How to Update LOGO!Soft Comfort to V8 for LOGO! 6ED1052-0BA6

David Krause14 min read
HMI ProgrammingSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

Connecting an older engineering laptop to a Siemens LOGO! 6ED1052-1FB00-0BA6 module is the most common field-encountered version-mismatch failure on the LOGO! platform. The 0BA6 suffix identifies the first-generation LOGO! 8 base unit (released 2014), while the engineering tool that originally programmed the panel may still be LOGO!Soft Comfort (LSC) V6.1 - a version that pre-dates the LOGO! 8 firmware protocol and cannot exchange program data with a 0BA6 over any physical interface. The repair is not a cable swap and not a driver reload; the only supported remedy is to upgrade the engineering software to LSC V8.4.1 (or later within the V8 stream) before any PC-to-LOGO! session can be initiated.

This article documents the complete migration path from LSC V6.x to LSC V8 while preserving license entitlements, explains why the historical LOGO! PC cable is no longer sufficient, and lays out a Windows 10 64-bit compatibility strategy that uses the native installer plus a virtual-machine fallback for any project that absolutely requires a pre-V7 toolchain (such as training-program-based or customer-mandated legacy deployments).

Hardware Identification: Decoding the 6ED1052-1FB00-0BA6 Part Number

The Siemens order code carries three fields that determine compatibility:

Field Value Interpretation
Series 6ED1052 LOGO! 8 base unit product family
Function group 1FB00 1 = digital inputs/outputs; FB = with Ethernet and integrated display
Sub-version -0BA6 Sixth-generation LOGO! (LOGO! 8, initial hardware release)

The 0BA6 hardware has the following connector and indicator layout relevant to the PC connection:

  • One front-mounted RJ45 Ethernet socket (10/100 Mbit/s) on the upper face of the unit.
  • One mini-USB service port on the lower right face for the LOGO! USB cable.
  • A FAIL LED that flashes red/orange when the firmware protocol hand-shake between the LOGO! base module and LSC is in progress.
Field tip: 0BA6 devices report firmware 0BA6.x.x on the module display via LOGO! menu Info > Module. Devices that ship today from authorized Siemens stock may carry 0BA7 or 0BA8 firmware even though the printed part number on the housing remains 6ED1052-1FB00-0BA6. This is normal - the housing part number is hardware frozen while the firmware is field-flashable. LSC V8 supports all three firmware revisions; LSC V6.1 supports none of them.

Reference: Siemens Industry Online Support entry for the 6ED1052 family.

LOGO!Soft Comfort Version Compatibility Matrix

The protocol that LSC uses to upload, download, and monitor programs changed substantially when the LOGO! 8 platform was introduced. Each LSC version knows only the firmware revisions that existed at the time of its release. The compatibility envelope is:

LSC Version LOGO! Hardware Supported Initial Release Notes
V6.0 / V6.1 0BA0 - 0BA4 ~2005-2009 Original LOGO! Classic and LOGO! 5 era; 32-bit installer only
V7 0BA0 - 0BA5 ~2012 Introduces LOGO! 5 (0BA5) protocol; cannot communicate with 0BA6+
V8 0BA0 - 0BA6 2014 First version with LOGO! 8 protocol; full Ethernet support
V8.1 0BA0 - 0BA7 2017 Adds LOGO! 8.1 (0BA7) protocol extensions
V8.2 / V8.3 0BA0 - 0BA8 2021 Supports LOGO! 8.3 (0BA8); current supported GA level
V8.4.1 0BA0 - 0BA8 (all) 2023 Recommended install for any greenfield field laptop
Critical: If your engineering PC ships with LSC V6.1, that version will never connect to a 6ED1052-1FB00-0BA6 regardless of how many times the cable is reseated, drivers are reinstalled, or Windows compatibility mode is invoked. The LSC version must be upgraded.

Prerequisites

  • Windows 7 SP1 / Windows 10 (64-bit recommended, 32-bit acceptable) or a current Windows 11 distribution that still tolerates the legacy COM-port enumeration.
  • Administrator credentials on the engineering laptop (the LSC installer writes to Program Files\Siemens\LOGOComfort_V8 and registers COM/DCOM handlers).
  • Source materials one of the following: (a) original V3.1 CD of LOGO!Soft Comfort, (b) an existing licensed install of any earlier LSC version on the same machine, or (c) the appropriate purchased upgrade entitlement from Siemens SIOS.
  • Network access for the upgrade download (default site: SIOS entry 109769180 - LOGO!Soft Comfort download).
  • An active Siemens customer-account login to obtain the latest Upgrade executable.
  • For Ethernet connection: a Cat5e patch cable, the IP address of the LOGO! module (factory default 192.168.0.4 / subnet 255.255.255.0), and a free Ethernet port on the engineering laptop.
  • For USB cable connection: the LOGO! USB cable (6ED1057-1AA01-0BA0); the older LOGO! PC cable (serial or COM-port) used with 0BA0-0BA4 units is not wired for the LOGO! 8 mini-USB service port and must not be substituted.

Step-by-Step Upgrade from LOGO!Soft Comfort V6.1 to V8.4.1

  1. Extract the existing license. If V6.x is still installed on the engineering PC, note the serial number of the original full license under Help > About. Copy the .LSCW license container from %LOCALAPPDATA%\Siemens\LOGOComfort to a USB stick as a backup. The license file is re-used by V8 - it does not need to be re-purchased for in-place upgrades.
  2. Verify your entitlement for the upgrade. The free upgrade path is documented under SIOS 109769180. If an upgrade was purchased separately, locate the license certificate (six-character product key) that came in the original shipment box.
  3. Activate / sign in to Siemens SIOS using the customer center account that owns the license. If the original license holder is no longer with the company, the legal entity owning the license must request a transfer through Siemens Customer Support.
  4. Download the V8.4.1 V8.4 Upgrade + the V8.4.1 hotfix file from the SIOS download area. The file naming follows the convention LOGOComfort_V8_4_1.zip. Verify the SHA-256 checksum against the value published on the SIOS page to prevent tampered executables.
  5. Disable antivirus during installation. Some endpoint security suites flag the LSC installer as a legacy WMI author; this is a false positive, but installation can fail under aggressive HIPS profiles.
  6. Install the V3.1 CD or full V8 install first if no LSC version is currently present on the target PC. Right-click Setup.exe, Run as Administrator. Accept the license terms. Default install directory: C:\Program Files\Siemens\LOGOComfort_V8\.
  7. Apply the V8.4.1 upgrade over the existing V8 base by running the upgrade MSI. Do not uninstall V6.x first - the upgrade installer reads the V6.x license registry keys to derive a migration key that re-activates V8 against your existing license; uninstalling V6 destroys those keys.
  8. Reboot when prompted. The reboot is required for the new WinUsb driver and the LSC service LOGOComfortRemoteService to bind correctly.
  9. Launch LOGO!Soft Comfort V8. On first run, choose Tools > Options > Interface and confirm the PC interface is set to the LOGO! USB cable (default) or Ethernet (selectable). The IP address of the LOGO! module must be reachable by ping 192.168.0.4 when using Ethernet.
  10. Convert older projects. Open any .lsc file saved in V6.1 - LSC V8 will auto-elevate to .lscp on save. Lift-and-shift projects target 0BA4 hardware, not 0BA6; conversion warnings will appear if the source program references blocks unsupported by the target module.

License Transfer: PC-to-PC Migration

Older LSC licenses are authorized against an immutable fingerprint of the host PC (CPU + BIOS + HDD serial). When the engineering PC is replaced, that fingerprint changes, and the license stops validating. To move an LSC V8 license from one PC to another:

  1. From the old PC, open LSC V8 and select Help > License > Activate License > Transfer License back to License Server. The license is returned to the Siemens activation server.
  2. Install LSC V8 on the new PC using the steps above.
  3. Activate the returned license from Help > License > Activate License. If the license returned cannot be reactivated because the old PC is offline, request a manual reset via Siemens Customer Support with the original Certificate of License PDF.
Pitfall: If LSC reports License not valid for this component after the upgrade, the install media used is the demo version (default V8.x demo 30-day trial). Confirm the V3.1 CD is the licensed master and not a marketing redemo disc.

Cable Selection and Driver Verification

The 0BA6 LOGO! module has two distinct PC interfaces. They are not interchangeable in the field:

Interface Hardware Siemens Order Code Driver Required on Windows 10 64-bit
Ethernet Standard Cat5e patch N/A - customer supplied None - standard NDIS driver
USB (preferred cable) LOGO! USB cable (suppress shield) 6ED1057-1AA01-0BA0 WinUsb / Siemens USB-Serial composite
USB (legacy LOGO! PC cable) DB9-style 0BA0-0BA4 cable 6ED1057-1AA00-0XA0 (legacy) N/A - electrical incompatibility

Driver verification procedure:

  1. Connect the LOGO! USB cable 6ED1057-1AA01-0BA0 to a free USB port. Windows Device Manager should display LOGO! USB Cable (COMx) under Ports (COM & LPT).
  2. If the device appears as Unknown Device, right-click and Update Driver > Search automatically for drivers. The Siemens USB-Serial driver is bundled with LSC V8 in C:\Program Files\Siemens\LOGOComfort_V8\Driver\.
  3. Confirm the assigned COM port number is below 10. LSC's serial frame parser occasionally has trouble resolving high COM numbers (COM36+). If Windows assigns a high port, change it via Device Manager > Port > Properties > Advanced > COM Port Number.

Windows 10 64-bit Compatibility Workarounds

The LSC V8 installer is signed and officially supported on Windows 10 64-bit. The most common failure modes are:

Symptom Likely Cause Workaround
Setup halts at "WindowsSideByState error 1406" MaxPathName registry mismatch Apply Microsoft KB workaround KB2263998
LSC starts, then crashes on selecting menu Help Older .NET runtime call to .NET 2.0 assembly Install .NET Framework 3.5 via Windows Features
PC interface dropdown is greyed out LOGOComfortRemoteService not running Run services.msc -> set LOGOComfortRemoteService to Automatic and start it
COM port visible to Windows but invisible to LSC LSC enumerates COM1-COM16 only in some builds Reassign COM port <= COM10
Win 10 64-bit installer reports "LSC version V6 not supported on this OS" V6.x is only 32-bit and pre-dates x64 support Do NOT downgrade; upgrade directly to V8 (this is the root fix)
Forcing 32-bit mode is no longer needed: LSC V8 ships as both 32-bit and 64-bit binaries; the 64-bit installer will run natively on Windows 10 64-bit. The historical advice to force 32-bit via NTVDM was specific to LSC V6.x and is not required for V8.

Ethernet Connection: Preferred on 0BA6 / 0BA7 / 0BA8

The 0BA6 module integrates a 10/100 Mbit Ethernet controller accessible from any system that can route to 192.168.0.4 / 255.255.255.0. For new installations Ethernet is the preferred PC-to-LOGO! channel because it is electrically robust, immune to USB driver regressions, and survives LSC version upgrades without cable swaps.

  1. Set the engineering laptop IP address to 192.168.0.50 / 255.255.255.0 via the Windows Network & Sharing Center > Ethernet > Properties > IPv4.
  2. Plug a Cat5e patch between the laptop and the RJ45 socket on the top of the LOGO! module.
  3. Verify link layer: ping -t 192.168.0.4 should receive a reply within 10 ms.
  4. In LSC V8, choose PC > Interface > Ethernet. LSC will auto-discover the LOGO! on the subnet as a UDP broadcast. Click Connect; the firmware version is read back as 0BA6 or later.
  5. If auto-discovery fails, manually enter the IP and re-attempt.
Wrong factory IP after firmware update? Some 0BA6/0BA7 modules ship with DHCP fallback enabled. After a factory reset on LOGO! menu > Setup > Network, the LOGO! returns to 192.168.0.4. If you have previously changed it, hold ESC + OK > Setup > Network > Reset to recover the default.

Virtual Machine Fallback for Legacy LSC Versions

If an absolute requirement forces the use of LSC V6.x (for example, when reproducing a printed training document or a customer's audited legacy program step), install the legacy version in a Windows 7 32-bit VM rather than the host OS:

  1. Download a Windows 7 32-bit ISO from your enterprise VLSC portal or Microsoft evaluation media.
  2. Provision a VM using Oracle VirtualBox, VMware Workstation, or Hyper-V. Allocate 2 vCPU, 4 GB RAM, 30 GB dynamic VHDX. Enable USB passthrough for the host's USB ports where the LOGO! USB cable will live.
  3. Disable Windows 7 hibernation, disable Windows Update, and disable UAC inside the VM - LSC V6 was written before UAC and the installer can write to non-virtualized Program Files if UAC redirects fail.
  4. Install the LOGO! USB cable driver inside the VM using the bundled driver on the V6.1 CD, even though Windows 7 will attempt to auto-install its own generic FTDI driver. Replace the generic driver manually using Device Manager > Update Driver > Let me pick from a list > Have Disk.
  5. Route the VM to the same subnet (192.168.0.x) as the LOGO! module by selecting Bridged Adapter in the VM network settings. The VM can then connect to the LOGO! using the V6 tools over Ethernet just as it does over USB.

Take a clean snapshot after a successful install. The VM becomes a portable legacy programming environment that you can ship to any PC without polluting the user's host OS with V6-era COM redirection components.

Connection Verification Procedure

After the upgrade and cable work is done, run this in-line checklist before declaring the migration complete:

  1. In LSC V8: PC > Online Test should show PC connected with LOGO! 0BAx along with the firmware revision detected. If the firmware is displayed as unknown but a model is detected, the LSC version is older than the firmware - upgrade LSC to V8.4.1 immediately.
  2. Send a PC > Upload from LOGO! command. A green status bar confirms round-trip read.
  3. Send a PC > Download to LOGO! command with a non-empty program. The LOGO! will restart into stop mode and back into run mode automatically.
  4. Watch the LOGO! display: the Online icon (a small 'eye' in the top right corner of the LOGO! display) confirms LSC is connected.
  5. From a terminal run wmic nic where 'NetEnabled=TRUE' get IPAddress and confirm the engineering laptop has the address 192.168.0.x (Ethernet path).

Field-Proven Caveats and Troubleshooting Matrix

Symptom Root Cause Correction
LSC V6.1 installed; cannot see 0BA6 LSC V6.1 pre-dates LOGO! 8 firmware protocol Upgrade LSC to V8.4.1
Old LOGO! PC cable (DB9) does not fit 0BA6 Hardware revision changed mini-USB jack Use 6ED1057-1AA01-0BA0 USB cable or Ethernet
LSC V8 installer refuses to start on Win 10 64-bit User Account Control silent install Right-click Setup.exe > Run as Administrator
Firmware update of 0BA6 fails from V8.3 to a later release FOAT (firmware update over Ethernet) requires the "Admin" password held by the LOGO! Set the Admin password via the LOGO! display before attempting FOAT
Memory card write of a V6 program rejects when loaded on V8 Older "REALTIME CLOCK" block signatures Open in V8, "Save As" - V8 rewrites the header and the card is recognized
License popup says "Component not found" V6 license registry was scrubbed Reinstall original V6 CD first to repopulate the registry, then apply V8 upgrade
LSC reports "Connection could not be established" over USB even after fixes High COM port assignment (>COM16) Reassign to COM1-COM9
V8.4.1 releases after V8.4 a slow Ethernet poll at startup DNS-SD enumeration (auto-discovery default) Disable auto-discovery under Tools > Options > Communication if device fixed-IP

Safety and Operational Considerations

Before initiating a download from the engineering laptop, place the controlled process in a safe state according to the P&ID. A LOGO! download interrupts program execution for up to two seconds and forces all outputs to their configured fallback states during the restart cycle. LSC V8 prompts for confirmation; do not bypass this prompt. Reset any watchdog timers and interlocks that the Engineering Workstation may have suppressed during the upload/download phase.

FAQ

Will LOGO!Soft Comfort V8.4.1 connect to a LOGO! 0BA5 module?

Yes. LSC V8.4.1 supports every LOGO! from 0BA0 through 0BA8 inclusive. Programs authored in LSC V6.x against a 0BA5 device open correctly in V8.4.1 with a project conversion prompt on save.

Can LSC V6.1 be installed and run on Windows 10 64-bit?

Effectively no. LSC V6 was a 32-bit installer for an era without .NET Framework 4.x and typically installs with broken COM-port redirection and unreliable USB-serial signalling on modern Windows. Use LSC V8 for any current field laptop; if a legacy V6 toolchain is mandatory, run it inside a Windows 7 32-bit virtual machine.

Which cable do I need for the Siemens LOGO! 6ED1052-1FB00-0BA6?

Use the LOGO! USB cable 6ED1057-1AA01-0BA0, or a standard Cat5e Ethernet cable into the onboard RJ45 socket. The legacy LOGO! PC cable used for 0BA0-0BA4 is electrically incompatible with the 0BA6 mini-USB service port and must not be substituted.

How do I transfer an LSC license to a new PC?

Return the license from the old PC via Help > License > Activate License > Transfer License Back, install LSC on the new PC, and re-activate. If the old PC is offline, contact Siemens Customer Support with your Certificate of License to request a manual reset.

Does the LOGO! 6ED1052-1FB00-0BA6 support connection over Ethernet?

Yes. The 0BA6 base unit ships with an integrated 10/100 Mbit Ethernet interface at the default IP 192.168.0.4. Configure the engineering laptop on the 192.168.0.x subnet, then select PC > Interface > Ethernet in LSC V8 - the LOGO! will be auto-discovered.

What is the difference between 0BA6, 0BA7, and 0BA8?

All three are LOGO! 8 series. 0BA6 is the original LOGO! 8 hardware (2014), 0BA7 is the LOGO! 8.1/8.2 revision, and 0BA8 is LOGO! 8.3 (current generation). The printed order code 6ED1052-1FB00 remains hardware-frozen, but the internal firmware is flashable; LSC V8.4.1 supports all three firmware revisions.