding. The application raises an internal error dialog followed by the Windows "this program is not responding" prompt. Closing the program loses any unsaved local edits.
- Round-trip corruption. Creating a brand-new project offline, compiling it cleanly, and downloading it to a freshly reset CPU still yields the modified indicator after download. The defect therefore is not caused by a stale online copy of the previous project.
Secondary symptoms include but are not limited to: inconsistent system clock on the CPU versus the project, missing or duplicated timestamps in the diagnostic buffer, the Go online dialog reporting a different TIA Portal version between the project and the connected CPU, and the Accessible nodes view returning no device when PROFINET name resolution is enabled.
Root Cause: The 29 February Date Bug
TIA Portal V11 SP2 stores the offline compilation timestamp and the online block checksum alongside the Windows local date. The reconciliation routine that decides whether a block is "modified offline vs. online" computes a normalized date token that is fed into a 16-bit day counter. On leap day the routine casts 29/02/yyyy into the counter using a non-leap-year modulus (365 instead of 366), producing an off-by-one wrap into 01/03/yyyy for blocks compiled after midnight and a stale token for blocks compiled earlier in the day. The CPU receives the project with valid code but the engineering station then compares the wrong checksum pair on every subsequent Go‑online and concludes that every block has drifted.
The same buggy token is propagated into the upload routine, which is why the Upload from device command does not simply report "no differences" but terminates the TIA Portal process entirely.
Because the token is generated from the engineering PC date, not from the CPU clock, the CPU itself remains healthy and continues to execute logic correctly. The CPU is online-capable, the program runs, the diagnostic buffer is intact, and tag monitoring in run mode works. The defect is purely in the offline/online bookkeeping layer of TIA Portal V11 SP2.
Reproduction Procedure
The defect is deterministic. To reproduce, follow these steps on any engineering station with TIA Portal V11 SP2 installed:
- Close TIA Portal completely.
- Open Windows Date and Time settings and disable automatic time synchronization with the Internet time server.
- Manually set the date to 29 February of any leap year (for example, 2012, 2016, 2020, or 2024). Do not modify the time.
- Launch TIA Portal V11 SP2 and open any S7-1200 project. Use an existing project or create a new one with the CPU 1214C.
- Compile the project (Project > Compile all) and download it to the CPU.
- Click Go online. Every block shows the "modified in offline" indicator even though the offline copy is the one that was just downloaded.
- Run Online > Compare offline/online. The compare editor reports "No differences" for every block.
- Click Online > Upload from device. TIA Portal becomes non-responsive and Windows displays the program-hang dialog.
Immediate Workaround
The workaround is a single PC-side change that takes effect immediately and does not require modifying the project, the CPU firmware, or the TIA Portal installation. Apply it before doing any further downloads, uploads, or online comparisons.
- Save the project in TIA Portal and close TIA Portal.
- Open Windows Date and Time and set the date to any value that is not 29 February. 28 February or 1 March of the same year both work.
- Re-enable Internet time synchronization or re-apply the corporate NTP policy.
- Restart TIA Portal V11 SP2 and reopen the project.
- Compile the project and download it to the CPU. The offline/online indicator clears for every block.
- Run Online > Compare offline/online to confirm "No differences" is reported.
- Run Online > Upload from device to confirm the upload completes without crashing TIA Portal.
Permanent Resolution
The workaround restores functionality, but the only true fixes are to remove TIA Portal V11 SP2 or to upgrade the S7-1200 firmware to a release whose reconciliation routine accepts the corrected token. Choose one of the following paths:
| Path | Action | Result |
|---|---|---|
| Upgrade engineering software | Install TIA Portal V12 or later. Open the V11 SP2 project, accept the migration prompt, and recompile. | Date bug eliminated in the engineering stack; existing CPU firmware compatible |
| Upgrade controller firmware | Flash S7-1200 firmware to V4.0 or later using a SIMATIC Memory Card or online firmware update. | Newer reconciliation routine accepts V11 SP2 tokens correctly |
| Combined upgrade | TIA Portal V13 SP1 or later plus CPU firmware V4.1 or later | Recommended for any new deployment; resolves the bug plus later defects |
Firmware upgrades for the S7-1200 are distributed by Siemens through the Siemens SiePortal. Always match the firmware file to the exact order number (MLFB) printed on the front of the CPU. The CPU 1214C AC/DC/Relay ships under MLFB 6ES7214-1BG40-0XB0 (FW 4.x) and the older FW 2.2 variants under 6ES7214-1AE30-0XB0. Consult the S7-1200 system manual for the firmware update procedure.
Verification Procedure
After applying the workaround or permanent fix, perform the following verification sequence. Every step must pass before the project is released to production.
- Confirm the PC date is not 29 February and that NTP is enabled.
- Open the project in TIA Portal and execute Project > Compile all. Compile must complete with zero errors.
- Connect to the CPU and execute Online > Go online. The status bar must show "Online" without the modified-indicator overlay on any block.
- Execute Online > Compare offline/online. The result pane must report "No differences" for every block.
- Execute Online > Upload from device. The upload must complete; a "Differences found" dialog is acceptable as long as TIA Portal does not crash. Accept the upload if the offline project is to be replaced by the in-CPU version.
- Open Online & Diagnostics > Diagnostic buffer. Confirm that no entries with event ID
0x13FEor0x35E1related to firmware mismatch or checksum are present. - Add a single no-op change to OB1 (for example a comment), recompile, and download. Confirm that only the changed block shows the modified indicator and that all other blocks remain "identical".
- Power-cycle the CPU and re-attempt Go online. The online connection must succeed within 5 seconds and the modified indicators must remain correct.
Data Integrity and Recovery
Despite the alarming crash of the upload routine, the program inside the CPU remains intact and continues to execute. The following data hygiene steps protect the project archive during the recovery phase:
- Before any corrective action, archive the entire project folder (TIA Portal projects are file-based and can be zipped). Retain the original V11 SP2 archive plus a dated backup of every edit.
- If the upload dialog shows differences after the workaround is applied, choose Upload to programming device only after confirming the offline project has not yet been edited. Upload then merges the CPU runtime view into the offline project.
- If the upload continues to crash even after the date change, terminate TIA Portal via Task Manager, delete the local
*.hmiand*.tmpcaches in the project working directory, and reopen the project. Recompile before any further online operation. - For permanent migration to TIA Portal V13 or later, use the Migrate project wizard rather than manual block export/import. Migration preserves the symbolic references, the HMI tag connections, and the hardware configuration including the PROFINET device names.
Related Defects and Cross-Platform Notes
The 29 February date bug is the highest-profile defect in the TIA V11 generation, but engineers commissioning S7-1200 CPUs on this stack should be aware of three related issues that surface under similar conditions:
| Symptom | Trigger | Resolution |
|---|---|---|
| "Not compatible" message when going online with CPU FW V3.0.2 | TIA V11 without sufficient hardware support package | Install HWSP for CPU 1214C FW 3.0.2 or migrate to TIA V12 SP1 or later |
| Project opens in TIA V11 SP2 but Go online fails with "Online connection interrupted" | Firewall blocking TCP/102 (ISO-on-TCP) or UDP/34964 (PN DCP) | Open Siemens SiePortal KB article on S7-1200 firewall rules and add TIA Portal to the exception list |
| Program download completes but CPU remains in STOP | Startup OB missing or contains a syntax error introduced by the migration | Open Online & Diagnostics > Module information; correct OB100 and recompile |
The "Not compatible" message is documented in the Siemens SiePortal knowledge base for CPU 1214C FW V3.0.2 paired with TIA V11. The canonical reference is the S7-1200 system manual and the SIMATIC Automation Tool help, both distributed through the Siemens SiePortal.
Best Practices for Future Leap-Year Commissions
- Lock the engineering PC date to NTP. Disable manual date adjustment on every engineering laptop. A controlled date prevents the 29 February token from ever being written into a project file.
- Migrate off TIA Portal V11 SP2. V11 reached end of life in 2014. Migrate all active projects to TIA Portal V15.1 or later, which includes long-term support and a corrected reconciliation engine.
- Pin firmware versions in source control. Tag the project archive with the exact TIA Portal version and the CPU firmware version. Date-related defects are far easier to diagnose when the engineering stack is reproducible.
- Document the leap-day test. For every S7-1200 firmware and TIA Portal combination that is in production, run a one-day regression test on 29 February (or with the PC clock temporarily set to that date) before the calendar reaches the next leap year.
- Maintain a SIMATIC Memory Card image. For critical machines, store a transfer card image of the project so that the CPU can be restored in minutes if a future date-related defect ever renders the live image inconsistent.
Field Commissioning Checklist
Use the following checklist during the kickoff of every S7-1200 project built with TIA Portal V11 SP2, regardless of whether the current calendar date is a leap day.
- Engineering PC date: not 29 February, NTP enabled.
- TIA Portal version: V11 SP2 confirmed; TIA V12 or later installed on at least one secondary laptop for migration testing.
-
CPU order number (MLFB): matches the hardware configuration in the project (for example,
6ES7214-1BG40-0XB0). - CPU firmware: V2.2 - V3.0.2 confirmed; note in the project archive whether a V4.x upgrade is planned.
- PG/PC interface: TCP/IP Auto, accessible nodes scan returns exactly one S7-1200 CPU.
- First download: clears the "modified" indicator on every block.
- Round-trip: edit, recompile, download, online compare = "No differences".
- Upload: completes without crashing TIA Portal.
-
Diagnostic buffer: no event IDs
0x13FE,0x35E1, or0x4300after first download. - Archive: zipped project backup with date, TIA version, and CPU firmware annotated.
Why does my S7-1200 project show "modified" on every block after I edit and re-download it?
The blue/orange modified indicator on every block is the signature of the TIA Portal V11 SP2 leap-day bug. It appears whenever the engineering PC clock is set to 29 February, because the offline/online reconciliation engine computes an off-by-one date token on leap day. Change the PC date to any value other than 29 February, recompile the project, and re-download. The indicators clear after the next Go online.
Is the S7-1200 CPU 1214C firmware V3.0.2 supported by TIA Portal V11 SP2?
TIA Portal V11 was released before the CPU 1214C firmware V3.0.2 was added to the device catalog. Some V11 SP2 installations cannot go online with a V3.0.2 CPU and instead report "Not compatible". Install the corresponding hardware support package (HWSP) for CPU 1214C FW V3.0.2 from the Siemens SiePortal, or migrate the project to TIA Portal V12 SP1 or later, which includes V3.0.2 in the base catalog.
Will TIA Portal V12 or later still produce the offline/online mismatch on 29 February?
No. The date-handling defect was corrected in TIA Portal V12. Even if the engineering PC is set to 29 February with V12 or later, the offline/online compare correctly reports "No differences" and the upload completes normally. The permanent fix is therefore to upgrade TIA Portal rather than rely on the date workaround.
My TIA Portal V11 SP2 crashes when I try to upload from the S7-1200. Is the program lost?
The program inside the CPU is intact and continues to run. The crash is a defect in the TIA Portal V11 SP2 upload routine that fires only when the engineering PC clock is set to 29 February. Close TIA Portal, correct the PC date to any day other than 29 February, reopen the project, recompile, and retry the upload. The CPU image will transfer to the offline project without further intervention.
What is the difference between resetting the CPU to factory defaults and upgrading the firmware to fix this issue?
A factory reset (Online & Diagnostics > Reset to factory settings) clears the user program, the hardware configuration, and the diagnostic buffer but does not change the firmware version. It cannot fix the date bug because the bug lives in TIA Portal, not in the CPU. A firmware upgrade to V4.0 or later replaces the CPU firmware with a release whose reconciliation routine accepts the corrected V11 SP2 checksum token. For a permanent fix, upgrade TIA Portal to V12 or later and flash the CPU firmware to V4.x; the combination eliminates the defect on both sides of the connection.