Implementing Ramp Functions on Siemens S7-300/400 Analog Outputs
Overview
A ramp function generator (RFG) shapes an analog output so the controlled variable changes at a defined rate instead of stepping. It is the most-requested missing block on the SIMATIC S7-300 and S7-400 platforms: STEP 7 V5.x does not ship a dedicated Ramp function block in the standard library the way the F-TM Servodrive in TIA Portal exposes one in firmware (see the TIA Portal ramp-function generator documentation for the modern equivalent). On the classic PLCs the engineer must build the RFG in an FB and trigger it from a cyclic-interrupt OB, then drive the value to the hardware with a peripheral write (PQW) because analog-output modules are mapped outside the process image.
Use cases for an analog-output ramp on a SIMATIC controller include:
- Valve position reference (avoid water hammer on hydraulic and pneumatic actuators)
- VFD / soft-starter speed reference (limit dV/dt on the analog setpoint input)
- Heater phase-angle setpoint (limit thermal shock on cartridge heaters and IR emitters)
- DC drive armature reference (limit inrush on the motor)
- PID controller output (smooth setpoint changes between recipe steps)
The physical law is always the same: dV/dt = constant between two setpoints. The implementation differs only in (a) the integration timebase, (b) the slope units (engineering units per second, raw counts per cycle, or percent per scan), and (c) whether the ramp is computed in the PLC, in the drive firmware (e.g. Sinamics r0106 / r0107), or in a dedicated hardware module (F-TM Servodrive).
Why Analog Outputs Use Peripheral Addressing (PQW)
| Instruction | Operand area | Hardware effect | Correct use |
|---|---|---|---|
T PQW 272 |
Peripheral output (PAA) | Immediate write to module during scan | Analog output channels in user program |
T QW 272 |
Process image output (PA) | Writes the snapshot; the module is not updated until the next OB1 image update | Digital outputs in OB1; never analog output modules |
L PIW 272 |
Peripheral input (PED) | Reads directly from the module ADC | Reading analog input status byte, diagnostics |
T PQB 272 |
Peripheral output byte | Direct byte write | Forcing a single AO channel of an 8-channel module |
T QW 272. The CPU accepts the instruction, the compiler does not warn, and the value silently never reaches the DAC. The field device sits at zero, full-scale, or last-value depending on the module's substitute-value behaviour. If you see the right number in a VAT table on QW 272 but the field device is at 4 mA, the bug is always the missing P.To find the actual PQW address for an analog output module, open the S7 project in SIMATIC Manager, expand the S7-300 / S7-400 station, double-click the SM332 / SM432 slot, and read the "Addresses" line in the object properties. The address is set automatically by the slot rule, or it can be manually assigned; the same value (with a leading P) is what the user program must use.
Hardware Prerequisites: SM332 and SM432 Output Modules
Before implementing the ramp, the analog output channel must be configured correctly in HW Config. Each SM332 and SM432 channel supports a configurable output type, range, and substitute value. A wrong output range is the second most common cause of an apparently dead analog output.
| Module | MLFB | Channels | Resolution | Configurable ranges |
|---|---|---|---|---|
| SM332 | 6ES7332-5HB01-0AB0 | 2 AO | 12-bit + sign | ±10 V, 0-10 V, ±20 mA, 0/4-20 mA |
| SM332 | 6ES7332-5HD01-0AB0 | 4 AO | 12-bit + sign | ±10 V, 0-10 V, ±20 mA, 0/4-20 mA |
| SM332 | 6ES7332-5HF00-0AB0 | 8 AO | 12-bit + sign | ±10 V, 0-10 V, ±20 mA, 0/4-20 mA |
| SM332 | 6ES7332-7ND02-0AB0 | 8 AO | 16-bit | ±10 V, 0-10 V, 0/4-20 mA |
| SM332 | 6ES7332-8TF00-0AB0 | 8 AO high-speed | 16-bit | ±10 V, 0-10 V, ±20 mA, 0/4-20 mA |
| SM432 | 6ES7432-1HF00-0AB0 | 8 AO | 16-bit | ±10 V, 0-10 V, 0/4-20 mA |
Two resolution ranges matter for the ramp math:
- 12-bit modules (SM332 5H-series): Bipolar nominal range ±27648 counts. The Siemens documentation states that values up to ±32511 are representable, but only ±27648 is the rated nominal; values above 32511 clip the DAC. Unipolar 0-10 V uses 0-27648 counts; 4-20 mA uses 0-27648 with 4 mA = 0 counts, 20 mA = 27648 counts.
- 16-bit modules (SM332 7ND/8TF, SM432): Bipolar nominal range ±27648 as well, but with 15-bit effective resolution. The mapping is identical; the difference is accuracy (0.3% on 12-bit, 0.1% on 16-bit) and step response time.
The Siemens S7-300 Module Data manual (entry 8859629) and the S7-400 Module Data manual (entry 1117740) document the full electrical ratings, settling time, and diagnostics. For a 0.3 s ramp on a 4-20 mA valve reference, a 12-bit SM332 is sufficient. For a 0-10 V reference on a high-resolution heater controller, the 16-bit SM332 7ND02 is preferred.
Siemens Standard Library: What Is and Is Not Available
STEP 7 V5.x ships several relevant FBs in the standard library, but none of them is a dedicated ramp generator. The available building blocks are:
| Block | Library path | Function | Use in ramp |
|---|---|---|---|
| FB41 / SFB41 CONT_C | Standard Library > PID Control Blocks | PID controller | Generates the target; ramp sits in front of it |
| FB42 / SFB42 CONT_S | Standard Library > PID Control Blocks | Step controller with pulse output | Not relevant for analog ramp |
| FB43 / SFB43 PULSEGEN | Standard Library > PID Control Blocks | Pulse-width modulator for CONT_C | Not relevant for analog ramp |
| FC1, FC2, FC3, FC4, FC5 | Standard Library > TI-S7 Converting Blocks | IEC 61131-3 conversions, scale, integrate | FC3 (Integrator) can be reused as the ramp integrator |
| OB35 | System software | Cyclic interrupt @ 100 ms (default) | Triggers the FB call at a fixed rate |
FC3 ("Integrator") is the closest built-in primitive. It accepts an input value, integrates it with a cycle-time tag, and emits the running sum. Used as a leak-free integrator with a constant input, it produces a linear ramp. The downside is that FC3 is purely additive — it does not clamp, does not detect "reached target", and does not handle direction changes cleanly. For production code, write a dedicated FB as shown below.
Step 1: Define the Ramp Parameters
Five parameters fully describe a linear ramp on an analog output:
- Start value (V_start) — the engineering-units value of the AO at the moment the ramp is armed
- Target value (V_target) — the EU value to reach at the end of the ramp
- Ramp time (T_ramp) — the time to traverse from V_start to V_target
- Cycle time (T_cycle) — the OB execution period (typical 100 ms for OB35)
- Output range — the EU-to-raw mapping (0-10 V = 0-27648, 4-20 mA = 0-27648 with offset)
The ramp slope and per-cycle step are computed once at ramp start:
slope (EU/s) = (V_target - V_start) / T_ramp
step (EU/cycle) = slope × T_cycle = (V_target - V_start) / (T_ramp / T_cycle)
Worked example: ramp from 20 % to 80 % in 5 s with OB35 at 100 ms:
- V_start = 20.0, V_target = 80.0, T_ramp = 5.0 s, T_cycle = 0.1 s
- slope = (80 - 20) / 5 = 12.0 %/s
- step = 12.0 × 0.1 = 1.2 %/cycle
- Number of steps = 5 / 0.1 = 50 cycles
For a 0.3 s ramp (the original Unitronics / Click question in the source research), a 100 ms OB is too coarse (3 steps). Use OB38 (10 ms) for 30 steps, or OB36 (50 ms) for 6 steps, or OB32 (1000 ms) only for > 10 s ramps. The cycle time of the OB is set in HW Config > CPU Properties > Cyclic Interrupts.
Step 2: Select the Execution Timebase
Eight cyclic-interrupt OBs are available, with default cycle times:
| OB | Default cycle | Typical use | Notes |
|---|---|---|---|
| OB30 | free / configurable | Reserved for user config | Set in HW Config, range 1-60000 ms |
| OB31 | 5000 ms | Slow thermal ramps | Allows OB to be skipped for energy savings |
| OB32 | 1000 ms | 1-second process scans | Standard for slow setpoint changes |
| OB33 | 500 ms | Mid-speed process scans | Good balance for valve ramps > 5 s |
| OB34 | 200 ms | Fast process scans | Used for short ramps 1-5 s |
| OB35 | 100 ms | Default PID scan | Most common for general PID + ramp |
| OB36 | 50 ms | Fast actuator control | Requires CPU 315-2 DP or higher |
| OB37 | 20 ms | High-speed control | CPU 315-2 DP / 317-2 / 319-3 / 400 |
| OB38 | 10 ms | Very fast actuator control | CPU 315-2 DP / 317-2 / 319-3 / 400 |
Selection rule: T_cycle should be 1/30 to 1/100 of T_ramp. A 0.3 s ramp with 30-100 steps requires an OB cycle of 3-10 ms. On a CPU 314, the smallest usable OB cycle is 50 ms (OB36). On a CPU 317-2 PN/DP or S7-400 CPU, OB38 (10 ms) is available and is the right choice. The original Unitronics / Click 0.3 s ramp requirement (from the source research) maps cleanly to OB38 on an S7-300/400 with the right CPU.
Step 3: Implement the Ramp FB in STEP 7
The cleanest implementation is a Function Block written in SCL (Structured Control Language) under STEP 7 V5.5 or TIA Portal. The same logic can be expressed in STL or LAD; the SCL version is shown because it is readable and the integration step is unambiguous.
FUNCTION_BLOCK FB1000
{ S7_m_c := 'true' }
VERSION : '1.0'
VAR_INPUT
i_Enable : BOOL; // 1 = start or continue ramp
i_TargetEU : REAL; // Target in engineering units
i_RampTime : TIME; // Time to reach target
i_CycleTime : TIME; // OB cycle time
i_MinEU : REAL; // Lower clamp (EU)
i_MaxEU : REAL; // Upper clamp (EU)
i_EU_at0 : REAL; // EU value corresponding to raw 0
i_EU_at100 : REAL; // EU value corresponding to raw full-scale
i_Raw_0 : INT; // Raw value at EU_at0 (e.g. 0 for unipolar)
i_Raw_100 : INT; // Raw value at EU_at100 (e.g. 27648)
END_VAR
VAR_OUTPUT
q_CurrentEU : REAL; // Current ramped EU value
q_RawOut : INT; // Value to write to PQW
q_Busy : BOOL; // 1 = ramp in progress
q_Done : BOOL; // 1 = target reached this cycle
q_RateEU_s : REAL; // Effective rate (EU/s)
END_VAR
VAR
s_StartValue : REAL; // EU at start of this ramp
s_StepEU : REAL; // Per-cycle increment in EU
s_RampActive : BOOL; // 1 = ramp in progress
s_FirstScan : BOOL; // 1 = first cycle after enable / new target
END_VAR
BEGIN
IF i_Enable THEN
// Detect new ramp: enable just went high, or target changed
IF NOT s_RampActive OR s_FirstScan THEN
s_StartValue := q_CurrentEU;
IF TIME_TO_REAL(i_RampTime) > 0.0 THEN
s_StepEU := (i_TargetEU - s_StartValue)
/ (TIME_TO_REAL(i_RampTime)
/ TIME_TO_REAL(i_CycleTime));
ELSE
s_StepEU := (i_TargetEU - s_StartValue); // instant
END_IF;
s_RampActive := TRUE;
s_FirstScan := FALSE;
END_IF;
// Integrate one cycle
q_CurrentEU := q_CurrentEU + s_StepEU;
// Overshoot detection: if overshot, snap to target
IF (s_StepEU >= 0.0 AND q_CurrentEU >= i_TargetEU)
OR (s_StepEU < 0.0 AND q_CurrentEU <= i_TargetEU) THEN
q_CurrentEU := i_TargetEU;
s_RampActive := FALSE;
q_Done := TRUE;
ELSE
q_Done := FALSE;
END_IF;
// Clamp to configured range
IF q_CurrentEU > i_MaxEU THEN q_CurrentEU := i_MaxEU; END_IF;
IF q_CurrentEU < i_MinEU THEN q_CurrentEU := i_MinEU; END_IF;
q_Busy := s_RampActive;
ELSE
s_RampActive := FALSE;
s_FirstScan := TRUE;
q_Busy := FALSE;
q_Done := FALSE;
END_IF;
// Convert EU to raw counts (linear, with EU-at-0 / EU-at-100 anchors)
q_RawOut := REAL_TO_INT(
(q_CurrentEU - i_EU_at0)
/ (i_EU_at100 - i_EU_at0)
* INT_TO_REAL(i_Raw_100 - i_Raw_0)
+ INT_TO_REAL(i_Raw_0)
);
// Rate in EU/s
IF TIME_TO_REAL(i_RampTime) > 0.0 THEN
q_RateEU_s := (i_TargetEU - s_StartValue)
/ TIME_TO_REAL(i_RampTime);
ELSE
q_RateEU_s := 0.0;
END_IF;
END_FUNCTION_BLOCK
The same function in STL (the most compact expression, useful for CPU 312/314 with no SCL license):
// Called from OB35 (100 ms default)
L #i_Enable
JC RMP1
L 0
T #s_RampActive
JU CONV
RMP1: L #s_RampActive
L 1
==I // 1=continue, 0=new
JC INTEG
// New ramp: capture start value, compute step
L #q_CurrentEU
T #s_StartValue
L #i_TargetEU
L #s_StartValue
-R
L 1.0
T #s_StepEU // placeholder
L #i_TargetEU
L #s_StartValue
-R
L 0.1 // T_cycle in seconds; edit per OB
*R
L #i_RampTime
DTR
/R
T #s_StepEU
SET
S #s_RampActive
INTEG: L #q_CurrentEU
L #s_StepEU
+R
T #q_CurrentEU
CONV: L #q_CurrentEU
L 0.0
>=R
JC POS
L 0
JU WR
POS: L #q_CurrentEU
L 2764.8
*R
RND
WR: T PQW 272 // PERIPHERAL WRITE - mandatory for AO
BE
The LAD equivalent uses MOVE, ADD, GT, and LT blocks feeding a single MOVE block that targets the PQW address. The critical instruction is the one that writes the result: it must be a coil on a symbol typed as WORD with the symbolic name PQW 272, or a MOVE block with the OUT terminal pointing to PQW 272. The compiler will not warn if the programmer accidentally drops the P; only the runtime behaviour will expose the bug.
Step 4: Wire the FB to the Peripheral Output
The FB call lives in OB35 (or whichever cyclic OB the engineer chose). For a 0-10 V / 4-20 mA valve on SM332 channel 0 at PQW 272, the call is:
// OB35 - 100 ms cyclic interrupt
CALL FB 1000 , DB1000
i_Enable := M 100.0 // ramp-armed flag from HMI or sequence
i_TargetEU := MD 200 // target from HMI, REAL (0.0-100.0 %)
i_RampTime := T#5s // recipe parameter
i_CycleTime := T#100ms // matches OB35 setting
i_MinEU := 0.0
i_MaxEU := 100.0
i_EU_at0 := 0.0
i_EU_at100 := 100.0
i_Raw_0 := 0
i_Raw_100 := 27648
q_CurrentEU := MD 210
q_RawOut := MW 212
q_Busy := M 100.1
q_Done := M 100.2
q_RateEU_s := MD 220
L MW 212
T PQW 272 // PERIPHERAL WRITE to SM332 CH0
The T PQW 272 instruction is unconditional and runs in OB35, so the DAC is updated every cycle. The PID FB (FB41) can be inserted between q_RawOut and the peripheral write, or the PID can be the source of i_TargetEU with the ramp in front. The decision depends on whether the PID output itself should ramp, or only the operator's setpoint changes should ramp.
IW 272; that returns the process-image snapshot from the last OB1 refresh, which is stale. If a feedback read is required (e.g. to detect wire break on a current output), use L PIW 272 for an immediate read of the module's status/diagnostic byte. The first two bytes of an SM332 are always the analog value; bytes 2-3 are status / diagnostic.Step 5: Commissioning and Verification
Commissioning should follow a fixed sequence to expose the most common ramp bugs before they reach the field:
-
Open a Watch Table in STEP 7 / TIA Portal on DB1000. Force
i_Enable := 1,i_TargetEU := 50.0,i_RampTime := T#5s. Monitorq_CurrentEUandq_RawOut. Confirmq_CurrentEUincreases by 1.0 each OB35 cycle (5 %/s, 0.5 %/100 ms = 0.5 %/cycle here, scaled to match the parameters). -
Read the PQW back with a VAT. If the value matches
q_RawOutafter the OB35 boundary, the peripheral write is working. If the PQW stays at zero, the write is hitting the process image instead — re-check thePprefix. - Connect a digital multimeter or HART communicator to the field device. Confirm the current or voltage matches the expected value (50 % should be 12 mA on a 4-20 mA loop, 5.0 V on 0-10 V).
- Trigger a step change in the target from 50 % to 100 % via the HMI. Observe the field device for 5 seconds. The valve / drive / heater should follow the linear ramp with no audible chattering and no overshoot.
-
Test the negative ramp: from 100 % to 0 %. Confirm
q_CurrentEUdecreases monotonically and does not go negative (the lower clamp prevents it). -
Test direction change mid-ramp: while ramping from 0 % to 100 %, change the target to 50 %. The ramp should re-arm with a new
s_StartValueequal to the current value, and the slope should re-compute. If the output jumps, thes_FirstScanlogic is wrong. -
Test the disable path: drop
i_Enable.q_Busyshould clear,q_CurrentEUshould freeze at its current value, and the PQW should hold the last ramped value. The output should not jump to zero. - Test CPU STOP behaviour: with the CPU in STOP, the SM332 substitutes a configurable value (0, 100 %, or hold-last). Verify the substitute value is set correctly in HW Config > SM332 > Outputs > Behaviour on CPU STOP.
For a longer commissioning record, use the STEP 7 trace / TIA Portal trace to record q_CurrentEU and the corresponding PQW 272 over one ramp cycle. The curve should be a straight line from start to target, with no kinks at direction changes and no chatter at the end.
Output Value Clamping, Bumpless Transfer, and Limits
Three edge cases must be handled by the FB and not by external logic, because they will eventually be hit by every operator:
1. Clamping. The FB's i_MinEU and i_MaxEU inputs enforce the safe range of the AO, independent of the operator's target. A common pattern is to clamp to the actuator's mechanical limits (e.g. 5-95 % on a control valve to avoid seat hits). The raw output is also clipped to 0-27648 because REAL_TO_INT wraps modulo 2^16; a negative raw value would set the output to a large positive value at the DAC.
2. Bumpless transfer. When the operator hands off from manual (jog from HMI) to auto (PID), the ramp should not produce a step. The standard technique is to seed q_CurrentEU with the actual AO value (PIW of a paired input, or a readback from the drive) at the moment the FB is enabled, so the start value equals the current output.
3. Direction change. When the operator changes the target mid-ramp, the FB must re-initialize s_StartValue to the current value, not the value at the original arming. The s_FirstScan flag in the implementation above triggers this when the target differs by more than a deadband from the previous target.
A S-curve profile (jerk-limited ramp) is implemented by inserting a second integrator on the output of the first one, with the second integrator's input clamped to a maximum rate. This is the same approach used by Sinamics drives (p1115 / p1120 / p1121) and by the F-TM Servodrive's ramp-function generator. The linear ramp above is the degenerate case where the S-curve smoothing constant is zero.
Troubleshooting Matrix
| Symptom | Likely cause | Diagnostic | Fix |
|---|---|---|---|
| AO stays at 0 V or 4 mA | Wrote to QW instead of PQW | Open VAT on QW 272 and PQW 272 simultaneously; only PQW should be non-zero | Change T QW to T PQW in the OB35 call |
| AO stuck at 10 V or 20 mA | Output range misconfigured (e.g. bipolar on a unipolar field device) | HW Config > SM332 > Properties > Outputs > check "Type" and "Range" | Match module type to field device (0-10 V vs ±10 V, 0-20 mA vs 4-20 mA) |
| Ramp runs but is jerky (stairsteps visible on the field device) | OB cycle too long for ramp time | Check number of steps: T_ramp / T_cycle should be > 30 | Use faster OB (OB36/OB37/OB38) or longer T_ramp |
| AO overshoots target then settles back | No overshoot-detection logic; integrator overshoots then leaks | Monitor q_CurrentEU near the end of the ramp | Add overshoot-snap logic: if (step >=0 AND value >= target) then value := target; rampActive := false |
| AO negative or > 20 mA | q_RawOut not clamped before T PQW; integer wrap on negative | Watch q_RawOut; if it goes negative or > 27648 the DAC interprets it as the opposite extreme | Clamp q_RawOut to 0-27648 in the FB before T PQW |
| Ramp does not start; output is constant | i_Enable edge not detected; s_FirstScan logic never triggers | Force i_Enable FALSE then TRUE; check s_FirstScan in VAT | Reset s_FirstScan := TRUE when i_Enable goes from FALSE to TRUE; track previous i_Enable |
| Ramp time is wrong by an integer factor | T_cycle in the FB does not match the actual OB cycle time | Read T_cycle value passed to FB; compare to OB35 setting in HW Config | Update i_CycleTime in the OB35 call to match the configured OB cycle |
| OB1 takes longer than OB35 cycle; ramp stutters | CPU scan time too long; OB35 is queued | SFC6 + SFC7 to read OB1 runtime; compare to T_cycle | Reduce OB1 work, or use a faster CPU (CPU 315-2 DP or higher for OB36/OB37/OB38) |
| AO holds last value on CPU STOP | SM332 substitute value is "Hold last value" | Check HW Config > SM332 > Outputs > "Behaviour on CPU STOP" | Set substitute to 0 or 100% if safe-by-default is required |
| No voltage at the field device but PQW has the right value | Wiring error, or module is in diagnostic state | Check SF LED on SM332; read module diagnostic with SFC13 / RD_REC | Check 24 V supply to module load group; check shielding; check channel diagnostic |
Migration to S7-1500 / TIA Portal
On the S7-1500 generation, the same peripheral-access discipline is still required for AO modules, but the syntax changes:
-
PQW 272becomes%QW272(TIA Portal absolute addressing) - OB35 becomes the standard
OB "CyclicInterrupt"in TIA Portal, with cycle time set in the OB properties in nanoseconds - S7-1500 OB time resolution is 1 ms, with a minimum cyclic-interrupt cycle of 1 ms (vs 10 ms on S7-300 OB38)
- The standard library now includes the
PID_CompactandPID_3Stepblocks; for ramps, the engineering-team typically uses theSYSTEM_CLOCKblock with an integrator, or a self-written FB equivalent to the one above
The TIA Portal F-TM Servodrive ramp-function generator implements the same shape entirely in module firmware, offloading the PLC scan. For new designs, that is the right answer. For retrofit of an existing S7-300/400 ramp application, the FB above ports unchanged: only the address syntax needs updating.
Safety and Field Wiring Considerations
Three safety points often missed on the first revision of an analog-output ramp:
- Substitute value on CPU STOP — for a heating application, the safe state is 0 % output. For a cooling / valve-closing application, the safe state may be 100 % output. Set the SM332 substitute value in HW Config accordingly. The FB does not run in STOP, so it is the substitute value that defines field behaviour.
- Wire break on current outputs — on a 4-20 mA output, a wire break is detected by the module and signalled in the diagnostic byte. The S7 program can read this via SFC13 / RD_REC on diagnostic interrupt OB82 and force the ramp output to a safe value (typically 0) until the wiring is restored. A 0-10 V output cannot detect wire break, so use a 4-20 mA output where fail-safe is required.
- Galvanic isolation — analog outputs on SM332 / SM432 are not isolated channel-to-channel by default; they share a common ground. For a multi-channel application driving devices at different potentials, use the 6ES7332-8TF00-0AB0 (high-speed, isolated) or fit external signal isolators. Without isolation, ground loops can add offsets that the FB's output-to-raw conversion will faithfully write to the DAC.
Why does my analog output stay at zero even though the FB output is correct in the VAT?
You are writing to the process image with T QW 272 instead of the peripheral output with T PQW 272. Analog output modules on S7-300 (SM332) and S7-400 (SM432) are mapped to the peripheral address area and only respond to PQW writes. Replace QW with PQW on every write to an analog output channel. See the Siemens Support entry 18325417 for the official explanation.
How fast can I configure OB35 on a CPU 314 vs a CPU 317-2 PN/DP?
OB35 has a fixed default cycle of 100 ms on every S7-300/400 CPU. The configurable range is 1-60000 ms (1 ms steps), but the actual minimum cycle you can run is constrained by the OB1 worst-case execution time. A CPU 314 reliably runs OB36 (50 ms) but not OB37 (20 ms) or OB38 (10 ms) on a typical program. A CPU 317-2 PN/DP or 319-3 PN/DP can run OB38 (10 ms) with adequate headroom. A CPU 412-3H or 416-3 can run OB38 (10 ms) at full duty. The setting is in HW Config > CPU Properties > Cyclic Interrupts.
Can I write a 0-10 V ramp with only 5 steps visible on the field device?
Technically yes, but it is a stair-step not a ramp. With a 0-10 V output and OB35 (100 ms), a 0.5 s ramp has only 5 steps, and a 0.3 s ramp has 3 steps. The field device will see discrete jumps of 2 V or 3.3 V per step. For a true smooth ramp on a 0.3 s timescale, use OB38 (10 ms) on a CPU 317 or higher to get 30 steps (1 V per 30 ms). The trade-off is higher CPU scan time consumption.
What is the difference between ramp rate per cycle and ramp rate per second?
Ramp rate per cycle is the EU increment added to the integrator each OB execution. Ramp rate per second is the same value divided by T_cycle. The FB above exposes both: q_RateEU_s is in EU/s, and the internal s_StepEU is in EU/cycle. Engineers usually specify ramps in EU/s, but the FB must integrate in EU/cycle because the integrator only fires once per OB. Specify the ramp in T#ns units in the HMI, then convert internally to the per-cycle step.
Can I implement a S-curve (jerk-limited) ramp with the same FB?
Yes, by adding a second integrator and clamping its input to a maximum dV/dt. The first integrator produces the target velocity; the second integrator produces the target position. The clamp on the first integrator input produces the trapezoidal / S-curve velocity profile that limits jerk. The same approach is used in the TIA Portal F-TM Servodrive ramp-function generator and in Sinamics drives (p1115, p1120, p1121). For a heater or valve, a linear ramp is normally sufficient; a S-curve is required only for high-inertia mechanical systems.