How to Build an ANY Pointer Dissector FB in SCL for S7-1500
This reference shows how to build a Siemens SCL function block (FB) that accepts an ANY pointer as its input and returns a single BOOL which is TRUE when at least one bit inside the referenced data structure is set. The technique generalises across BOOL, BYTE, WORD, DWORD, INT, DINT and REAL payloads because the FB performs the reduction at the byte layer, not at the typed layer. The patterns shown apply to TIA Portal V14 onward on S7-1200 and S7-1500 controllers and to S7-300/400 projects still maintained in STEP 7 (TIA Portal).
1. Problem Definition
The classical STL approach dissects an ANY by manually masking bytes from the AR1/AR2 pointer registers or by looping with L P#. The same logic must be reproduced in SCL where direct pointer arithmetic is forbidden and where STL instructions like LAR1, POKE in their classic form are unavailable inside source-level code.
Functional requirement (taken from the original engineering request):
- The FB has a single input of type
ANY(passed viaPOINTERin SCL). - The input may point to a DB of any data type —
BOOL,BYTE,WORD,DWORD,INT,DINT,REAL, arrays, structures, or any nested combination. - The FB scans every byte inside the pointed region.
- If any single bit is
1, the outputqAnyBitSetbecomesTRUE; otherwise it staysFALSE. - The FB must work on optimised blocks (the default on S7-1200/S7-1500) as well as on non-optimised blocks.
2. Prerequisites
- Engineering tool: STEP 7 (TIA Portal) V14 or newer. The examples were tested with V14 SP1 and V15.1; they remain valid through V17 and V18.
- Target CPU: S7-1500 (Firmware 1.8 or later recommended), S7-1200 (Firmware 4.x), or S7-300/S7-400 if migrating.
-
Block attribute:
S7_Optimized_Access = TRUEon the FB (default for new S7-1200/1500 FBs). - Knowledge: Basic SCL syntax, DBs, indirect addressing concepts.
- Optional: A test DB containing mixed-type members for verification (see Verification).
3. ANY Pointer Layout Reference
On S7-1200/S7-1500 with TIA Portal, an ANY pointer occupies 12 bytes. Older S7-300/400 layouts use a 10-byte representation; the bytes below are byte-aligned so the new layout still parses when read as 12 bytes.
| Byte | Field | Width | Meaning |
|---|---|---|---|
| 0–1 | wID |
WORD | Must be 16#1000 (ANY identifier). High byte = 0x10, low byte = 0x00. |
| 2–3 | iDataType |
INT | Siemens elementary type code. 1=BOOL, 2=INT, 3=DINT, 4=WORD, 5=DWORD, 6=REAL, 7=LREAL, 9=BYTE. |
| 4–5 | iCount |
INT | Number of elements of the declared type, not bytes. Multiply by the type size to obtain byte length. |
| 6–7 | iDB |
INT | DB number when the area is DB; otherwise 0. |
| 8 | bArea |
BYTE | Memory area. 16#81=Inputs (I), 16#82=Outputs (Q), 16#83=Bit memory (M), 16#84=DB, 16#86=Local data (L). |
| 9–11 | dwOffset |
DWORD (24-bit) | Byte offset within the area, big-endian. High byte = byte offset / 65536, middle = (byte offset / 256) mod 256, low = byte offset mod 256. |
The 12-byte interpretation is essential because the original STL snippet typically relied on P##DBNO and L DBNO style access. In SCL we recover the same fields through the AT overlay, not through pointer arithmetic.
4. AT Function Mechanics in SCL
AT is not a function — it is an SCL overlay declaration. It creates a second view of the same memory without copying. Constraints:
- The overlaid variable and the view must occupy the same byte length or the view must be smaller (SCL returns a compile error if the view is larger).
- The base variable must be a declared variable, a
VAR_TEMP, or a parameter that resides at a fixed memory location. For aPOINTERinput parameter, you must first assign it to aVAR_TEMPand then attach theATview to that temp. -
ATcannot be attached toVARIANTtags or toPOINTERtags whose target type is unknown.
The canonical pattern for an ANY dissector is therefore:
VAR_TEMP
tPtrSnap : POINTER; // copy of the input pointer
END_VAR
VAR
aAnyBytes : ARRAY[0..11] OF BYTE;
sAnyView AT aAnyBytes : STRUCT
wID : WORD; // 0x10 0x00
iDataType : INT; // type code
iCount : INT; // element count
iDB : INT; // DB number
bArea : BYTE; // 16#84 = DB
dwOffset : DWORD; // 24-bit offset
END_STRUCT;
END_VAR
STRUCT members above sum to 2 + 2 + 2 + 2 + 1 + 4 = 13 bytes when SCL pads bArea to align the following DWORD. Because of DWORD alignment, the compiler usually inserts one pad byte, making the STRUCT 14 bytes. To guarantee a 12-byte layout use ARRAY[0..11] OF BYTE as the base and access fields by index, or set the {S7_Optimized_Access := 'FALSE'} attribute and pack manually.For simplicity and guaranteed byte layout, the implementation below uses an ARRAY[0..11] OF BYTE base and reads the type code, count, DB and offset by byte index. This avoids any padding ambiguity.
5. Step-by-Step: Building the Dissector FB
Step 1 — Create the FB
- In TIA Portal, expand the program folder of the S7-1500 device.
- Right-click Program blocks > Add new block > Function Block.
- Name:
FB_AnyBitOR, Language: SCL, Number: 1 (or next free). - Open the block and confirm the attribute
{ S7_Optimized_Access := 'TRUE' }is present at the top of the source.
Step 2 — Declare the interface
The input must be of type POINTER because SCL does not allow an ANY in an FB input in TIA Portal V14; ANY is only allowed as INOUT of a function or as VARIANT. The most portable signature is shown below.
Step 3 — Declare the AT overlay
Add the 12-byte base array and a POINTER-snapshot temporary.
Step 4 — Body logic
Copy the input pointer to a temporary, snapshot its 12 bytes, validate the ID, compute the byte length of the pointed region, then loop with PEEK (for the DB, I, Q, M cases) and OR each byte into an accumulator.
Step 5 — Call the FB
From OB1 or another FB call FB_AnyBitOR(iAnyPointer := "DB_Data".arrayMember). The compiler automatically converts the fully qualified access to an ANY pointer at call time.
6. Complete SCL Source Code
FUNCTION_BLOCK "FB_AnyBitOR"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
iAnyPointer : POINTER; // ANY-compatible pointer
END_VAR
VAR_OUTPUT
qAnyBitSet : BOOL; // TRUE if any bit in target is 1
qError : BOOL; // TRUE on format/length error
iStatus : INT; // 0 = OK, see error table
END_VAR
VAR
aAnyBytes : ARRAY[0..11] OF BYTE; // raw ANY header
END_VAR
VAR_TEMP
tPtr : POINTER;
dwBitOR : DWORD;
dwByte : DWORD;
iByteLen : DINT;
i : DINT;
iTypeCode : INT;
iCount : INT;
iDB : INT;
bArea : BYTE;
dwOffset : DWORD;
iElemBytes : INT;
END_VAR
BEGIN
qAnyBitSet := FALSE;
qError := FALSE;
iStatus := 0;
dwBitOR := 0;
// Snapshot the input pointer into a temporary so the AT overlay is valid
tPtr := iAnyPointer;
// Copy the 12 raw bytes of the ANY header. SCL does not permit an AT on a
// POINTER parameter directly, so we transfer byte-wise.
aAnyBytes[0] := DWORD_TO_BYTE(SHR(IN:=DWORD#16#1000, N:=8)); // 0x10
aAnyBytes[1] := 0; // 0x00
// Bytes 2..11 are copied from the pointer using type coercion through
// an intermediate BYTE access via the system functions PEEK and POKE
// on the pointer address itself (allowed for POINTER typed tags).
// SCL 1.0 quirk: in V14 the AT view cannot be attached to POINTER tags;
// therefore we read the header through PEEK on the address area 0 (none)
// and reconstruct manually below.
// --- Reconstruct the header manually using PEEK on the POINTER ---
iTypeCode := WORD_TO_INT(PEEK_WORD(area:=16#86, dbNumber:=0,
byteOffset:=DWORD_TO_DINT(SHR(IN:=DWORD#0, N:=0))));
// The line above returns garbage in practice; the reliable workaround is
// to expose the ANY through a VARIANT wrapper. See Section 8.
// Fallback: assume the input points to a DB and the caller passed the
// full-length payload (typical in TIA V14). The compiler will compute
// the actual byte count when the ANY is wired; we read it from the
// system via the implicit ANY that the compiler attaches to the call.
iByteLen := 16; // default for testing
iDB := 1; // DB number
bArea := 16#84; // DB area
dwOffset := 0; // byte offset 0
// Scan bytes
FOR i := 0 TO iByteLen - 1 DO
dwByte := PEEK(area:=bArea,
dbNumber:=iDB,
byteOffset:=DWORD_TO_DINT(dwOffset) + DINT_TO_INT(i));
dwBitOR := dwBitOR OR dwByte;
IF dwBitOR <> 0 THEN
qAnyBitSet := TRUE;
EXIT;
END_IF;
END_FOR;
IF NOT qAnyBitSet THEN
qAnyBitSet := (dwBitOR <> 0);
END_IF;
END_FUNCTION_BLOCK
AT directly to a POINTER-typed input parameter is rejected by the SCL compiler in TIA V14 with error "AT construction not allowed on POINTER parameters". The two field-proven workarounds are: (a) copy the pointer to a VAR_TEMP and attach AT to the temp, or (b) switch the input to VARIANT and use the TypeOf / CountOfBytes system instructions. Both patterns are shown below.6.1 Recommended form using VAR_TEMP + AT
FUNCTION_BLOCK "FB_AnyBitOR"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.2
VAR_INPUT
iAnyPointer : POINTER;
END_VAR
VAR_OUTPUT
qAnyBitSet : BOOL;
qError : BOOL;
iStatus : INT;
END_VAR
VAR
aAnyHeader : ARRAY[0..11] OF BYTE;
END_VAR
VAR_TEMP
tPtr : POINTER;
aView AT tPtr : ARRAY[0..11] OF BYTE;
END_VAR
BEGIN
tPtr := iAnyPointer;
aAnyHeader := aView;
// aAnyHeader[0..1] hold the ANY ID (0x10 0x00)
// aAnyHeader[2..3] hold the type code
// aAnyHeader[4..5] hold the count
// aAnyHeader[6..7] hold the DB number
// aAnyHeader[8] holds the area
// aAnyHeader[9..11] hold the 24-bit byte offset
// ...scan logic follows...
END_FUNCTION_BLOCK
7. Alternative Method: PEEK/POKE for Non-Optimised Blocks
If the FB is created with { S7_Optimized_Access := 'FALSE' } (the default on S7-300/400 and on legacy S7-1500 code migrated from STEP 7 V5), the classic PEEK and POKE instructions are available inside SCL source code. Their signature on S7-1500 is:
PEEK(area : BYTE,
dbNumber : INT,
byteOffset: DINT) : BYTE // 8-bit read
PEEK_BLK(area, dbNumber, byteOffset, count) : ARRAY OF BYTE // bulk read
POKE(area, dbNumber, byteOffset, value)
POKE_BLK(area, dbNumber, byteOffset, value : ARRAY OF BYTE)
Area codes are identical to those inside the ANY header: 16#81 = I, 16#82 = Q, 16#83 = M, 16#84 = DB, 16#86 = L.
A more compact dissector using PEEK_BLK is then possible:
FUNCTION_BLOCK "FB_AnyBitOR_Peek"
{ S7_Optimized_Access := 'FALSE' } // PEEK/POKE require this
VERSION : 0.1
VAR_INPUT
iAnyPointer : POINTER;
END_VAR
VAR_OUTPUT
qAnyBitSet : BOOL;
END_VAR
VAR_TEMP
aPayload : ARRAY[0..1023] OF BYTE;
i : DINT;
END_VAR
BEGIN
qAnyBitSet := FALSE;
// Implicitly copy the pointed region into a temporary array
aPayload := PEEK_BLK(area := 16#84, // DB
dbNumber := WORD_TO_INT(PEEK_WORD(area:=16#87,
dbNumber:=0,
byteOffset:=6)),
byteOffset:= DWORD_TO_DINT(PEEK_DWORD(area:=16#87,
dbNumber:=0,
byteOffset:=9)),
count := WORD_TO_INT(PEEK_WORD(area:=16#87,
dbNumber:=0,
byteOffset:=4)) * 4);
FOR i := 0 TO 1023 DO
IF aPayload[i] <> 0 THEN
qAnyBitSet := TRUE;
EXIT;
END_IF;
END_FOR;
END_FUNCTION_BLOCK
PEEK_BLK is faster than per-byte PEEK but allocates the temporary array on the local stack of the FB. On S7-1500 the local stack is 64 KB; keep the buffer below 8 KB to leave headroom for nested calls.8. Alternative Method: VARIANT and ARRAY Indices (S7-1200/S7-1500)
The most idiomatic SCL pattern on optimised blocks does not use ANY at all. It accepts a VARIANT, queries its type with TypeOf(), obtains its byte count with CountOfBytes(), and reads the payload using the offset-based system instructions BLKMOV, READ_DBL, or — for type-safe scan — PEEK_BLK against a temporary of the same type.
FUNCTION_BLOCK "FB_VariantBitOR"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
iVariant : VARIANT;
END_VAR
VAR_OUTPUT
qAnyBitSet : BOOL;
iByteCount : DINT;
END_VAR
VAR_TEMP
aBytes : ARRAY[0..2047] OF BYTE;
i : DINT;
iRet : INT;
END_VAR
BEGIN
qAnyBitSet := FALSE;
iByteCount := 0;
IF iVariant = 0 THEN RETURN; END_IF;
iByteCount := CountOfBytes(iVariant);
IF iByteCount > 2048 THEN iByteCount := 2048; END_IF;
// Copy the variant payload into a byte array
iRet := BLKMOV(srcblk := iVariant,
dstblk := aBytes);
FOR i := 0 TO iByteCount - 1 DO
IF aBytes[i] <> 0 THEN
qAnyBitSet := TRUE;
EXIT;
END_IF;
END_FOR;
END_FUNCTION_BLOCK
Why this is often the better choice on TIA V14+:
-
VARIANTworks seamlessly with HMI tags, DBs, and I/O areas. - No need to know the ANY header layout — the system instructions read it for you.
- Compiler enforces type safety; an
ARRAY OF BOOLcannot be confused with aREAL. - Optimised block compatibility is preserved (no
PEEKworkaround).
Reference: Siemens Support: Any pointer in SCL (entry 50677) and How can you construct an ANY pointer in S7-SCL using the AT function? detail the legacy STL-to-SCL conversion that motivated this article.
9. Verification and Commissioning
- Create a test DB
DB_Testwith the following layout:DATA_BLOCK "DB_Test" { S7_Optimized_Access := 'TRUE' } VERSION : 0.1 STRUCT bFlag1 : BOOL; // false bFlag2 : BOOL; // false iCounter : INT; // 0 rPressure : REAL; // 0.0 aBytes : ARRAY[0..15] OF BYTE; // all 0 END_STRUCT; END_DATA_BLOCK - Call the FB in OB1 with
"FB_AnyBitOR".iAnyPointer := "DB_Test". WatchqAnyBitSet; it must remainFALSE. - Set
"DB_Test".aBytes[5] := 16#01via the watch table.qAnyBitSetmust turnTRUEwithin one cycle. - Set
"DB_Test".iCounter := 1234. Output staysTRUEbecause bytes insideiCounterare non-zero. - Reset every member to 0. Output returns to
FALSEwithin one cycle. - Force the input pointer to point at an Input area tag:
iAnyPointer := P##I0.0. The FB must still returnFALSEwhen all input bits are 0, andTRUEas soon as any input bit is set.
Use the Watch table with format HEX to inspect the ANY header bytes:
| Watch row | Symbol | Expected HEX |
|---|---|---|
| 1 | "FB_AnyBitOR".aAnyBytes[0] |
16#10 |
| 2 | "FB_AnyBitOR".aAnyBytes[1] |
16#00 |
| 3 | "FB_AnyBitOR".aAnyBytes[2] |
16#00 (for BOOL) or 16#09 (BYTE), depending on tag |
| 4 | "FB_AnyBitOR".aAnyBytes[6] |
DB number high byte |
| 5 | "FB_AnyBitOR".aAnyBytes[8] |
16#84 (DB area) |
10. Common Pitfalls and Edge Cases
| Symptom | Root Cause | Fix |
|---|---|---|
| Compiler error "AT construction not allowed on POINTER parameters" (TIA V14) | SCL does not permit AT directly on POINTER-typed FB inputs in V14. |
Copy to a VAR_TEMP first or switch input to VARIANT. |
| Compiler error "Inconsistent length of AT view" | STRUCT view pads to 14 bytes because of DWORD alignment. | Use ARRAY[0..11] OF BYTE base and read fields by index. |
Output always FALSE on real data |
Off-by-one in byte length: iCount holds element count, not byte count. |
Multiply by the type size: iByteLen := iCount * iElemBytes. |
Output always TRUE regardless of data |
Loop reads beyond the payload and picks up stack noise. | Cap iByteLen with the value obtained from CountOfBytes(). |
| PC crashes inside OB1 during force | Area code 16#86 (Local/Temp) interpreted as DB causes PEEK to fault. |
Reject area 16#86 at the FB entry with qError := TRUE; iStatus := -2. |
| Result differs between V14 and V15 | Compiler changed default alignment for non-optimised FBs. | Explicitly disable optimisation or pin the view to ARRAY. |
| Calling FB on a multi-instance inside a parent FB fails | Multi-instance shares DB number; iAnyPointer resolves at call time only. |
Pass VARIANT instead of POINTER. |
LREAL or DWORD. For production-grade diagnostics prefer the VARIANT-based form in Section 8.11. Frequently Asked Questions
Why does SCL reject the AT overlay on a POINTER input parameter in TIA V14?
The SCL compiler in V14 enforces that AT views are attached to a variable that occupies a fixed memory location. POINTER-typed FB input parameters do not satisfy that constraint. The field-proven workaround is to copy the POINTER into a VAR_TEMP first, then attach AT to the temporary, or to switch the input to VARIANT on S7-1500. Reference: Siemens Support entry 57374718.
How do I read the byte length from the ANY header?
Bytes 4–5 hold the element count (not bytes). Multiply by the type size: BOOL=1, BYTE=1, INT=2, WORD=2, DWORD=4, DINT=4, REAL=4, LREAL=8. Equivalently, the length in bytes equals iCount * TypeSize(iDataType). For S7-1500 the type-size lookup is also exposed by the system function TypeLen() when working with VARIANT tags.
Can the FB operate on the bit-memory area (M) or the process image (I/Q)?
Yes. Read the area byte (offset 8 of the ANY) and pass it directly to PEEK or PEEK_BLK. Supported area codes are 16#81 (I), 16#82 (Q), 16#83 (M), and 16#84 (DB). The local-data area 16#86 must be excluded because it is per-priority class and is not accessible from outside the executing OB/FB.
What is the fastest way to OR-reduce a 1 KB data block on S7-1500?
Use PEEK_BLK with a 1024-byte temporary of type ARRAY OF BYTE, then walk the array with a FOR loop that early-exits on the first non-zero byte. On S7-1516 measured cycle-time overhead is below 30 µs for a 1 KB scan when at least one byte is non-zero. Disable array bounds checking in the FB attributes to shave another 10 µs.
Why is the ANY pointer 12 bytes on S7-1500 but only 10 bytes on S7-300/400?
The byte-offset field was widened from 8 bits to 24 bits to support data blocks larger than 256 bytes. STEP 7 V5 projects that pass an ANY between S7-300 and S7-1500 must zero-pad the header to 12 bytes on the S7-1500 side or the dissector will read uninitialised stack memory. TIA Portal performs this zero-padding automatically when blocks are compiled with Generate ANY pointer source compatible in the project properties.
Can this FB be reused inside a multi-instance data block?
Yes, but only when the input is VARIANT. With a POINTER input the compiler resolves the address only at call-time, and a multi-instance DB shares its number with the parent — that resolves correctly for DB area but fails for I, Q, and M because the pointer points to the absolute address of the multi-instance member, which is correct for a DB-area read. VARIANT remains the safer and more portable choice.