How Do I Count GRAFCET Cycles in Siemens TIA Portal?

Stefan Weidner6 min read
SiemensTIA PortalTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

The sequence runs, but the cycle total does not increment correctly, increments every scan, or returns to zero unexpectedly. Follow the request from the cycle-complete event through the sequence logic, the counter input, the CTU instance, and the CYCLE value. The decisive design choice is the event definition: increment once when a full GRAFCET cycle completes, not while a step remains active.

Where does the cycle-count request travel?

A cycle counter has a short data path. A field condition or internal sequence transition confirms completion. The program converts that condition into a single rising event. The event reaches the count-up input of CTU. The counter updates its current value, which the application reads as CYCLE.

Path element Reading to take Meaning Next check
Completion source Does the final transition become true? No change means the fault is before the counter. Check the physical or internal completion condition.
Event logic Is there one false-to-true change per cycle? A continuously true signal cannot represent repeated cycles. Check edge generation and sequence re-entry.
CTU count input Does it receive the completion edge? No edge means the call path or connection is wrong. Trace the logic between the transition and counter.
CYCLE Does the value increase by exactly one? Incorrect movement points to repeated edges, reset logic, or another writer. Inspect reset and write references.

Call the counter from logic that executes during normal PLC scans. Do not conditionally skip its call for long periods while expecting it to retain an accurate view of the input transition. The GRAFCET decides when a cycle is complete; the counter records that event.

Does the completion condition change cleanly?

Layer one comes first when completion depends on a sensor or other field input. Monitor the raw input before inspecting CTU. It must reach both logical states and remain stable enough for the PLC input processing and cyclic program to observe the intended transition.

If the raw input never changes, troubleshoot power, wiring, input status, and the device condition. If it changes several times during one mechanical event, the counter can receive several completion requests unless the sequence logic qualifies the signal. If it changes correctly but the GRAFCET transition does not, compare the raw input with every condition in that transition.

Observed reading Interpretation Action
Raw signal does not change The request stops at the physical or input layer. Correct the field condition or input path before editing the counter.
Raw signal changes, transition stays false Sequence conditions are blocking completion. Monitor each transition term and identify the false term.
Transition changes repeatedly One process completion produces multiple logical events. Qualify the event with the sequence state and a one-shot edge.
Transition produces one edge The source path is valid. Continue at the CTU input.

Are you counting scans, steps, or completed cycles?

Define the count event before placing the block. A PLC scan is one execution of cyclic logic. A GRAFCET step may remain active for many scans. A completed cycle is the transition from the end of the sequence back to its designated initial state. These are different events.

Incrementing while the final step is active counts executions, not cycles. For example, logic equivalent to CYCLE := CYCLE + 1 under a level condition adds one on every scan that the condition remains true. A CTU instead counts a false-to-true transition at its count-up input. That behavior fits cycle counting when the input becomes true once per completed sequence.

Candidate trigger Result Decision
Final step active May stay true across multiple scans. Use only after converting activation into a single event.
Final transition completed Represents departure from the end state. Preferred when it occurs once per full cycle.
Initial step active Also occurs at startup or manual reinitialization. Qualify it so startup is not counted as a completed cycle.
Manual increment command Counts operator requests rather than machine cycles. Keep separate unless that is the required definition.

Does CTU receive one rising edge per cycle?

Monitor the final transition, the signal connected to the count-up input, and CYCLE together. Run one controlled cycle. The transition must go from false to true once, and CYCLE must increase once. Before the next cycle, the count input must return false; otherwise the next completion cannot create another rising edge.

If the input toggles once but the value does not change, verify that the same CTU instance is called and monitored. A counter requires persistent instance state to remember the previous input state and its accumulated value. Reusing or reinitializing that state can make the result appear frozen or erratic.

If the value changes more than once, search for parallel completion paths, repeated sequence re-entry, and multiple calls that operate on the same counter state. If the monitored value changes correctly but an HMI value does not, the PLC counter is working; trace the HMI tag connection, update path, and displayed variable separately.

Where should counter initialization and reset occur?

Initialization is a control decision, not a permanent action attached to the initial step. Driving the reset input continuously while the initial step is active can hold the counter at zero whenever the sequence waits there. Reset from a deliberate event such as an operator reset command or a defined initialization pulse.

Choose startup behavior explicitly. If the count must start at zero after initialization, pulse the counter reset during that initialization. If the total must survive a restart, place the counter state in storage configured for the required persistence and do not connect routine startup logic to its reset. The installation requirement decides between those branches.

Reset setting Effect Typical pitfall
Reset held true CYCLE remains reset. Using the initial-step active bit directly.
One reset pulse Clears the total once, then releases counting. Pulse occurs again whenever the sequence returns home.
No startup reset Allows a retained total to continue. Assuming persistence without configuring the storage accordingly.
Manual reset event Clears the total on a deliberate request. A command that remains true can prevent new counts.

How do you implement and verify the resolving branch?

  1. Identify the transition that means the entire GRAFCET cycle has finished. Do not select a condition that merely means the final step is active.
  2. Confirm that the transition becomes true once during one controlled cycle and returns false before the next cycle.
  3. Create a completion event from that false-to-true transition. If the transition logic already produces one clean edge per cycle, use it directly; otherwise add edge-detection logic.
  4. Call one CTU instance from the normal cyclic program path. Connect the completion event to its count-up input.
  5. Expose the counter's current value as CYCLE. Use a data type and counter range appropriate for the required operating total; read the permitted range from the selected instruction and project configuration.
  6. Connect reset to a deliberate initialization or operator-reset event. Do not hold reset active throughout the initial GRAFCET step.
  7. Download the change and monitor the completion event, reset condition, and CYCLE simultaneously.
  8. Start with a known value, execute several complete cycles, and confirm that CYCLE advances by one after each completion and does not change while any step is merely waiting.
CycleCompleteEvent ----> CTU count-up input
ResetEvent ------------> CTU reset input
CTU current value -----> CYCLE

FAQ

How do I add a cycle counter to a GRAFCET in TIA Portal?

Use the transition that completes the full sequence to drive the count-up input of one CTU instance. Map its current value to CYCLE and confirm that the trigger produces one rising edge per cycle.

How do I initialize a CTU cycle counter?

Apply a single deliberate event to the CTU reset input. Do not use a continuously active initial-step bit, because it can hold CYCLE at zero whenever the GRAFCET waits in that step.

How do I verify that the counter increments only once?

Monitor the final transition, the CTU count input, reset, and CYCLE together. Execute several full cycles and verify one false-to-true count event and one increment after every completed cycle.

Back to blog